![background image](http://html1.mh-extra.com/html/daikin/fxma100a5veb/fxma100a5veb_installation-and-operation-manual_2460124022.webp)
16 Configuration
Installation and operation manual
22
FXMA-A
VRV system air conditioner
3P680922-1A – 2022.01
1
Operate the unit in
fan only mode
prior to using the airflow
automatic adjustment function.
2
Stop
the air conditioning unit.
3
Set the value
number “—“ to 03 for
M
11(21) and
SW
7.
4
Start
the air conditioning unit.
Result:
The operation lamp lights up and the unit starts the fan
operation for airflow automatic adjustment.
5
After airflow automatic adjustment is finished (air conditioning
unit will stop) check if the value number “—“ is set to 02. If there
is no change, perform the setting again.
Setting content:
Then
(1)
M
SW
—
Airflow adjustment is OFF
11(21)
7
01
Completion of automatic airflow adjustment
02
Start of automatic airflow adjustment
03
To set external static pressure by the user interface
Check the indoor unit setting: the value number “—“ must be set to
01 for
M
11(21) and
SW
7.
1
Change the value number “—“ according to the external static
pressure of the duct to be connected as in table below.
M
SW
—
External static pressure (Pa)
(1)
13(23)
6
01
—
02
50
03
60
04
70
05
80
06
90
07
100
08
110
09
120
10
130
11
140
12
150
13
160
14
180
15
200
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It
determines the fan speed of the indoor unit during thermostat OFF
condition.
1
If you have set the fan to operate, set the air volume speed:
If you want…
Then
(1)
M
SW
—
During thermostat
OFF at cooling
operation
LL
(2)
12 (22)
6
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
During thermostat
OFF at heating
operation
LL
(2)
12 (22)
3
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
(a)
Only use in combination with optional remote sensor or when
setting
M
10 (20),
SW
2, —
03 is used.
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room.
It determines the interval at which
"Time to clean filter"
notification
is displayed on the user interface.
If you want an interval of…
(air contamination)
Then
(1)
M
SW
—
±2500 h (light)
10 (20)
0
01
±1250 h (heavy)
02
Notification ON
3
01
Notification OFF
02
Setting: Thermostat sensor selection
This setting must correspond with how/if the remote controller
thermostat sensor is used.
When the remote controller thermostat
sensor is…
Then
(1)
M
SW
—
Used in combination with indoor unit
thermistor
10 (20)
2
01
Not used (indoor unit thermistor only)
02
Used exclusively
03
Setting: Thermostat differential changeover (if remote sensor is
used)
If the system contains a remote sensor, set the increase/decrease
increments.
If you want to change increments to…
Then
(1)
M
SW
—
1°C
12 (22)
2
01
0.5°C
02
Setting: Differential for automatic changeover
Set temperature difference between cooling setpoint and heating
setpoint in automatic mode (availability depends on the system
type). Differential is cooling setpoint minus heating setpoint.
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
SW
: Setting number
• —: Value number
•
: Default
(2)
Fan speed:
•
LL
: Low fan speed (set during thermostat OFF)
•
L
: Low fan speed (set by the user interface)
•
Setup volume
: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
•
Monitoring 1, 2
: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by
LL
(Monitoring 1) or by
L
(Monitoring 2).
Summary of Contents for FXMA100A5VEB
Page 25: ......
Page 26: ......
Page 27: ......
Page 28: ...3P680922 1A 2022 01 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...