REFRIGERANT PIPING WORK 

3) After the work is finished, make sure to check that there is no 

gas leak.

4) After checking for gas leaks, be sure to insulate the pipe connections.

• Insulate using the insulation for fitting included with the liquid and gas pipes. Besides, make sure the insulation for fitting 

on the liquid and gas piping has its seams facing up.
(Tighten both edges with clamp.)

• For the gas piping, wrap the medium sealing pad over the insulation for fitting (flare nut part).

Caution

Be sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

Cautions on Pipe Handling

• Protect the open end of the pipe against dust and moisture.

(Tighten both edges with clamp.)

• All pipe bends should be as gentle as possible. Use a pipe bender for 

bending.
(Bending radius should be 30 to 40 mm or larger.)

Selection of Copper and Heat Insulation materials

When using commercial copper pipes and fittings, observe the following:
• Insulation material: Polyethylene foam

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045 kcal/mh°C)
Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

• Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below.

Also, when subject to high humidity, heat insulation of the refrigerant 
piping (the unit piping and branch piping) must be further reinforced.
Reinforce the insulation when installing the unit near bathrooms, 
kitchens, and other similar locations.
Refer to the following:

• 30°C, more than 75% RH: 20 mm Min. in thickness

If the insulation is not sufficient, condensation may form on the surface 
of the insulation.

• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Coat here with 
refrigeration machine oil

Torque wrench

Piping union

Flare nut

Spanner

Gas pipe

Liquid pipe

Piping insulation 
material (main unit)

Attach to base

Flare nut connection

Turn seams up

Insulation for fitting 

(attached)

Clamp 

Piping insulation material
(Field supplied)

Gas Piping Insulation Procedure

(attached)

Main unit

Clamp (attached)

Flare nut connection

Turn seams up

Piping insulation material
(Field supplied)

Piping insulation 
material (main unit)

Attach to base

Main unit

Insulation for fitting 
(attached)

Liquid Piping Insulation Procedure

Small sealing pad 

Measure the length of the gas 
pipe as you will have to cover 
it with the sealing tape.

(attached)

Wrap the sealing 
tape around the 
gas pipe.

Main unit

Wall

If no flare cap is 
available, cover 
the flare mouth 
with tape to keep 
dirt or water out.

Be sure to 
place a cap.

Rain

Gas side

Gas pipe thermal insulation

Liquid side

Liquid pipe

thermal insulation

25/35 class

50/60 class

O.D. 9.5mm

O.D. 12.7mm

25/35 class

50/60 class

I.D. 12-15mm

I.D. 14-16mm

Thickness 0.8mm

O.D. 6.4mm

I.D. 8-10mm

Thickness 10mm Min.

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wiring

01_EN_3P132003-2N.fm  Page 7  Tuesday, December 5, 2006  2:02 PM

Summary of Contents for Inverter FDXS25CVMB

Page 1: ...KS60CVMB English Deutsch Fran ais Nederlands Espa ol Italiano Portugues Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Monta...

Page 2: ...ita ku Osaka 530 8323 Japan 3P132004 2C FDXS25CVMB FDXS35CVMB FDKS25CVMB FDKS35CVMB CDXS50CVMB CDXS60CVMB CDKS50CVMB CDKS60CVMB FDXS25CAVMB FDXS35CAVMB FDKS25CAVMB FDKS35CAVMB Noboru Murata Manager Qu...

Page 3: ...be sure to shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrica...

Page 4: ...he conditions under which the electric wave is generated even if a one meter allowance is maintained Use suspension bolts to install the unit Check whether or not the ceiling is strong enough to suppo...

Page 5: ...pressure is not exceeded See the technical documentation for the range of the external static pressure setting Open the installation hole Pre set ceilings Once the installation hole is opened in the c...

Page 6: ...d in one room one of the two wireless remote controllers can be easily set for another addresses Air inlet 3 Air discharge Air discharge Air inlet Anti sweat material included with the product Anti sw...

Page 7: ...tch out for in particular is if it is installed so that the slope is not in the direction of the drain piping as this might cause leaking Tighten the upper nut Mounting the receiver Mount the receiver...

Page 8: ...REFRIGERANT PIPING 1 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces of the flare Use refrigeration oil for R410A 2 Align the centres of both flares and tighten...

Page 9: ...he refrigerant piping the unit piping and branch piping must be further reinforced Reinforce the insulation when installing the unit near bathrooms kitchens and other similar locations Refer to the fo...

Page 10: ...er to leak Drain piping passing indoors Drain sockets Referring the figure below insulate the metal clamp and drain hose using the included large sealing pad PRECAUTIONS Drain piping connections Do no...

Page 11: ...y is at least 50 in a gravimetric technique Outlet side Connect the duct according to the inside of the outlet side flange Wrap the outlet side flange and the duct connection area with aluminum tape o...

Page 12: ...xt pull the wires into the unit through the wiring through hole and connect to the power wiring terminal block 4P Warning Do not use tapped wires stand wires extensioncords or starbust connections as...

Page 13: ...If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air...

Page 14: ...0701 HT 3P132003 2N M04B108D Two dimensional bar code is a code for manufacturing...

Reviews: