English

3. When including BS unit

[ PRECAUTIONS ] 

1. A single switch can be used to supply power to units on the 

same system. However, branch switches and branch circuit 
breakers must be selected carefully. 

2. Do not ground the equipment on gas pipes, water pipes or 

lightning rods, or crossground with telephones. Improper 
grounding could result in electric shock.

9-4

CONTROL BY 2 REMOTE CONTROLLERS 
(Controlling 1 indoor unit by 2 remote control-
lers)

• When using 2 remote controllers, one must be set to “MAIN” 

and the other to “SUB”.

MAIN/SUB CHANGEOVER

(1)

Insert a  

 screw driver into the recess between the upper 

and lower part of remote controller and, working from the 2 
positions, pry off the upper part.
The remote controller PC board is attached to the upper 
part of remote controller. 

(2)

Turn the MAIN/SUB changeover switch on one of the two 
remote controller PC boards to “S”.
(Leave the switch of the other remote controller set to “M”.)

Wiring Method 

(See “ELECTRIC WIRING WORK”)

(3)

Remove the electric parts box lid.

(4) Add remote control 2 (slave) to the terminal block for 

remote controller (P

1

, P

2

) in the electric parts box.

(There is no polarity.) (Refer to Fig. 1 and 8-3.)

9-5

COMPUTERISED CONTROL (FORCED OFF 
AND ON/OFF OPERATION) 

(1)

Wire specifications and how to perform wiring
• Connect input from outside to terminals T1 and T2 of the 

terminal block for remote controller.

(2)

Actuation 
• The following table explains FORCED OFF and ON/OFF 

OPERATIONS in response to Input A. 

(3)

How to select FORCED OFF and ON/OFF OPERATION
• Turn the power on and then use the remote controller to 

selet operation. 

9-6

CENTRALIZED CONTROL 

• For centralized control, it is necessary to designate the group 

No. For details, refer to the manual of each optional control-
lers for centralized control.

IN/D OUT/D

F1 F2 F1 F2

IN/D

OUT/D

F1 F2 F1 F2

L N

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

BS unit

No. 3
System

Outdoor unit

Power 

supply

220-240V

50Hz

or

220V

60Hz

Indoor unit A

Most 
downstream
indoor unit

Power 

supply

220-240V

50Hz

or

220V

60Hz

Control box

Control box

IN/D

OUT/D

F1 F2 F1 F2

BS unit

Control box

L N

P

1

P

2

P

1

P

2

F

1

F

2

T

1

T

2

L N

L N

Upper part of 
remote controller

Lower part of 
remote controller

Insert the screwdriver here and gently work 
off the upper part of remote controller.

S

M

S

S

M

Remote controller 
PC board

(Factory setting)

Only one remote controller 
needs to be changed if 
factory settings have 
remained untouched.

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75 - 1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum appli-
cable load of 15 V DC, 1 mA.

FORCED OFF

ON/OFF OPERATION

Input “ON” stops operation (impossible 
by remote controllers).

Input “OFF” 

→ 

“ON” turns 

ON unit.

Input “OFF” enables control by remote 
controller.

Input “ON” 

→ 

“OFF” turns 

OFF unit.

F2

T1

T2

FORCED 
OFF

Input A

01_EN_3P086156-8F.fm  Page 10  Wednesday, March 19, 2003  6:55 PM

Summary of Contents for FXKQ25MVE

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVU...

Page 2: ...rmidade com a s seguinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retningsgiven...

Page 3: ...g to local laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is...

Page 4: ...Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environment If installed as a household appliance it could cause electro...

Page 5: ...ight exceeds 2 7 meters however the connector of terminal board A2P must be replaced and an air outlet blocking pad must be installed Refer to HIGH CEILING INSTALLATION P 9 3 Use suspension bolts for...

Page 6: ...and paper pattern for installation have been adjusted to the dimensions of the ceiling opening Be sure to establish thorough communi cation with those who are to do the ceiling work 4 Check the unit i...

Page 7: ...absolutely sure to execute heat insulation works on the pipe connecting section after checking gas leakage by thor oughly studying the following figure and using the attached heat insulating materials...

Page 8: ...ing piping Secure a downward gradient of 1 100 or more for the drain pipe To accomplish this mount supporting brackets at an interval of 1 1 5 m Precautions when doing drain up piping work Make sure t...

Page 9: ...d switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosions...

Page 10: ...ws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw will not be properly tightened If the te...

Page 11: ...actory set Insert Insert Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N L N IN D OUT D F1 F2 F1 F2...

Page 12: ...terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF O...

Page 13: ...No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPERATION Refer to the installation manual of the outdoor unit The operatio...

Page 14: ...0303 HT 3P086156 8J EM02A082A...

Reviews: