10-1 Settings for external static pressure

• 

Make settings in either method (a) or method (b).

(a) Make settings with Air volume automatic adjust-

ment function.

“Air volume automatic adjustment” function: The air volume 
is adjusted to the rated air volume automatically.

 CAUTION

• 

Be sure to check that the external static pressure is within 
the specification range before making settings. The external 

static pressure will not be automatically adjusted and air 

volume insufficiency or water leakage may result if the 
external static pressure is outside the range. (Refer to the 
technical document for the setting range of external static 

pressure.)

(1) 

Check that the electrical wiring and duct work have been 
completed.  
(If the closing damper is set midway, be sure to check that 
the damper is opened. Furthermore, check that the air 

passage on the suction side is provided with an air filter 
(field supply)).

(2) 

If air conditioner has more than one discharge and suc-
tion, be sure to make adjustments so that the air volume 
ratio of each discharge and the corresponding suction 
will conform to the designed air volume ratio. 
In that case, set the operating mode to “Fan”. (In the case 
of changing the air volume, press the fan speed button on 
the remote controller and change the current selection to 
“High”, “Medium”, or “Low”.)

(3) 

Make settings to adjust the air volume automatically. 
After setting the operating mode to “Fan”, set the air 

conditioner to field setting mode with the operation of the 

air conditioner stopped. Select Mode No. [21] (11 in the 
case of batch settings), select FIRST CODE No. “7”, and 
set the SECOND CODE No. to “03”. 
Return to the “Basic screen” (“Normal mode” if a wireless 
remote controller is used), and press the ON/OFF button. 
The operation lamp is lit, and the indoor unit will go into 
fan operation for air volume automatic adjustments (at 
which time, do not adjust the opening of the discharge or 
suction). The air volume adjustments will automatically 

terminate approximately 1 to 15 minutes after the indoor 

unit comes into operation, and the operation lamp will be 
OFF and the indoor unit will come to a stop.

Table 7

Mode No.

FIRST 
CODE 

No.

Setting 

content

SECOND CODE No.

01

02

03

11 (21)

7

Air volume 

adjust-

ment

OFF

Air volume 

adjust-

ment 

completion

Air volume 

adjust-

ment start

(4) 

After the air conditioner comes to a stop, be sure to 
check with Mode No. [21] per indoor unit that the above 
SECOND CODE No. is “02”. If the operation of the air 
conditioner does not stop automatically or the SECOND 
CODE No. is not set to “02”, repeat the setting procedure 
from (3).

 CAUTION

• 

If airflow pathway changes, such as duct and discharge 

changes, are made after air volume adjustments, be sure to 
make “Air volume automatic adjustment” again.

• 

If airflow pathway changes, such as duct and discharge 

changes, are made after 

11. TEST OPERATION

 or air 

conditioner relocation, contact your dealer.

(b) Select external static pressure with the remote controller.

Check with Mode No. [21] per indoor unit that the SECOND 
CODE No. for the above “Air volume adjustment” is set to 
“01” (OFF). (The SECOND CODE No. is factory set to “01” 
(OFF).) 
Change the SECOND CODE No. by referring to the table 

below according to the external static pressure of the duct 

to be connected.

Table 8
In case of 15-48 type

External static pressure

Mode No.

FIRST  

CODE No.

SECOND 

CODE No.

0.20 inWG (50 Pa)

13(23)

6

02

0.24 inWG (60 Pa)

03

0.28 inWG (70 Pa)

04

0.32 inWG (80 Pa)

05

0.36 inWG (90 Pa)

06

0.40 inWG (100 Pa)

07

0.44 inWG (110 Pa)

08

0.48 inWG (120 Pa)

09

0.52 inWG (130 Pa)

10

0.56 inWG (140 Pa)

11

0.60 inWG (150 Pa)

12

0.64 inWG (160 Pa)

13

0.72 inWG (180 Pa)

14

0.80 inWG (200 Pa)

15

In case of 54 type

External static pressure

Mode No.

FIRST  

CODE No.

SECOND 

CODE No.

0.20 inWG (50 Pa)

13(23)

6

02

0.24 inWG (60 Pa)

03

0.28 inWG (70 Pa)

04

0.32 inWG (80 Pa)

05

0.36 inWG (90 Pa)

06

0.40 inWG (100 Pa)

07

0.44 inWG (110 Pa)

08

0.48 inWG (120 Pa)

09

0.52 inWG (130 Pa)

10

0.56 inWG (140 Pa)

11

10-2 SETTING WHEN AN OPTIONAL ACCESSORY 

IS ATTACHED

• 

For setting when attaching an optional accessory, refer to 
the installation manual attached to the optional accessory.

10-3 SETTING FAN SPEED DURING THERMOSTAT 

OFF

• 

Set the fan speed according to the using environment after 
consultation with your customer.

• 

When the fan speed is changed, explain the set fan speed 

to your customer.

01_EN_3P493125-6E.indd   18

2022/08/03   10:36:14

Summary of Contents for FXMQ15TBVJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...ere injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due t...

Page 3: ...Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required...

Page 4: ...ctric parts may be damaged 2 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Name 1 Metal clamp 2 Drain hose 3 Duct flange connection screw Quantity 1 pc 1 pc See belo...

Page 5: ...he optional accessory and make field settings as needed Is the remote controller icon displayed Is the re mote controller connected to the master unit if the system is in simultaneous multi operation...

Page 6: ...ighting type inverter or rapid start type fluorescent lamp is installed 2 Use suspension bolts for installation Investigate if the installation place can withstand the weight of the indoor unit and if...

Page 7: ...ain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the piping connection port and wiring connection port of the indoor...

Page 8: ...spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust so that the unit is...

Page 9: ...a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Spanner Flare...

Page 10: ...Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE 2 After all the brazing...

Page 11: ...ig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put the metal clamp 1 to t...

Page 12: ...ate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection do not connect the drain...

Page 13: ...y not come off 3 Gradually pour 1 4 gal 1 of water from the dis charge into the drain pan and be careful spraying water to the electric components such as drain pump Refer to Fig 18 4 When the power s...

Page 14: ...ation material Field supply Suction Discharge Screws for duct anges 3 Accessory Screws for duct anges 3 Accessory Flange on discharge side Provided with the unit Fig 20 CAUTION Connect the flange and...

Page 15: ...unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insulated thickness 1 16 in 1 mm or more 9 4 WIRING CONNECTION METHOD CAUTION FOR WIRING F...

Page 16: ...ture if you have difficulty in performing this step Screws 2 locations Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control bo...

Page 17: ...1 P F 2 F 1 P L1 F 1 2 T 2 T 1 P P 2 1 F 2 L2 F L1 1 2 T T P Remote controller Remote controller Remote controller L1 L2 L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller...

Page 18: ...on Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC 15 V 1 mA 2 Actuation...

Page 19: ...ill be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume...

Page 20: ...arly if the indication is one of those shown in the Table 13 it may be an error in the electrical wiring or the power supply is disconnected Therefore recheck wiring Table 13 Remote controller indicat...

Page 21: ...2209 HT 3P493125 6E EM21A039A Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P493125 6E indd 2 2022 08 03 10 34 56...

Reviews: