7.  DRAIN PIPING WORK

(1)  Carry out drain piping.

Carry out drain piping so that drainage is ensured.

• 

Select the piping diameter equal to or larger than 

(except for riser) that of the connection piping (polyvi-

nyl chloride piping, nominal diameter 13/16 in. (25 mm), 
outside diameter 1-1/4 in. (32 mm)).

• 

Install the drain piping as short as possible with down-
ward inclination of 1/100 or more and without such that 
air may not stagnate. 

(Refer to Fig. 13)

 (It may cause 

abnormal sound such as bubbling noise.)

Downward

inclination of 

1/100 or more

40-60 in. 

(1-1.5 m)

Support

Good

Wrong

Fig. 13

 CAUTION

If drain stagnates in the drain piping, the piping may be 
clogged.

• 

If sufficient downward inclination cannot be ensured, 

carry out upward drain piping.

• 

Install supports at a distance of 40-60 in. (1 to 1.5 m) so 

that the piping may not deflect. 

(Refer to Fig. 13)

• 

Make sure to use the attached drain hose (2) and the 
metal clamp (1). 
Insert the drain hose (2) into the drain socket up to the 
point where the socket diameter becomes larger.  

  Put the metal clamp (1) to the taped hose end and 

tighten the metal clamp (1) with torque 0.9-1.1 lbf·ft.  
(1.2-1.5 N·m).

Metal clamp (1)
(Accessory)

Tape

Indoor unit

Drain hose (2)
(Accessory)

Fig. 14

 CAUTION

• 

Do not tighten the metal clamp (1) with the torque more 

than the specified value.

 

The drain hose (2), the socket or the metal clamp (1) may 
be damaged.

• 

Wrap the vinyl tape around the end of the metal clamp 
(1) so that the sealing material (Large) (6) to be used at 

the next process may not be damaged with the clamp 

end or bend the tip of the metal clamp (1) inward as 
shown. 

(Refer to Fig. 15)

<In case of sticking vinyl tape>

Tightened part

appro

x.

 90°

Stick vinyl tape without 

tearing the sealing 

material (Large) (6).

Vinyl tape

<In case of bending the tip>

Bend the tip without tearing the 
sealing material (Large) (6).

Tightened part

appro

x.

 90°

Fig. 15

01_EN_3P493125-6E.indd   10

2022/08/03   10:36:10

Summary of Contents for FXMQ15TBVJU

Page 1: ...for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel...

Page 2: ...ere injury or death After completing the installation work check that the refrigerant gas does not leak throughout the system Do not install unit in an area where flammable materials are present due t...

Page 3: ...Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the procedures Since R410A is a blend the required...

Page 4: ...ctric parts may be damaged 2 1 ACCESSORIES Check if the following accessories are attached to the indoor unit Name 1 Metal clamp 2 Drain hose 3 Duct flange connection screw Quantity 1 pc 1 pc See belo...

Page 5: ...he optional accessory and make field settings as needed Is the remote controller icon displayed Is the re mote controller connected to the master unit if the system is in simultaneous multi operation...

Page 6: ...ighting type inverter or rapid start type fluorescent lamp is installed 2 Use suspension bolts for installation Investigate if the installation place can withstand the weight of the indoor unit and if...

Page 7: ...ain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the piping connection port and wiring connection port of the indoor...

Page 8: ...spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust so that the unit is...

Page 9: ...a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Spanner Flare...

Page 10: ...Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE 2 After all the brazing...

Page 11: ...ig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put the metal clamp 1 to t...

Page 12: ...ate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection do not connect the drain...

Page 13: ...y not come off 3 Gradually pour 1 4 gal 1 of water from the dis charge into the drain pan and be careful spraying water to the electric components such as drain pump Refer to Fig 18 4 When the power s...

Page 14: ...ation material Field supply Suction Discharge Screws for duct anges 3 Accessory Screws for duct anges 3 Accessory Flange on discharge side Provided with the unit Fig 20 CAUTION Connect the flange and...

Page 15: ...unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insulated thickness 1 16 in 1 mm or more 9 4 WIRING CONNECTION METHOD CAUTION FOR WIRING F...

Page 16: ...ture if you have difficulty in performing this step Screws 2 locations Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control bo...

Page 17: ...1 P F 2 F 1 P L1 F 1 2 T 2 T 1 P P 2 1 F 2 L2 F L1 1 2 T T P Remote controller Remote controller Remote controller L1 L2 L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller...

Page 18: ...on Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC 15 V 1 mA 2 Actuation...

Page 19: ...ill be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume...

Page 20: ...arly if the indication is one of those shown in the Table 13 it may be an error in the electrical wiring or the power supply is disconnected Therefore recheck wiring Table 13 Remote controller indicat...

Page 21: ...2209 HT 3P493125 6E EM21A039A Daikin Texas Technology Park 19001 Kermier Road Waller TX 77484 U S A 00_CV_3P493125 6E indd 2 2022 08 03 10 34 56...

Reviews: