VRV SYSTEM Inverter Air Conditioners

Installation manual

CONTENTS

1. SAFETY CONSIDERATIONS.......................................... 1

2. BEFORE INSTALLATION ................................................ 2

3. SELECTING INSTALLATION SITE ................................. 3

4. PREPARATIONS BEFORE INSTALLATION.................... 3

5. INDOOR UNIT INSTALLATION ....................................... 4

6. REFRIGERANT PIPING WORK ..................................... 4

7. DRAIN PIPING WORK .................................................... 6

8. ELECTRIC WIRING WORK ............................................ 7

9. WIRING EXAMPLE AND HOW TO SET THE

REMOTE CONTROLLER................................................ 7

10. DECORATION PANEL INSTALLATION ......................... 11

11. FIELD SETTING............................................................ 11

12. TEST OPERATION........................................................ 11

1.

SAFETY CONSIDERATIONS

Please read these “SAFETY CONSIDERATIONS” carefully 
before installing air conditioning equipment and be sure to 
install it correctly.  After completing the installation, make sure 
that the unit operates properly during the start-up operation.  
Please instruct the customer on how to operate the unit and 
keep it maintained.
Also, inform customers that they should store this installation 
manual along with the operation manual for future reference.
This air conditioner comes under the term “appliances not acces-
sible to the general public”.

Safety Precaution

This unit is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

Meaning of warning and caution symbols.

WARNING

  ............. Failure to observe a warning may 

result in death.

CAUTION

  .............. Failure to observe a caution may 

result in injury or damage to the equip-
ment.

WARNING

• Ask your dealer or qualified personnel to carry out installation 

work. Do not try to install the machine yourself.
Improper installation may result in water leakage, electric 
shocks or fire.

• Perform installation work in accordance with this installation 

manual.
Improper installation may result in water leakage, electric 
shocks or fire.

• When installing the unit in a small room, take measures 

against to keep refrigerant concentration from exceeding 
allowable safety limits in the event of refrigerant leakage. Con-
tact the place of purchase for more information. Excessive 
refrigerant in a closed ambient can lead to oxygen deficiency.

• Be sure to use only the specified accessories and parts for 

installation work.
Failure to use the specified parts may result in water leakage, 
electric shocks, fire or the unit falling.

• Install the air conditioner on a foundation strong enough to 

withstand the weight of the unit.
A foundation of insufficient strength may result in the equip-
ment falling and causing injuries.

• Carry out the specified installation work after taking into 

account strong winds, typhoons or earthquakes.

Improper installation work may result in the equipment falling 
and causing accidents.

• Make sure that a separate power supply circuit is provided for 

this unit and that all electrical work is carried out by qualified 
personnel according to local laws and regulations and this 
installation manual.
An insufficient power supply capacity or improper electrical 
construction may lead to electric shocks or fire.

• Make sure that all wiring is secured, the specified wires and 

used, and no external forces act on the terminal connections 
or wires.
Improper connections or installation may result in fire.

• When wiring the power supply and connecting the remote 

controller wiring and transmission wiring, position the wires 
so that the electric parts box lid can be securely fastened.
Improper positioning of the electric parts box lid may result in 
electric shocks, fire or the terminals overheating.

• If the refrigerant gas leaks during installation, ventilate the 

area immediately.
Toxic gas may be produced if the refrigerant gas comes into 
contact with fire.

• After completing the installation work, check that the refriger-

ant gas does not leak.
Toxic gas may be produced if the refrigerant gas leaks into 
the room and comes into contact with a source of fire, such 
as a fan heater, stove or cooker.

• Before touching electrical parts, turn off the unit.

CAUTION

• Ground the air conditioner.

Do not connect the ground wire to gas or water pipes, light-
ning rod or a telephone ground wire.
Incomplete grounding may result in electric shocks.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in elec-
tric shocks.

• While following the instructions in this installation manual, 

install drain piping in order to ensure proper drainage and 
insulate piping in order to prevent condensation.
Improper drain piping may result in water leakage and prop-
erty damage.

• Install the indoor and outdoor units, power supply wiring and 

connecting wires at least 1 meter away from televisions or 
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may 
not be sufficient enough to eliminate the noise.)

• Remote controller (wireless kit) transmitting distance can 

result shorter than expected in rooms with electronic fluores-
cent lamps. (inverter or rapid start types) 
Install the indoor unit as far away from fluorescent lamps as 
possible.

• Do not install the air conditioner in the following locations:

(a)

where a mineral oil mist or an oil spray or vapor is pro-
duced, for example in a kitchen
Plastic parts may deteriorate and fall off or result in 
water leakage.

(b)

where corrosive gas, such as sulfurous acid gas, is pro-
duced
Corroding copper pipes or soldered parts may result in 
refrigerant leakage.

(c)

near machinery emitting electromagnetic waves
Electromagnetic waves may disturb the operation of the 
control system and result in a malfunction of the equip-
ment.

(d)

where flammable gases may leak, where there are car-
bon fiber or ignitable dust suspensions in the air, or 
where volatile flammables such as thinner or gasoline 
are handled.
Operating the unit in such conditions may result in fire.

01_EN_3P086156-8F.fm  Page 1  Wednesday, March 19, 2003  6:55 PM

Summary of Contents for FXKQ25MVE

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVU...

Page 2: ...rmidade com a s seguinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retningsgiven...

Page 3: ...g to local laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is...

Page 4: ...Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environment If installed as a household appliance it could cause electro...

Page 5: ...ight exceeds 2 7 meters however the connector of terminal board A2P must be replaced and an air outlet blocking pad must be installed Refer to HIGH CEILING INSTALLATION P 9 3 Use suspension bolts for...

Page 6: ...and paper pattern for installation have been adjusted to the dimensions of the ceiling opening Be sure to establish thorough communi cation with those who are to do the ceiling work 4 Check the unit i...

Page 7: ...absolutely sure to execute heat insulation works on the pipe connecting section after checking gas leakage by thor oughly studying the following figure and using the attached heat insulating materials...

Page 8: ...ing piping Secure a downward gradient of 1 100 or more for the drain pipe To accomplish this mount supporting brackets at an interval of 1 1 5 m Precautions when doing drain up piping work Make sure t...

Page 9: ...d switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosions...

Page 10: ...ws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw will not be properly tightened If the te...

Page 11: ...actory set Insert Insert Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N L N IN D OUT D F1 F2 F1 F2...

Page 12: ...terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF O...

Page 13: ...No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPERATION Refer to the installation manual of the outdoor unit The operatio...