CHOOSING A SITE

Select the signal receiver mounting location according to the following conditions:

• Install the signal receiver, which has a built-in temperature sensor, near the intake vent 

where there is convection of air and it can get an accurate reading of the room’s temperature. 
If the intake vent is in another room or the unit cannot be installed near the intake vent for any 
other reason, install it 1.5m above the floor on a wall where there is convection.

• In order to get an accurate reading of the room’s temperature, install the 

signal receiver in a location where it is not exposed directly to cold or hot air 
from the air discharge grille or to direct sunlight.

• Since the receiver has a built-in light receptor to receive signals from the wireless remote 

controller, do not mount it in a location where the signal may be blocked by a curtain, etc.

Caution

If the signal receiver is not installed in a location where there is convection of air, it may be unable to get an accurate reading of the room’s temperature.

• Turn on all the fluorescent lamps in the room, if any, and find the site where remote controller signals are properly received 

by the indoor unit (within 4 metres).

• For outdoor unit installation, see the installation manual supplied with the outdoor unit.

PREPARATIONS BEFORE INSTALLATION

Relation of the unit to the suspension bolt positions. 

• Install the inspection opening on the control box side where 

maintenance and inspection of the control box are easy.  Install the 
inspection opening also in the lower part of the unit.

Make sure the range of the unit’s external static 
pressure is not exceeded.

(See the technical documentation for the range of the external 
static pressure setting.)

Open the installation hole. (Pre-set ceilings)

• Once the installation hole is opened in the ceiling where the unit 

is to be installed, pass refrigerant piping, drain piping, 
transmission wiring, and remote controller wiring (unneeded if 
using a wireless remote controller) to the unit’s piping and 
wiring holes.See 

“REFRIGERANT PIPING WORK”

“DRAIN 

PIPING WORK”

, and 

“WIRING”

.

• After opening the ceiling hole, make sure ceiling is level if 

needed. It might be necessary to reinforce the ceiling frame to 
prevent shaking.Consult an architect or carpenter for details.

Install the suspension bolts.

(Use W3/8 to M10 suspension bolts.)
Use a hole-in-anchor, sunken insert, sunken anchor for existing 
ceilings, and a sunken insert, sunken anchor or other part to be 
procured in the field to reinforce the ceiling to bearing the weight 
of the unit. (Refer to Fig.)

Mount chamber lid

 and air filter 

(accessory).

For bottom intake, replace the chamber lid 
in the procedure listed in Fig.
(1)Remove the chamber lid. (7 locations)
(2)Reattached the removed chamber lid in 

the orientation shown in Fig. (7 locations)

Air discharge grille: 
Wooden or plastic grille is recommended 
because condensation may occur 
depending on humidity conditions.

Wireless remote controller

Outdoor unit

B

A

620

500

450×450

(Inspection 

opening size)

Air discharge

Suspension
bolt pitch

(length : mm)

Air inlet

Control box

(Suspension bolt pitch )

Ceiling

620

A

Allow view 

Inspection door

(Ceiling opening)

SERVICE SPACE

Model

25 · 35 · 50 type

60 type

A

900

1100

B

940

1140

(length: mm)

Note: All the above parts are field supplied.

Suspension bolt

Long nut or turn-buckle

Anchor bolt

Indoor unit

Ceiling slab

Air inlet

(1)

Air discharge

Chamber lid

(2)

Air discharge

Air inlet

Chamber lid

01_EN_3P132003-2N.fm  Page 3  Tuesday, December 5, 2006  2:02 PM

Summary of Contents for Inverter FDXS25CVMB

Page 1: ...KS60CVMB English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Monta...

Page 2: ...ita ku Osaka 530 8323 Japan 3P132004 2C FDXS25CVMB FDXS35CVMB FDKS25CVMB FDKS35CVMB CDXS50CVMB CDXS60CVMB CDKS50CVMB CDKS60CVMB FDXS25CAVMB FDXS35CAVMB FDKS25CAVMB FDKS35CAVMB Noboru Murata Manager Qu...

Page 3: ...be sure to shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrica...

Page 4: ...he conditions under which the electric wave is generated even if a one meter allowance is maintained Use suspension bolts to install the unit Check whether or not the ceiling is strong enough to suppo...

Page 5: ...pressure is not exceeded See the technical documentation for the range of the external static pressure setting Open the installation hole Pre set ceilings Once the installation hole is opened in the c...

Page 6: ...d in one room one of the two wireless remote controllers can be easily set for another addresses Air inlet 3 Air discharge Air discharge Air inlet Anti sweat material included with the product Anti sw...

Page 7: ...tch out for in particular is if it is installed so that the slope is not in the direction of the drain piping as this might cause leaking Tighten the upper nut Mounting the receiver Mount the receiver...

Page 8: ...REFRIGERANT PIPING 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare Use refrigeration oil for R410A 2 Align the centres of both flares and tighten...

Page 9: ...he refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation when installing the unit near bathrooms kitchens and other similar locations Refer to the fo...

Page 10: ...er to leak Drain piping passing indoors Drain sockets Referring the figure below insulate the metal clamp and drain hose using the included large sealing pad PRECAUTIONS Drain piping connections Do no...

Page 11: ...y is at least 50 in a gravimetric technique Outlet side Connect the duct according to the inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape o...

Page 12: ...xt pull the wires into the unit through the wiring through hole and connect to the power wiring terminal block 4P Warning Do not use tapped wires stand wires extensioncords or starbust connections as...

Page 13: ...If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air...

Page 14: ...0701 HT 3P132003 2N M04B108D Two dimensional bar code is a code for manufacturing...

Reviews: