(2)

Open a hole in the ceiling for installation. (Case of existing 
ceiling)
• Use the paper pattern for installation which has been 

adjusted to the dimensions of the ceiling opening.

• Open a hole in the ceiling for installation at the place the 

unit is to be installed, and run refrigerant and drain piping, 
remote controller cord, and outdoor/indoor transmission 
wiring to the unit’s piping and wiring hole. (For wiring pro-
cedure, refer to “WIRING EXAMPLE AND HOW TO SET 
THE REMOTE CONTROLLER.” For piping procedure, 
refer to the attached installation manual of the outdoor 
unit.)

• After opening a hole in the ceiling, reinforcement of the 

ceiling frame, etc., may be required to maintain the level-
ness of the ceiling and to prevent vibration of the ceiling. 
For details, consult with your builder and interior contrac-
tor.

(3)

Install the suspension bolts.
(Use M8 size suspension bolts.)
Use anchors for existing ceilings and embedded inserts, 
embedded anchors, etc., for newly built ceilings so that the 
weight of the unit can be supported. Adjust the length of the 
bolts to the ceiling before installing the unit.

5.

INDOOR UNIT INSTALLATION

Installing optional accessories (except for the decoration 
panel) before installing the indoor unit is easier.

As for the parts to be used for installation work, be sure to use 
the provided accessories and specified parts designated by our 
company.

(1)

Install the unit temporarily.
• Fix the hanger bracket to the suspension bolt. Tighten 

both upper and lower nuts firmly using washers.

(2)

Using the attached positioning jig for installation, adjust the 
height of the unit.

(3)

Adjust the unit to the correct position based on “SELECT-
ING INSTALLATION SITE.” 

(1)

.

• The positioning jig for installation and paper pattern for 

installation have been adjusted to the dimensions of the 
ceiling opening. Be sure to establish thorough communi-
cation with those who are to do the ceiling work.

(4)

Check the unit is horizontally level.

CAUTION

The unit is equipped with a built-in drain pump and 
float switch. Level the four corners with a level or a 
vinyl tube containing water.

(If the unit is tilted against condensate flow, the float switch 
may malfunction and cause water to drip.)

(5)

Tighten the upper nut.

(6)

Apply the insulation for 
hanger bracket to the hanger 
bracket installation bolts of the 
units. 
(4 locations). (See figure on 
right.)

(7)

After setting up the unit, be sure to remove the positioning 
jig for installation.

NOTE

• For a newly built ceiling, carry out the same procedure and 

be sure to establish thorough communication with those who 
are to do the ceiling work. The positioning jig for installation 
and paper pattern for installation have been adjusted to the 
dimensions of the ceiling opening.

6.

REFRIGERANT PIPING WORK

〈〈〈〈

For refrigerant piping of outdoor units, see the installation 

manual attached to the outdoor unit.

〉 〉 〉 〉 

〈〈〈〈

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.

〉 〉 〉 〉 

Model

A

B

C

D

FXKQ25 · 32 · 40MVE

1110

1150

1200

1240

FXKQ63MVE

1310

1350

1400

1440

Ceiling slab

Set-up example

Ceiling surface

(length: mm)

Note) All the above parts are field supplied.

Anchor

Wing nut or turnbuckle

Suspension bolt

Approx. 

100 

Part to be procured 
in the field

Tighten from above and 
below (Double nut)

Washer (accessory)

Screws (×4)

Lower 
surface 
of ceiling

Positioning 
jig for 
installation 2

Positioning jig for installation 1

(

accessory

)

Positioning jig for 
installation 2

(

accessory

)

Positioning jig for installation 1

(

accessory

)

(accessory)

Positioning jig for installation 
fastening screw hole

Vinyl tube

Level

Insulation for 
hanger bracket
(accessory)

01_EN_3P086156-8F.fm  Page 4  Wednesday, March 19, 2003  6:55 PM

Summary of Contents for FXKQ25MVE

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVU...

Page 2: ...rmidade com a s seguinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retningsgiven...

Page 3: ...g to local laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is...

Page 4: ...Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environment If installed as a household appliance it could cause electro...

Page 5: ...ight exceeds 2 7 meters however the connector of terminal board A2P must be replaced and an air outlet blocking pad must be installed Refer to HIGH CEILING INSTALLATION P 9 3 Use suspension bolts for...

Page 6: ...and paper pattern for installation have been adjusted to the dimensions of the ceiling opening Be sure to establish thorough communi cation with those who are to do the ceiling work 4 Check the unit i...

Page 7: ...absolutely sure to execute heat insulation works on the pipe connecting section after checking gas leakage by thor oughly studying the following figure and using the attached heat insulating materials...

Page 8: ...ing piping Secure a downward gradient of 1 100 or more for the drain pipe To accomplish this mount supporting brackets at an interval of 1 1 5 m Precautions when doing drain up piping work Make sure t...

Page 9: ...d switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosions...

Page 10: ...ws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw will not be properly tightened If the te...

Page 11: ...actory set Insert Insert Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N L N IN D OUT D F1 F2 F1 F2...

Page 12: ...terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF O...

Page 13: ...No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPERATION Refer to the installation manual of the outdoor unit The operatio...

Page 14: ...0303 HT 3P086156 8J EM02A082A...

Reviews: