15
English
• If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of terminals.
• Do not carry out soldering finish when stranded wiring are used.
•
Power supply wiring, earth wiring
Remove the control box lid, match the symbol to that of the
power supply terminal block (X2M) and connect the wiring.
Connect the earth wiring also to the power supply terminal
block (X2M). Then, lead the wiring into the indoor unit
through the hole bored on the cover for penetrating piping
according to the section “
6. REFRIGERANT PIPING WORK
”
and bind the wiring with the clamp (4).
•
Remote controller wiring, transmission wiring.
Connect the remote controller wiring to [P1 · P2] and the trans-
mission wiring to [F1 · F2] of the terminal block (X1M) for
remote controller and transmission wiring. Bind the remote
controller wiring and the transmission wiring with the clamp (4).
•
Sticking non woven fabric (15).
To prevent wiring from floating, stick non woven fabric (15).
CAUTION
• Never connect the power supply wiring to the terminal
block for remote controller/transmission wiring (X1M).
It may damage the total system.
• Do not connect the remote controller/transmission wiring
to the wrong terminal block.
Tightening
torque (N · m)
Terminal block for remote controller and
transmission wiring
0.88 ± 0.08
Terminal for power supply
1.47 ± 0.14
Earth terminal
1.47 ± 0.14
Non woven fabric (15)
Start sticking from the
radius ending line.
< Non woven fabric (15) sticking method >
Power supply
terminal block (X2M)
Fig. 38
Terminal block for remote
controller/transmission wiring (X1M)
Power supply terminal block (X2M)
Clamp (4) (accessory)
Remote controller wiring
Transmission wiring
Power supply wiring ·
Earth wiring
< Power supply wiring · Earth wiring · Remote
controller wiring · Transmission wiring >
Clamp (4)
(accessory)
Power supply wiring ·
Earth wiring
Clamp (4) (accessory)
< Remote controller wiring ·
Transmission wiring >
Prohibited
(Sheath peeling allowance)
Approx. 7mm
Earth terminal
Earth wiring
(Sheath peeling allowance)
Power supply
wiring
Sheathed part
Earth wiring
< Power supply wiring · Earth wiring >
L
N
After the wiring are fixed,
cut the extra part.
The part of the wiring
shown with “ ” must
be orderly formed so
that they may not be
tensioned.
After the cover is
peeled, twist the
wiring.
• Do not connect power supply
wiring (high voltage).
Bind the power supply wiring and the
earth wiring, and the remote controller
and the transmission wiring.
After the wiring are fixed, cut the
extra part.
After the wiring are fixed, cut the
extra part.
Terminal block for remote
controller/transmission
wiring (X1M)
Sheathed part of the remote
controller wiring or the
transmission wiring
Non woven fabric (15)
sticking reference