background image

English

5

(When using a heat pump, the temperature of the gas piping 
can reach up to approximately 120°C, so use insulation which is 
sufficiently resistant.)

〈〈〈〈

Also, in cases where the temperature and humidity of the 

refrigerant piping sections might exceed 30°C or RH80 %, 
reinforce the refrigerant insulation. (20 mm or thicker) Con-
densation may form on the surface of the insulating material.

〉〉〉〉

〈〈〈〈

Before ringging tubes, check which type of refrigerant is 

used. Proper operation is not possible if the types of refrig-
erant are not the same.

〉〉〉〉

CAUTION

• Use a pipe cutter and flare suitable for the type of refrigerant.
• Apply ester oil or ether oil around the flare portions 

before connecting.

• To prevent dust, moisuture or other foreign matter from infil-

trating the tube, either pinch the end or cover it with tape.

Do not allow anything other than the designated refrig-
erant to get mixed into the freezing cycle, such as air, 
etc. If any refrigerant gas leaks while working on the 
unit, ventilate the room thoroughly right away

.

• The outdoor unit is charged with refrigerant.
• Be sure to use both a spanner and torque wrench together, 

as shown in the drawing, when connecting or disconnecting 
pipes to/from the unit.

• Refer to the Table 3 for the dimensionons of flare not spaces.
• When connecting the flare nut, coat the flare section (both 

inside and outside) with ester oil or ether oil, rotate three or  
four times first, then screw in.

• Refer to the Table 3 for tightening torque.

Overtightening may damage the flare.

• Check the pipe connector for gas leaks, then insulate it as 

shown in the drawing.

• Wrap only the gas line side with the sealing pad. Bend the pad 

over the insulation for fitting (union) from above.

CAUTION

Over-tightening may damage the flare and cause a refriger-
ant leakage.

Use “ Tabel 4 ” as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque will sud-
denly increase. From that position, tighten the nut to the angle 
shown on “ Tabel 4 ”.

• Make absolutely sure to execute heat insulation works on the 

pipe-connecting section after checking gas leakage by thor-
oughly studying the following figure and using the attached 
heat insulating materials for fitting. (Fasten both ends with 
the clamps (accessory).)  

• Wrap the sealing pad (accessory) only around the insulation 

for the joints on the gas piping side.

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-
ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filter metal (BCuP) which 
does not require flux.
(Flux has extremely harmful infulence on refrigerant piping 
sysems. For instance, if the chlorine based flux is used, it will 
cause pipe corrosion or, in particular, if the flux contains fluo-
rine, it will damage the refrigerant oil.)

Before brazing local refrigerant piping, nitrogen gas shall be 
blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

When brazing the refrigerant piping, only begin brazing after 
having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 0.02 Mpa (0.2 kg/cm

2

) with a pres-

sure-reducing valve if brazing while inserting nitrogen into 
the piping.

NOTE

The flare nuts used must be those included with the 
main body.

• Refer to Table 3 for tightening torque.

Table 3

Ester oil or ether oil.

Torque wrench

Spanner

Piping union

Flare nut

Pipe 

size

Tightening torque

Flare 

dimensions

A (mm)

Flare

 φ

 6.4

(1/4”)

14.2 – 17.2N·m 

(144 – 176 kgf·cm)

8.7 – 9.1

 φ

 9.5

(3/8”)

32.7 – 39.9N·m 

(333 – 407 kgf·cm)

12.8 – 13.2

 φ

 12.7

(1/2”)

49.5 – 60.3N·m 

(504 – 616 kgf·cm)

16.2 – 16.6

 φ

 15.9

(5/8”)

61.8 – 75.4N·m 

(630 – 770 kgf·cm)

19.3 – 19.7

Small sealing pad
(accessory)

(accessory)

Gas pipe

Liquid pipe

Insulation 
for fitting

Clamp
(× 6 accessory)

Refrigerant 
piping

Part to be 
brazed

Taping

Pressure-
reducing 
valve

hands valve

Nitrogen

Nitrogen

A

45

0

2

0

R0.4-0.8

90

0

2

0

 

01_EN_3P086156-8F.fm  Page 5  Wednesday, March 19, 2003  6:55 PM

Summary of Contents for FXKQ25MVE

Page 1: ...MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVU...

Page 2: ...rmidade com a s seguinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retningsgiven...

Page 3: ...g to local laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is...

Page 4: ...Also in vehicles or vessels This unit both indoor and outdoor is suitable for installation in a commercial and light industrial environment If installed as a household appliance it could cause electro...

Page 5: ...ight exceeds 2 7 meters however the connector of terminal board A2P must be replaced and an air outlet blocking pad must be installed Refer to HIGH CEILING INSTALLATION P 9 3 Use suspension bolts for...

Page 6: ...and paper pattern for installation have been adjusted to the dimensions of the ceiling opening Be sure to establish thorough communi cation with those who are to do the ceiling work 4 Check the unit i...

Page 7: ...absolutely sure to execute heat insulation works on the pipe connecting section after checking gas leakage by thor oughly studying the following figure and using the attached heat insulating materials...

Page 8: ...ing piping Secure a downward gradient of 1 100 or more for the drain pipe To accomplish this mount supporting brackets at an interval of 1 1 5 m Precautions when doing drain up piping work Make sure t...

Page 9: ...d switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes light ning rods or telephone ground wires Gas pipes might cause explosions...

Page 10: ...ws Use the correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw will not be properly tightened If the te...

Page 11: ...actory set Insert Insert Power supply wiring Transmission wiring Switch Fuse Power supply Main switch Remote controller Indoor unit BS unit Only for Heat recovery system L N L N IN D OUT D F1 F2 F1 F2...

Page 12: ...terminals T1 and T2 of the terminal block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF O...

Page 13: ...No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPERATION Refer to the installation manual of the outdoor unit The operatio...

Page 14: ...0303 HT 3P086156 8J EM02A082A...

Reviews: