background image

8 Troubleshooting

Installation and operation manual

13

FXMA-A
VRV system air conditioner
3P680922-1A – 2022.01

7.3.1

About the refrigerant leakage sensor

WARNING

The R32 refrigerant leakage sensor must be replaced after
every  detection  or  at  the  end  of  its  lifetime.  ONLY
authorised persons may replace the sensor.

NOTICE

Functionality  of  the  safety  measures  are  periodically
automatically  checked.  In  case  of  malfunction,  an  error
code will be displayed on the user interface.

NOTICE

The  R32  refrigerant  leakage  sensor  is  a  semiconductor
detector  which  may  incorrectly  detect  substances  other
than  R32  refrigerant.  Avoid  using  chemical  substances
(e.g.  organic  solvents,  hair  spray,  paint)  in  high
concentrations,  in  the  close  proximity  of  the  indoor  unit
because  this  may  cause  misdetection  of  the  R32
refrigerant leakage sensor.

INFORMATION

The  sensor  has  a  lifetime  of  10  years.  The  user  interface
displays  error  "

CH-05

"  6  months  before  the  end  of  the

sensor  lifetime  and  error  "

CH-02

"  after  the  end  of  the

sensor lifetime. For more information, refer to the reference
guide of the user interface and contact your dealer.

In case of detection when the unit is in standby

When  the  detection  occurs  when  the  unit  is  in  standby,  a  "false
detection check" will occur.

False detection check

1

The unit starts fan operation on the lowest setting.

2

The user interface displays error "

A0-13

", emits an alarm sound

and the status indicator blinks.

3

The  sensor  checks  if  a  refrigerant  leakage  or  misdetection
occurred.

▪ No  refrigerant  leakage  detected. 

Result: 

  The  system  resumes

normal operation after approximately 2 minutes.

▪ Refrigerant leakage detected. 

Result:

1

The user interface displays error "

A0-11

", emits an alarm sound

and the status indicator blinks.

2

Contact your dealer immediately. For more information, see the
installation manual of the outdoor unit.

In case of detection when the unit is turned on

1

The user interface displays error "

A0-11

", emits an alarm sound

and the status indicator blinks.

2

Contact your dealer immediately. For more information, see the
installation manual of the outdoor unit.

INFORMATION

To stop alarm of the user interface see the reference guide
of the user interface.

INFORMATION

The minimum airflow during normal operation or during the
refrigerant leakage detection is always >240 m

3

/h.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  OFF  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause  breakage,  electrical  shock  or  fire.  Contact  your
dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
circuit breaker or a residual current
device frequently actuates or the ON/
OFF switch does NOT function properly.

Turn OFF all main power
supply switches to the
unit.

If water leaks from the unit.

Stop operation.

The operation switch does NOT function
properly.

Turn OFF the power
supply.

If the user interface displays 

.

Notify your installer and
report the error code. To
display an error code see
the reference guide of the
user interface.

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

INFORMATION

Refer  to  the  reference  guide  located  on 

http://

www.daikineurope.com/support-and-manuals/product-
information/

 for more troubleshooting tips.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

9

Relocation

Contact  your  dealer  for  removing  and  reinstalling  the  total  unit.
Moving units requires technical expertise.

10

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

Summary of Contents for FXMA100A5VEB

Page 1: ...Installation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXMA50A5VEB FXMA63A5VEB FXMA80A5VEB FXMA100A5VEB FXMA125A5VEB...

Page 2: ...bus eksploatuojami laikantis m s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpiso...

Page 3: ...roducts are used in accordance with our instructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following the pro...

Page 4: ...e commissioning 21 15 2 To perform a test run 21 16 Configuration 21 16 1 Field setting 21 17 Technical data 23 17 1 Wiring diagram 23 17 1 1 Unified wiring diagram legend 23 1 About the documentation...

Page 5: ...llation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas...

Page 6: ...ammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process other than those recommended by the manufacturer Be aware that...

Page 7: ...nderstand the hazards involved Children SHALL NOT play with the appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire D...

Page 8: ...ct your dealer WARNING This unit contains electrical and hot parts WARNING Before operating the unit be sure the installation has been carried out correctly by an installer CAUTION It is unhealthy to...

Page 9: ...AMMABLE MATERIAL The refrigerant inside this unit is mildly flammable WARNING Do NOT pierce or burn refrigerant cycle parts Do NOT use cleaning materials or means to accelerate the defrosting process...

Page 10: ...erface d Suction air e Discharge air f Refrigerant piping transmission cable g Drain pipe 5 User interface CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some p...

Page 11: ...Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury NOTICE NEVER inspect or service the unit by yourself Ask a qualifi...

Page 12: ...with duct close the protective guard In case of rear suction with duct close service duct opening 9 Turn ON the power 10 To remove warning screens see the reference guide of the user interface 7 2 2 T...

Page 13: ...your dealer immediately For more information see the installation manual of the outdoor unit INFORMATION To stop alarm of the user interface see the reference guide of the user interface INFORMATION...

Page 14: ...ets the requirement for commercial and light industrial location when professionally installed and maintained NOTICE The professional installer shall evaluate the EMC situation before installation if...

Page 15: ...al service space Refer to the installation manual of the used option before installation 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit Installation options CAUTION In...

Page 16: ...the installation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install t...

Page 17: ...r bubbles Rising piping 300 mm from the unit 625 mm perpendicular to the unit 625 300 0 75 1000 1500 mm b a b a d d c a Metal clamp accessory b Drain hose accessory c Rising drain piping vinyl pipe of...

Page 18: ...1 l of water through the water inlet and check for leaks f e d b a g c a Drain connection b Water inlet c Refrigerant pipes d Drain outlet for maintenance e Water inlet cover f Bucket adding water thr...

Page 19: ...The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant piping as short as possible Flare connections Connect refrigerant piping to the unit using flare connections Insulati...

Page 20: ...rame and connect the cable to the terminal block L N earth Fix the cable with a tie wrap on the wiring fixture a b a Circuit breaker b Residual current device 10 15 70 90 7 P1P2 F1 F2 b L N 10 15 70 9...

Page 21: ...t they correspond with the actual installation setup and with the needs of the user Bottom suction or rear suction installation External static pressure setting using Airflow automatic adjustment sett...

Page 22: ...up volume 2 02 OFF a 03 Monitoring 1 2 04 Monitoring 2 2 05 a Only use in combination with optional remote sensor or when setting M 10 20 SW 2 03 is used Setting Time to clean air filter This setting...

Page 23: ...tion Contact that can make and break the min load of DC15 V 1 mA This setting must correspond with the needs of the user If you want to set Then 1 M SW Forced OFF 12 22 1 01 ON OFF Operation 02 Emerge...

Page 24: ...e core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated gate bipolar transistor IGBT Q C Circuit breaker Q DI KLM Earth...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...3P680922 1A 2022 01 Copyright 2022 Daikin Verantwortung f r Energie und Umwelt...

Reviews: