Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

15.9 mm (5/8")

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

13.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

10~14 mm

≥13 mm

12.7 mm (1/2")

14~16 mm

≥13 mm

15.9 mm (5/8")

16~20 mm

≥13 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

13.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

13.2.1

To connect the refrigerant piping to the
indoor unit

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Pipe length

. Keep refrigerant piping as short as possible.

Flare  connections

.  Connect  refrigerant  piping  to  the  unit  using

flare connections.

Insulation

.  Insulate  the  refrigerant  piping  on  the  indoor  unit  as

follows:

B

A

a

d

c

e f

b

b

a

d

c

e f

b

b

2

4

3

g

1

2

3

4

g

1

A B

A

Liquid piping

B

Gas piping

a

Insulation material (field supply)

b

Tie wrap (field supply)

c

Insulation pieces: Large (gas pipe), small (liquid pipe)
(accessories)

d

Flare nut (attached to the unit)

e

Refrigerant pipe connection (attached to the unit)

f

Unit

g

Sealing pads: Medium 1 (gas pipe), medium 2 (liquid
pipe) (accessories)

1

Turn up the seams of the insulation pieces.

2

Attach to the base of the unit.

3

Tighten the tie wrap on the insulation pieces.

4

Wrap the sealing pad from the base of the unit to the top
of the flare nut.

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

14

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

14.1

Specifications of standard wiring
components

Component

Power
supply cable

MCA

(a)

"    14‒1 Minimum circuit

ampacity" 

[

4

 20]

Voltage

220~240 V/220 V

Phase

1~

Frequency

50/60 Hz

Wire sizes

1.5 mm

(3‑core wire)

H07RN-F (60245 IEC 66)

Transmission wiring

For specification refer to the installation

manual of the outdoor unit

User interface cable

0.75 to 1.25 mm

2

 (2‑core wire)

H05RN-F (60245 IEC 57)

Length ≤500 m

Summary of Contents for FXMA100A5VEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMA50A5VEB FXMA63A5VEB FXMA80A5VEB FXMA100A5VEB FXMA125A5VEB...

Page 2: ...bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpiso...

Page 3: ...roducts are used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the pro...

Page 4: ...e commissioning 21 15 2 To perform a test run 21 16 Configuration 21 16 1 Field setting 21 17 Technical data 23 17 1 Wiring diagram 23 17 1 1 Unified wiring diagram legend 23 1 About the documentation...

Page 5: ...llation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas...

Page 6: ...ammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that...

Page 7: ...nderstand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire D...

Page 8: ...ct your dealer WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is unhealthy to...

Page 9: ...AMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process...

Page 10: ...erface d Suction air e Discharge air f Refrigerant piping transmission cable g Drain pipe 5 User interface CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some p...

Page 11: ...Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury NOTICE NEVER inspect or service the unit by yourself Ask a qualifi...

Page 12: ...with duct close the protective guard In case of rear suction with duct close service duct opening 9 Turn ON the power 10 To remove warning screens see the reference guide of the user interface 7 2 2 T...

Page 13: ...your dealer immediately For more information see the installation manual of the outdoor unit INFORMATION To stop alarm of the user interface see the reference guide of the user interface INFORMATION...

Page 14: ...ets the requirement for commercial and light industrial location when professionally installed and maintained NOTICE The professional installer shall evaluate the EMC situation before installation if...

Page 15: ...al service space Refer to the installation manual of the used option before installation 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit Installation options CAUTION In...

Page 16: ...the installation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install t...

Page 17: ...r bubbles Rising piping 300 mm from the unit 625 mm perpendicular to the unit 625 300 0 75 1000 1500 mm b a b a d d c a Metal clamp accessory b Drain hose accessory c Rising drain piping vinyl pipe of...

Page 18: ...1 l of water through the water inlet and check for leaks f e d b a g c a Drain connection b Water inlet c Refrigerant pipes d Drain outlet for maintenance e Water inlet cover f Bucket adding water thr...

Page 19: ...The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulati...

Page 20: ...rame and connect the cable to the terminal block L N earth Fix the cable with a tie wrap on the wiring fixture a b a Circuit breaker b Residual current device 10 15 70 90 7 P1P2 F1 F2 b L N 10 15 70 9...

Page 21: ...t they correspond with the actual installation setup and with the needs of the user Bottom suction or rear suction installation External static pressure setting using Airflow automatic adjustment sett...

Page 22: ...up volume 2 02 OFF a 03 Monitoring 1 2 04 Monitoring 2 2 05 a Only use in combination with optional remote sensor or when setting M 10 20 SW 2 03 is used Setting Time to clean air filter This setting...

Page 23: ...tion Contact that can make and break the min load of DC15 V 1 mA This setting must correspond with the needs of the user If you want to set Then 1 M SW Forced OFF 12 22 1 01 ON OFF Operation 02 Emerge...

Page 24: ...e core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...3P680922 1A 2022 01 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: