background image

9

English

• 

After leak test, referring to 

Fig. 11

, insulate both the 

gas and liquid piping connection with the attached joint 
insulating material (4) and (5) to prevent the pipings from 

getting exposed.

 

Then, tighten both the ends of insulating material with 
the clamp (8).

• 

Wrap the sealing material (Medium) (7) around the joint 

insulating material (4) and (5) (flare nut section), both the 

gas and liquid piping.

• 

Make sure to bring the seam of joint insulating material 
(4) and (5) to the top.

Joint insulating 

material (4)
(Accessory)

Gas piping

Liquid piping

Liquid piping insulating method

Indoor unit

Indoor unit

Clamp (8)
(Accessory)

Sealing 

material (7) 

Medium
(Accessory)

Clamp (8) 
(Accessory)

Piping 

insulating 

material
(Field supply)

Gas piping insulating method

Joint insulating 

material (5) 
(Accessory)

Piping insulating 

material (Main unit)

Bring the 

seam 

to the top.

Flare nut 

connection

Piping 

insulating 

material 
(Field supply)

Do not leave 

clearance.

Flare nut 

connection

Bring the 

seam 

to the top.

Do not leave 

clearance.

Piping insulating 

material (Main unit)

Sealing material

(7) Medium
(Accessory)

Wind around the 

piping until top of the 

flare nut connection, 

beginning at the base.

Do not expose the 

piping in order to 

prevent the vapor 

condensation.

Tighten the portion 

where overlapped by 

the piping insulating 

material.

Tighten the portion 

where overlapped by 

the piping insulating 

material.

Do not expose the 

piping in order to 

prevent the vapor 

condensation.

Wind around the 

piping, beginning 

at the base.

Fig. 11

• 

Before brazing refrigerant piping, have nitrogen flow 

through the refrigerant piping and substitute air with 
nitrogen (NOTE 1) 

(Refer to Fig. 12)

. Then, carry out 

brazing (NOTE 2). 

After all the brazing works are finished, carry out flare 

connection with the indoor unit. 

(Refer to Fig. 11)

Pressure reducing valve

Nitrogen

Taping

Stop valve

Brazing place

Nitrogen

Refrigerant piping

Fig. 12

NOTE 

1. 

The proper pressure for having nitrogen flow through 
the piping is approximately 2.9 psi (0.02 MPa) , a pres

-

sure that makes one feel like slight breeze and can be 
obtained through a pressure reducing valve.

2. 

Do not use flux when brazing refrigerant piping.

 

Use phosphor copper brazing filler metal (BCuP-2/
B-Cu93P-710/795: ISO 3677) that does not require flux.

 

(If chlorinated flux is used, the piping will be corroded 
and, in addition if fluorine is contained, the refrig erant 

oil will be deteriorated and the refrigerant circuit will be 
affected badly.)

3. 

When carrying out air tight test of refrigerant piping 
and the indoor unit after the installation of indoor unit is 

finished, confirm the connecting outdoor unit installation 

manual for test pressure. 
Refer to also the outdoor unit installation manual or tech-
nical document for refrigerant piping.

4. 

In case of refrigerant shortage due to forgetting addition-
al refrigerant charge etc., it will result in malfunc tion such 
as does not cool or does not heat. 
Refer to the outdoor unit installation manual or technical 
document for refrigerant piping.

 CAUTION

Do not use antioxidant when brazing piping.

It may result in malfunction of components and clogging of 
piping due to residue.

01_EN_3P493125-6E.indd   9

2022/08/03   10:36:09

Summary of Contents for FXMQ15TBVJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...ere injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due t...

Page 3: ...Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required...

Page 4: ...ctric parts may be damaged 2 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Name 1 Metal clamp 2 Drain hose 3 Duct flange connection screw Quantity 1 pc 1 pc See belo...

Page 5: ...he optional accessory and make field settings as needed Is the remote controller icon displayed Is the re mote controller connected to the master unit if the system is in simultaneous multi operation...

Page 6: ...ighting type inverter or rapid start type fluorescent lamp is installed 2 Use suspension bolts for installation Investigate if the installation place can withstand the weight of the indoor unit and if...

Page 7: ...ain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the piping connection port and wiring connection port of the indoor...

Page 8: ...spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust so that the unit is...

Page 9: ...a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Spanner Flare...

Page 10: ...Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE 2 After all the brazing...

Page 11: ...ig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put the metal clamp 1 to t...

Page 12: ...ate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection do not connect the drain...

Page 13: ...y not come off 3 Gradually pour 1 4 gal 1 of water from the dis charge into the drain pan and be careful spraying water to the electric components such as drain pump Refer to Fig 18 4 When the power s...

Page 14: ...ation material Field supply Suction Discharge Screws for duct anges 3 Accessory Screws for duct anges 3 Accessory Flange on discharge side Provided with the unit Fig 20 CAUTION Connect the flange and...

Page 15: ...unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insulated thickness 1 16 in 1 mm or more 9 4 WIRING CONNECTION METHOD CAUTION FOR WIRING F...

Page 16: ...ture if you have difficulty in performing this step Screws 2 locations Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control bo...

Page 17: ...1 P F 2 F 1 P L1 F 1 2 T 2 T 1 P P 2 1 F 2 L2 F L1 1 2 T T P Remote controller Remote controller Remote controller L1 L2 L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller...

Page 18: ...on Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC 15 V 1 mA 2 Actuation...

Page 19: ...ill be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume...

Page 20: ...arly if the indication is one of those shown in the Table 13 it may be an error in the electrical wiring or the power supply is disconnected Therefore recheck wiring Table 13 Remote controller indicat...

Page 21: ...2209 HT 3P493125 6E EM21A039A Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P493125 6E indd 2 2022 08 03 10 34 56...

Reviews: