background image

17

English

9-6  FOR CONTROL WITH 2 REMOTE CONTROL-

LERS (TO CONTROL 1 INDOOR UNIT WITH 2 

REMOTE CONTROLLERS)

• 

For control with 2 remote controllers, set one remote con-
troller as Main and the other remote controller as Sub.

< Changeover method from Main to Sub and vice versa >

Refer to the installation manual attached to the remote 
controller.

< Wiring method >

(1) 

  Remove the control box cover.

(2) 

  Carry out additional wiring from the remote controller 

2 (Sub) to the terminals (P1, P2) for remote controller 

wiring on the terminal block (X2M) in the control box.

Terminal for remote 

controller wiring (P1, P2)

No polarity

Remote 

controller 2

(Sub)

Remote 

controller 1

(Main)

Terminal block 

(X2M)

< Caution >

• 

When using the group control and the 2 remote con-
trollers control at the same time, connect the remote 
controller 2 (Sub) to the indoor unit at the end of the 
crossover wiring (the largest No.). 

(Refer to Fig. 29)

Indoor unit 1

Indoor unit 2

Indoor unit 

largest No.

Remote 

controller 2 

(Sub)

Crossover 

wiring (Remote 

controller)

Remote 

controller 1 

(Main)

Fig. 29

9-7  FOR CENTRALIZED CONTROL

• 

When centralized equipment (such as centralized control-
ler) is used for control, it is required to set the group No. on 
the remote controller. 
For details, refer to the manuals attached to the centralized 
equipment.

• 

Connect the centralized equipment to the indoor unit con-
nected to the remote controller.

9-8  FOR REMOTE CONTROL (FORCE OFF OR ON / 

OFF OPERATION) 

(1) 

Wiring method and specification

• 

Remote control is available by connecting the external 

input to the terminal T1 and T2 on the terminal block for 
remote controller and transmission wiring (X2M).

F2 T1 T2

FORCED

OFF

Input A

Wiring  

specification

Sheathed vinyl 
cord or 2 core 
cable

Wiring size

AWG 18-16 
(0.75-1.25 mm

2

)

Wiring length

Max. 328 ft. 

 

(100 m)

External 

 

contact spec

Contact that can 
make and break 
the min. load of 
DC 15 V · 1 mA

(2)  Actuation

• 

Input A of FORCED OFF and ON/OFF OPERATION 
will be as the table shown below.

Input A = ON

Input A = OFF

In case of FORCED 
OFF

Remote controller 

prohibited

Remote controller 

permitted

In case of ON/OFF 
OPERATION

Operation

Stop

(3)  How to choose FORCED OFF or ON/OFF OPERATION 

• 

For choosing FORCED OFF or ON/OFF OPERATION, 
setting by remote controller is required.
(Refer to 

10. FIELD SETTING

)

10. FIELD SETTING

 CAUTION

Before carrying out field setting, check the items mentioned in 

 

(1) Items to be checked after the installation work is com-

pleted

 on page 3.

• 

Check if all the installation and piping works for the air con-
ditioner are completed.

• 

Check that the outside panel and piping cover of the indoor 
and outdoor units  are closed.

< FIELD SETTING >

After turning on the power supply, carry out field setting 

from the remote controller according to the installation 

state.

• 

Carry out setting at 3 places, “Mode No.”, “FIRST CODE 
No.” and “SECOND CODE No.”. 
The settings shown by 

 in the following tables indi-

cate those when shipped from the factory.

• 

The method of setting procedure and operation is shown in 
the installation manual attached to the remote controller.
(Note)  Though setting of “Mode No.” is carried out as a 

group, if you intend to carry out individual setting by 

each indoor unit or confirmation after setting, carry 

out setting with the Mode No. shown in the paren-
thesis ( ). 

• 

Ask your customer to keep the manual attached to the re-
mote controller together with the operation manual.

• 

Do not carry out settings other than those shown in the table.

• 

Settings are performed by selecting “Mode No.”, “FIRST 
CODE No.”, and “SECOND CODE No.”.

01_EN_3P493125-6E.indd   17

2022/08/03   10:36:14

Summary of Contents for FXMQ15TBVJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...ere injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due t...

Page 3: ...Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required...

Page 4: ...ctric parts may be damaged 2 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Name 1 Metal clamp 2 Drain hose 3 Duct flange connection screw Quantity 1 pc 1 pc See belo...

Page 5: ...he optional accessory and make field settings as needed Is the remote controller icon displayed Is the re mote controller connected to the master unit if the system is in simultaneous multi operation...

Page 6: ...ighting type inverter or rapid start type fluorescent lamp is installed 2 Use suspension bolts for installation Investigate if the installation place can withstand the weight of the indoor unit and if...

Page 7: ...ain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the piping connection port and wiring connection port of the indoor...

Page 8: ...spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust so that the unit is...

Page 9: ...a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Spanner Flare...

Page 10: ...Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE 2 After all the brazing...

Page 11: ...ig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put the metal clamp 1 to t...

Page 12: ...ate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection do not connect the drain...

Page 13: ...y not come off 3 Gradually pour 1 4 gal 1 of water from the dis charge into the drain pan and be careful spraying water to the electric components such as drain pump Refer to Fig 18 4 When the power s...

Page 14: ...ation material Field supply Suction Discharge Screws for duct anges 3 Accessory Screws for duct anges 3 Accessory Flange on discharge side Provided with the unit Fig 20 CAUTION Connect the flange and...

Page 15: ...unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insulated thickness 1 16 in 1 mm or more 9 4 WIRING CONNECTION METHOD CAUTION FOR WIRING F...

Page 16: ...ture if you have difficulty in performing this step Screws 2 locations Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control bo...

Page 17: ...1 P F 2 F 1 P L1 F 1 2 T 2 T 1 P P 2 1 F 2 L2 F L1 1 2 T T P Remote controller Remote controller Remote controller L1 L2 L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller...

Page 18: ...on Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC 15 V 1 mA 2 Actuation...

Page 19: ...ill be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume...

Page 20: ...arly if the indication is one of those shown in the Table 13 it may be an error in the electrical wiring or the power supply is disconnected Therefore recheck wiring Table 13 Remote controller indicat...

Page 21: ...2209 HT 3P493125 6E EM21A039A Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P493125 6E indd 2 2022 08 03 10 34 56...

Reviews: