background image

19

English

< FIELD SETTING >



After turn on the power supply, carry out field setting from 

the remote controller according to the installation state.



Carry out setting at 3 places, “Mode No.”, “FIRST CODE No.” 
and “SECOND CODE No.”.
The settings shown by “ 

 ” in the table indicate those 

when shipped from the factory.

The method of setting procedure and operation is shown in 
the installation manual attached to the remote controller.
(Note) Though setting of “Mode No.” is carried out as a 

group, if you intend to carry out individual setting by 
each indoor unit or confirmation after setting, carry 
out setting with the Mode No. shown in the parenthe-
sis ( ). 

In case of remote control, for changeover of input to 
FORCED OFF or to ON/OFF OPERATION.
[1] Enter into the field setting mode with the remote controller.
[2] Select Mode No. “12”.
[3] Set the FIRST CODE No. to “1”.
[4-1] For FORCE OFF, set the SECOND CODE No. to “01”.
[4-2] For ON/OFF OPERATION, set the SECOND CODE 

No. to “02”.

(It is set to FORCED OFF when shipped from the factory.)

Ask your customer to keep the instruction attached to the 
remote controller together with the operation manual.

Do not carry out setting other than those shown in the table.

10-1 SETTING OF CEILING HEIGHT

Set the SECOND CODE No. according to the ceiling height 
as shown in the Table 3.

Table 3

10-2 SETTING WHEN AN OPTIONAL ACCESSORY IS 

ATTACHED

For setting when attaching an optional accessory, refer to the 
installation manual attached to the optional accessory.

10-3 WHEN USING WIRELESS REMOTE CONTROL-

LER

When using a wireless remote controller, it is necessary to 
set the wireless remote controller address.
Refer to the installation manual attached to the wireless 
remote controller.

10-4 SETTING FAN SPEED DURING THERMOSTAT 

OFF

Set the fan speed according to the using environment after 
consultation with your customer.

When the fan speed is changed, explain the fan speed rate to 
your customer.

Table 4

10-5 SETTING FILTER SIGN

A message to inform the air filter cleaning time will be indi-
cated on the remote controller.

Set the SECOND CODE No. shown in the Table 5 according 
to the amount of dust or pollution in the room.

Though the indoor unit is equipped with the long life filter, it is 
necessary to periodically clean the filter to avoid clogging of 
the filter. Please also explain the set time to the customer.

The periodical filter cleaning time can be shortened depend-
ing on the environment.

Table 5

* Use “No indication” setting when cleaning indication is not 

necessary such as the case of periodical cleaning being car-
ried out.

10-6 SETTING AIR DISCHARGE DIRECTION

When changing air discharge setting (2-way or 3-way dis-
charge), set the SECOND CODE No. as shown in the Table 
6.

Table 6

Setting

Ceiling height (m)

Mode 

No.

FIRST 
CODE 

No.

SECOND 

CODE No.

FXUQ71AVEB FXUQ100AVEB

Standard

2.7 or less

3.2 or less

13 (23)

0

01

High 

ceiling 1

2.7 - 3.0

3.2 - 3.6

02

High 

ceiling 2

3.0 - 3.5

3.6 - 4.0

03

Setting

Mode No.

FIRST 

CODE No.

SECOND 

CODE No.

Fan speed during 
cooling thermo-
stat OFF

LL (Extra 

low)

12 (22)

6

01

Setting

02

Fan speed during 
heating thermo-
stat OFF

LL (Extra 

low)

12 (22)

3

01

Setting

02

Contamination

Filter hours

(long life type)

Mode No.

FIRST 
CODE 

No.

SEC-

OND 

CODE 

No.

Normal

Approx. 

2500 hrs

10 (20)

0

01

More contami-

nated

Approx. 

1250 hrs

02

With indication

3

01

No indication*

02

Setting

Mode No.

FIRST CODE 

No.

SECOND 

CODE No.

4-way air 

discharge

13 (23)

1

01

3-way air 

discharge

02

2-way air 

discharge

03

01_EN_3P177351-7S.fm  Page 19  Thursday, March 21, 2013  10:19 PM

Summary of Contents for FXUQ100AVEB

Page 1: ...RE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACCESSIBILE PER RIFERIMENTO FUTURO ΔΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟΔΗΓΙΕΣ ΠΡΙΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΦΥΛΑΞΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙΔΙΟ ΣΕ ΒΟΛΙΚΟ ΜΕΡΟΣ ΓΙΑ ΜΕΛΛΟΝΤΙΚΗ ΑΝΑΦΟΡΑ LEES DEZE INSTRUCTIES ZOGVULDIG DOOR VOORDAT MET DE INSTALLATIE WORDT BEGONNEN BEWAAR DEZE HANDLEIDING VOOR TOEKOMSTIG GEBRUIK OP EEN GESCHIKTE PLAATS ONDER HANDBEREIK LEIA ATENTAMENTE ESTAS INS...

Page 2: ...air condi tioner falling down water leakage electric shocks a fire etc Install the air conditioner on a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleasant chattering noise Carry out the specified installation work in consideration of strong winds typ...

Page 3: ...llation work is R410A The air conditioner will not properly operate if a wrong refrig erant is used For installation of the outdoor unit refer to the installation manual attached to the outdoor unit Do not throw away the accessories until the installation work is completed After the indoor unit is carried into the room to avoid the indoor unit from getting damaged take measures to protect the indo...

Page 4: ...s not heat Is the insulation of refrigerant piping and drain piping com pletely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner Does not operate burnout Are you sure that there is no wrong wiring nor piping or no loose wiring Does not operate burnout Is earthing complete...

Page 5: ...te controller For details see the section 10 FIELD SETTING AND TEST OPERATION Caution Since there are some restriction on the piping connection side make sure to select the air dis charge pattern from the Fig 3 The names of air outlet are shown in inscription by the num ber of marks on the underside of the air outlet Refer to the Fig 4 4 Use hanging bolts for installation Investigate if the instal...

Page 6: ...grille Refer to Fig 8 Slide the two suction grille fixing knobs toward inner direction as shown by an arrow lifting upward At the same time have another person lift the tape stuck to the center of air outlet When the suction grille is opened to approximately 45 the grille can be removed from the unit Remove the 4 corner covers 835 hanging bolt pitch 835 hanging bolt pitch 950 950 unit mm Gas pipin...

Page 7: ...t the bent part 2 places at both ends of the blocking material into the clearance between the lower decoration panel and the drain pan until you hear a clicking sound When doing this work lift the end of the lower decoration panel slightly and insert the blocking material If it is difficult to insert it first loosen the screws on the both sides of the lower decoration panel and then insert it 3 In...

Page 8: ...t the hangers on the air outlet side and hang them tentatively Insert the remaining 2 hanging bolts into the hanger and fix the underside washers for the hanger 3 and the nuts Fig 12 Drain pan Lower decoration panel Insulation Projected part Blocking material Projected part Upper decoration panel 2 1 3 1 2 Insert 1 2 3 Blocking material Insert Projected part Upper decoration panel Insulation Lower...

Page 9: ... which heat resistant temperature is not less than 120 C For use under high humidity strengthen the insulation mate rial for refrigerant piping If not strengthened the surface of insulation material may sweat Before installation work make sure that the refrigerant is R410A Unless the refrigerant is R410A the normal opera tion cannot be expected CAUTION This air conditioner is a dedicated model for...

Page 10: ...ng torque sud denly increases From that position tighten the nut additionally the angle shown in Table 2 After the work is finished check securely that there is no gas leak If the nut is not tightened as instructed it may cause slow refrigerant leak and result in malfunction such as does not cool or heat Table 2 CAUTION Insulation of field piping must be carried out up to the connection inside the...

Page 11: ...rial unit side Liquid side piping insulating method Do not leave clearance Clamp 4 accessory Sealing material Small 9 accessory Flare nut connection Bring the seam to the top Wrap the sealing material from the root of the unit to the part of flare nut connection For prevention of sweating do not expose the piping Tighten the section where the piping insulating material and the joint insulating mat...

Page 12: ...efer to the outdoor unit installation manual or technical document for refrigerant piping CAUTION Do not use antioxidant when brazing piping It may result in malfunction of components and clogging of piping due to residue 7 DRAIN PIPING WORK 1 Carry out drain piping Carry out drain piping so that drainage can ensured Drain piping can be connected from 3 directions Refer to Fig 25 26 and 27 Select ...

Page 13: ...rs more than the width of metal clamp 2 leaving 10 15 mm from the tip of the elbow 10 without wrapping as shown in Fig 30 2 Insert the drain hose 1 and the elbow 10 to the root of the drain socket Tighten the metal clamp 2 within the taped range of hose inserted tip with the torque 1 35 0 15N m 135 15N cm Refer to Fig 25 26 27 and 31 Do not tighten the metal clamp 2 with the torque more than the s...

Page 14: ...ontrol box lid and connect the single phase power supply to the terminal L N on the terminal block X2M Connect the earth wiring to the earth terminal Refer to Fig 35 2 Make sure the control box lid is closed before turning on the power supply Fig 32 1 Section A A of Fig 31 Tightened part In case of bending the tip approx 90 Bend the tip without tearing the sealing material Large 8 Fig 32 2 Section...

Page 15: ...installation manual attached to the remote controller Do not touch the Printed Circuit Board assembly It may cause malfunction 8 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 8 3 SPECIFICATION FOR FIELD SUPPLIED FUSES AND WIRING The lengths of remote controller wiring and transmission wiring are as follows 1 Remote control...

Page 16: ...nd transmission wiring 0 88 0 08 Terminal for power supply 1 47 0 14 Earth terminal 1 47 0 14 Non woven fabric 15 Start sticking from the radius ending line Non woven fabric 15 sticking method Power supply terminal block X2M Fig 38 Terminal block for remote controller transmission wiring X1M Power supply terminal block X2M Clamp 4 accessory Remote controller wiring Transmission wiring Power supply...

Page 17: ...is used for 1 indoor unit No 2 system When carrying out group control or 2 remote controllers control No 3 system When BS unit is used NOTE Remote controller wiring and transmission wiring do not have polarity WARNING Be sure to install an earth leakage circuit breaker Failure to do so may cause electric shocks and a fire Sealing material Small 9 Remote controller transmission wiring Power supply ...

Page 18: ...ted to the remote controller 8 8 FOR REMOTE CONTROL FORCED OFF OR ON OFF OPERATION 1 Wiring method and specification Remote control is available by connecting the external input to the terminals T1 and T2 on the terminal block for remote controller and transmission wiring 2 Actuation Input A of FORCED OFF and ON OFF OPERATION will be as the table shown below 3 How to choose FORCED OFF or ON OFF OP...

Page 19: ...AUTION Before carrying out field setting check the items mentioned in the clause 2 1 Items to be checked after the installation work is completed on page 3 Check if all the installation and piping works for the air condi tioner are completed Check if the control box lids of the air conditioner are closed Fig 45 Piping penetrating place Piping penetrating place Cut with saw blade Cut with a saw bla...

Page 20: ...ual attached to the wireless remote controller 10 4 SETTING FAN SPEED DURING THERMOSTAT OFF Set the fan speed according to the using environment after consultation with your customer When the fan speed is changed explain the fan speed rate to your customer Table 4 10 5 SETTING FILTER SIGN A message to inform the air filter cleaning time will be indi cated on the remote controller Set the SECOND CO...

Page 21: ... and leakage To the operator carrying out test operation After test operation is completed before delivering the air conditioner to the customer confirm that the control box lid is closed In addition explain the power supply status power supply ON OFF to the customer 11 WIRING DIAGRAM Refer to Fig 48 Remote controller indication Details Though the central ized control is not carried out the lamp t...

Page 22: ...H WIRELESS ADDRESS SET R1T CONNECTOR WIRELESS REMOTE CONTROLLER CONNECTOR POWER SUPPLY FOR ADAPTOR X24A X35A WIRING DIAGRAM WIRELESS REMOTE CONTROLLER RECEIVER DISPLAY UNIT INDOOR UNIT 2 IN CASE USING CENTRAL REMOTE CONTROLLER CONNECT IT TO THE UNIT IN ACCORDANCE WITH THE ATTACHED INSTALLATION MANUAL 3 IN CASE OF MAIN SUB CHANGEOVER SEE THE INSTALLATION MANUAL ATTACHED TO REMOTE CONTROLLER 4 SYMBO...

Page 23: ... 1303 HT 3P177351 7S EM12A004A 00_CV_3P177351 7S fm Page 2 Friday March 8 2013 5 15 PM ...

Reviews: