background image

8

English

6.  REFRIGERANT PIPING WORK

• 

For the outdoor unit refrigerant piping, refer to the installa-
tion manual attached to the outdoor unit.

• 

Carry out insulation of both gas and liquid refrigerant piping 
securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 250°F (120°C). 
For use under high humidity, strengthen the insulation ma-
terial for refrigerant piping. If not strengthened, the surface 
of insulation material may sweat.

• 

Before installation work, make sure that the refrigerant is 
R410A. (Unless the refrigerant is R410A, the nor mal opera-

tion cannot be expected.)

 CAUTION

This air conditioner is a dedicated model for refriger-

ant R410A. Make sure to meet the require ments shown 

below and carry out installation work.

• 

Use dedicated piping cutters and flaring tools for 

R410A.

• 

When making a flare connection, coat the flared in

-

ner surface only with ether oil or ester oil.

• 

Use only the flare nuts attached to the air condition

-

er. If other flare nuts are used, it may cause refriger

-

ant leakage.

•  To prevent contamination or moisture from getting 

into the piping, take measures such as pinch ing or 

taping the pipings.

Do not mix substance other than the specified refrig

-

erant such as air into the refrigeration circuit. 

If the refrigerant leaks during the work, ventilate the 

room.

• 

The refrigerant is pre-charged in the outdoor unit.

• 

When connecting the pipings to the air conditioner, 
make sure to use a spanner and a torque wrench as 
shown in 

Fig. 9

.

• 

For the dimension of flared part and the tightening 

torque, refer to the Table 2.

• 

When making a flare connection, coat the flared inner 

surface only with ether oil or ester oil.  

(Refer to Fig. 10)

 

Then, turn the flare nut 3 to 4 times with your hand and 

screw in the nut.

 

Torque wrench

Spanner

Flare nut

Union joint

Fig. 9

Coat the flared inner surface 

only with ether oil or ester oil

Fig. 10

Table 2

Piping 

size 

[in. (mm)]

Tightening 

torque 

[lbf·ft. (N·m)]

Dimension for 

processing flare 

A [in. (mm)]

Flare shape 

[in. (mm)]

f

 1/4 

(6.4)

10.4–12.7 

(15.7±1.5)

0.342–0.358

(8.9±0.2)

90°±2°

A

45°±2°

R0.016-0.031

(0.4-0.8)

f

 3/8 

(9.5)

24.1–29.4

(36.3±3.6)

0.504–0.520

(13.0±0.2)

f

 1/2 

(12.7)

36.5–44.5

(54.9±5.4)

0.638–0.654

(16.4±0.2)

f

 5/8 

(15.9)

45.6–55.6

(68.6±6.8)

0.760–0.776

(19.5±0.2)

 CAUTION

Do not have oil adhere to the screw fixing part of resin 

parts.

If oil adheres, it may weaken the strength of screwed part.

Do not tighten flare nuts too tight.

If a flare nut cracks, the refrigerant may leak.

• 

If there is no torque wrench, use Table 3 as a rule of 
thumb. 

When tightening a flare nut with a spanner harder and 

harder, there is a point where the tightening torque sud-
denly increases. 
From that position, tighten the nut additionally at the 
angle shown in Table 3. 

After the work is finished, check securely that there is no 

gas leak. 
If the nut is not tightened as instructed, it may cause 
slow refrigerant leak and result in malfunction (such as 
does not cool or heat).

Table 3

Piping size 

[in. (mm)]

Tightening 

angle

Recommended arm length of 

tool used [in. (mm)]

f

 1/4 (6.4)

60°–90°

Approx. 6 (150)

f

 3/8 (9.5)

60°–90°

Approx. 8 (200)

f

 1/2 (12.7)

30°–60°

Approx. 10 (250)

f

 5/8 (15.9)

30°–60°

Approx. 12 (300)

 CAUTION

Insulation of field piping must be carried out up to the 

connection inside the casing.

If the piping is exposed to the atmosphere, it may cause 

sweating, burn due to touching the piping, electric shock or 

fire due to the wiring touching the piping.

01_EN_3P493125-6E.indd   8

2022/08/03   10:36:09

Summary of Contents for FXMQ15TBVJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...ere injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due t...

Page 3: ...Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required...

Page 4: ...ctric parts may be damaged 2 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Name 1 Metal clamp 2 Drain hose 3 Duct flange connection screw Quantity 1 pc 1 pc See belo...

Page 5: ...he optional accessory and make field settings as needed Is the remote controller icon displayed Is the re mote controller connected to the master unit if the system is in simultaneous multi operation...

Page 6: ...ighting type inverter or rapid start type fluorescent lamp is installed 2 Use suspension bolts for installation Investigate if the installation place can withstand the weight of the indoor unit and if...

Page 7: ...ain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the piping connection port and wiring connection port of the indoor...

Page 8: ...spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust so that the unit is...

Page 9: ...a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Spanner Flare...

Page 10: ...Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE 2 After all the brazing...

Page 11: ...ig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put the metal clamp 1 to t...

Page 12: ...ate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection do not connect the drain...

Page 13: ...y not come off 3 Gradually pour 1 4 gal 1 of water from the dis charge into the drain pan and be careful spraying water to the electric components such as drain pump Refer to Fig 18 4 When the power s...

Page 14: ...ation material Field supply Suction Discharge Screws for duct anges 3 Accessory Screws for duct anges 3 Accessory Flange on discharge side Provided with the unit Fig 20 CAUTION Connect the flange and...

Page 15: ...unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insulated thickness 1 16 in 1 mm or more 9 4 WIRING CONNECTION METHOD CAUTION FOR WIRING F...

Page 16: ...ture if you have difficulty in performing this step Screws 2 locations Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control bo...

Page 17: ...1 P F 2 F 1 P L1 F 1 2 T 2 T 1 P P 2 1 F 2 L2 F L1 1 2 T T P Remote controller Remote controller Remote controller L1 L2 L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller...

Page 18: ...on Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC 15 V 1 mA 2 Actuation...

Page 19: ...ill be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume...

Page 20: ...arly if the indication is one of those shown in the Table 13 it may be an error in the electrical wiring or the power supply is disconnected Therefore recheck wiring Table 13 Remote controller indicat...

Page 21: ...2209 HT 3P493125 6E EM21A039A Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P493125 6E indd 2 2022 08 03 10 34 56...

Reviews: