2 Specific installer safety instructions

Installation and operation manual

6

FXMA-A

VRV system air conditioner

3P680922-1A – 2022.01

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

CAUTION

▪ Each  indoor  unit  has  to  be  connected  to  a  separate

user interface. Only a safety system compatible remote
controller  can  be  used  as  the  user  interface.  See
technical  data  sheet  for  remote  controller  compatibility
(e.g. BRC1H52/82*).

▪ The  user  interface  has  to  be  put  in  the  same  room  as

the  indoor  unit.  For  details,  please  refer  to  the
installation and operation manual of the user interface.

CAUTION

In case shielded wire is used, connect the shielding to the
outdoor unit side only.

Configuration (see 

"16 Configuration"

 [

4

 21])

WARNING

In case of R32 refrigerant, terminal connections T1/T2 are
for  fire  alarm  input  ONLY.  Fire  alarm  has  a  higher  priority
than R32 safety and shuts the entire system down.

T1

T2

X1M

a

a

 Fire alarm input signal (potential free contact)

2.1

Instructions for equipment using
R32 refrigerant

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (example:  open  flames,  an
operating  gas  appliance  or  an  operating  electric  heater)
and have a room size as specified below.

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation and are executed ONLY by authorised persons.

WARNING

If  one  or  more  rooms  are  connected  to  the  unit  using  a
duct system, make sure:

▪ there are no operating ignition sources (example: open

flames,  an  operating  gas  appliance  or  an  operating
electric  heater)  in  case  the  floor  area  is  less  than  the
minimum floor area A (m²).

▪ no  auxiliary  devices,  which  may  be  a  potential  ignition

source,  are  installed  in  the  duct  work  (example:  hot
surfaces  with  a  temperature  exceeding  700°C  and
electric switching device);

▪ only  auxiliary  devices  approved  by  the  manufacturer

are used in the duct work;

▪ air inlet AND outlet are connected directly to the same

room  by  ducting.  Do  NOT  use  spaces  such  as  a  false
ceiling as a duct for the air inlet or outlet.

NOTICE

▪ Precautions shall be taken to avoid excessive vibration

or pulsation to refrigeration piping.

▪ Protection  devices,  piping  and  fittings  shall  be

protected  as  far  as  possible  against  adverse
environmental effects.

▪ Provision shall be made for expansion and contraction

of long runs of piping.

▪ Piping  in  refrigerating  systems  shall  be  designed  and

installed such as to minimise the likelihood of hydraulic
shock damaging the system.

▪ The  indoor  equipment  and  pipes  shall  be  securely

mounted  and  guarded  such  that  accidental  rupture  of
equipment  or  pipes  cannot  occur  from  events  such  as
moving furniture or reconstruction activities.

CAUTION

Do  NOT  use  potential  sources  of  ignition  in  searching  for
or detection of refrigerant leaks.

NOTICE

▪ Do  NOT  re-use  joints  and  copper  gaskets  which  have

been used already.

▪ Joints  made  in  installation  between  parts  of  refrigerant

system shall be accessible for maintenance purposes.

Summary of Contents for FXMA100A5VEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMA50A5VEB FXMA63A5VEB FXMA80A5VEB FXMA100A5VEB FXMA125A5VEB...

Page 2: ...bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpiso...

Page 3: ...roducts are used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the pro...

Page 4: ...e commissioning 21 15 2 To perform a test run 21 16 Configuration 21 16 1 Field setting 21 17 Technical data 23 17 1 Wiring diagram 23 17 1 1 Unified wiring diagram legend 23 1 About the documentation...

Page 5: ...llation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas...

Page 6: ...ammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that...

Page 7: ...nderstand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire D...

Page 8: ...ct your dealer WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is unhealthy to...

Page 9: ...AMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process...

Page 10: ...erface d Suction air e Discharge air f Refrigerant piping transmission cable g Drain pipe 5 User interface CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some p...

Page 11: ...Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury NOTICE NEVER inspect or service the unit by yourself Ask a qualifi...

Page 12: ...with duct close the protective guard In case of rear suction with duct close service duct opening 9 Turn ON the power 10 To remove warning screens see the reference guide of the user interface 7 2 2 T...

Page 13: ...your dealer immediately For more information see the installation manual of the outdoor unit INFORMATION To stop alarm of the user interface see the reference guide of the user interface INFORMATION...

Page 14: ...ets the requirement for commercial and light industrial location when professionally installed and maintained NOTICE The professional installer shall evaluate the EMC situation before installation if...

Page 15: ...al service space Refer to the installation manual of the used option before installation 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit Installation options CAUTION In...

Page 16: ...the installation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install t...

Page 17: ...r bubbles Rising piping 300 mm from the unit 625 mm perpendicular to the unit 625 300 0 75 1000 1500 mm b a b a d d c a Metal clamp accessory b Drain hose accessory c Rising drain piping vinyl pipe of...

Page 18: ...1 l of water through the water inlet and check for leaks f e d b a g c a Drain connection b Water inlet c Refrigerant pipes d Drain outlet for maintenance e Water inlet cover f Bucket adding water thr...

Page 19: ...The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulati...

Page 20: ...rame and connect the cable to the terminal block L N earth Fix the cable with a tie wrap on the wiring fixture a b a Circuit breaker b Residual current device 10 15 70 90 7 P1P2 F1 F2 b L N 10 15 70 9...

Page 21: ...t they correspond with the actual installation setup and with the needs of the user Bottom suction or rear suction installation External static pressure setting using Airflow automatic adjustment sett...

Page 22: ...up volume 2 02 OFF a 03 Monitoring 1 2 04 Monitoring 2 2 05 a Only use in combination with optional remote sensor or when setting M 10 20 SW 2 03 is used Setting Time to clean air filter This setting...

Page 23: ...tion Contact that can make and break the min load of DC15 V 1 mA This setting must correspond with the needs of the user If you want to set Then 1 M SW Forced OFF 12 22 1 01 ON OFF Operation 02 Emerge...

Page 24: ...e core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...3P680922 1A 2022 01 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: