Installation

EDUS39-600-F5

26

FXHQ-M

(2) Check to make sure the water flows smoothly after 

piping is complete.

• Slo

w

ly pour 600ml of drain-checking 

w

ater into the drain 

pan through the air outlet.

CAUTION

•   If 

w

ater collects on drain pipe it 

w

ill cause blockage.

8.

ELECTRIC WIRING WORK 

8-1 GENERAL INSTRUCTIONS 

• All field-supplied parts, materials, and electrical 

w

orks 

must conform to local codes.

• Use only copper 

w

ire .

• For electrical 

w

iring 

w

ork, refer to the 

  

Wiring Diagram 

Label

 attached to the control box lid.

• For remote controller 

w

iring details, refer to the installation 

manual attached to the remote controller.

• All  

w

iring must be performed by an authorized electrician.

• This system consists of multiple indoor units. Mark each 

indoor unit as unit A, unit B,and so on, and be sure the ter-
minal board 

w

iring to the outdoor unit and BS unit are prop-

erly matched. If controls 

w

iring and piping bet

w

een the 

outdoor and indoor units are mismatched, a communica-
tions malfunction is likely

.

• An  ground leakage circuit breaker capable of shutting 

do

w

n the po

w

er supply to the entire system must be 

installed.

• Refer to the installation manual attached to the outdoor unit 

for the size of po

w

er supply 

w

iring connected to the outdoor 

unit, the capacity of the circuit breaker and s

w

itch, and 

w

ir-

ing instructions.

• Be sure to ground the air conditioner.

DANGER

• Do not ground units to 

w

ater pipes, telephone 

w

ires, or 

lightning rods because incomplete grounding  can cause a 
severe shock hazard resulting in severe injury or death. Do 
not ground to gas pipes because a gas leak  can result in an 
explosion  leading to severe injury or death.

8-2 ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A);MFA: Max. Fuse Amps (A) 
W: Fan Motor Rated Output (W);FLA: Full Load Amps (A)

8-3 SPECIFICATIONS FOR FIELD SUPPLIED 

FUSES AND WIRES 

Allo

w

able length of transmission 

w

ire bet

w

een indoor/out-

door units and bet

w

een the indoor unit and the remote con-

troller 

w

ire are as follo

w

s.

(1) Outdoor unit – Indoor unit:

Max. 3280 ft. (Total 

w

ire length: 6560 ft.)

(2) Indoor unit – Remote controller:

Max. 1640 ft.

9.

WIRING EXAMPLE AND HOW TO SET 
THE REMOTE CONTROLLER

9-1 HOW TO CONNECT WIRES

CAUTION

• Even if the control box lid is removed, pull the remote con-

troller 

w

ire, transmission 

w

ire, and the po

w

er supply 

w

ire 

inside the unit, using conduits for each, so that the 

w

ires do 

not come into contact 

w

ith the opening section of the metal 

casing.

• Pass conduits through the 

w

all and secure them along 

w

ith 

the refrigerant pipe in order to prevent external pressure  to 
transmission 

w

ire and po

w

er supply 

w

ire.

• Prevent dust from entering into the unit by filling the gap 

around the pipe or 

w

ire 

w

ith corking or putty.

• Arrange the 

w

ires and fix  the lid firmly so that  it does not 

float during 

w

iring 

w

ork.

• Do not clamp remote controller 

w

ire and transmission 

w

ire 

together 

w

ith po

w

er supply 

w

ire. Doing so may cause mal-

function.

• Remote controller 

w

ire, transmission 

w

ire, and po

w

er sup-

ply 

w

ire should be located at least 5  inches from other 

electrical 

w

ires. 

N

ot follo

w

ing this guideline may result in 

malfunction due to electrical noise.

Method of wiring power supply, units, and connecting 
remote controller wiring: (Refer to Fig. 27)

Air outlet

Plastic container for pouring

Make sure not to splash the 

w

ater.

Fig. 25

Units

Po

w

er supply

Fan motor

Model

Hz

Volts

Voltage 

range

MCA

MFA

W

FLA

FXHQ12MVJU

60

208-

230V

Max. 

253V

Min.  

187V

0.8

15

62

0.6

FXHQ24MVJU

1.0

15

130

0.8

FXHQ36MVJU

1.4

15

130

1.1

Model

Po

w

er supply 

w

iring

Remote controller 

w

iring

Transmission 

w

iring

Field fuses 

Size

Wire

Size

FXHQ12MVJU

15A

Wire size 

must comply 

w

ith local 
codes

2 conducutor

stranded 

copper, non-

shielded, 

PVC or vinyl 

jacket  

w

ire

AWG18-16

FXHQ24MVJU

FXHQ36MVJU

Summary of Contents for FXHQ-M

Page 1: ...AMERICAS EDUS 39 600 F5 FXHQ M Ceiling Suspended Type...

Page 2: ...ecifications 3 3 Dimensions 4 4 Piping Diagrams 7 5 Wiring Diagrams 8 6 Electric Characteristics 9 7 Capacity Tables 10 7 1 Cooling Capacity 10 7 2 Heating Capacity 11 8 Air Velocity and Temperature D...

Page 3: ...erating sound H L 12 42 38 24 44 42 36 46 42 dB A Low operating sound Uses the new quiet stream fan and many more quiet technologies Sound absor ption member Turbulent flow is produced Straightening v...

Page 4: ...Drive Direct Drive Direct Drive Direct Drive Temperature Control Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooling and Heating Microprocessor Thermostat for Cooli...

Page 5: ...Dimensions EDUS39 600 F5 4 FXHQ M 3 Dimensions FXHQ12MVJU 3D049330...

Page 6: ...EDUS39 600 F5 Dimensions FXHQ M 5 FXHQ24MVJU 3D049331...

Page 7: ...Dimensions EDUS39 600 F5 6 FXHQ M FXHQ36MVJU 3D049332...

Page 8: ...ir temperature R2T Thermistor for liquid line temperature R3T Thermistor for gas line temperature Capacity GAS Liquid 12M 1 2 1 4 24 36M 5 8 3 8 C 4D024460A Heat exchanger Gas piping connection port L...

Page 9: ...Wiring Diagrams EDUS39 600 F5 8 FXHQ M 5 Wiring Diagrams FXHQ12MVJU FXHQ24MVJU FXHQ36MVJU 3D048116...

Page 10: ...EDUS39 600 F5 Electric Characteristics FXHQ M 9 6 Electric Characteristics C 4D049333...

Page 11: ...9 4 12 3 9 2 12 4 8 8 12 7 8 7 24 75 18 9 15 3 21 5 16 6 24 0 17 1 26 5 17 8 28 0 18 1 28 5 17 2 79 18 9 15 3 21 5 16 6 24 0 17 1 26 5 17 8 27 6 18 0 28 1 17 0 83 18 9 15 3 21 5 16 6 24 0 17 1 26 5 1...

Page 12: ...0 56 0 15 5 14 7 14 0 13 5 13 0 12 3 24 22 0 20 0 23 3 23 3 23 3 23 2 23 2 23 2 26 0 24 0 24 5 24 4 24 4 24 3 24 3 24 3 30 0 28 0 25 6 25 5 25 5 25 5 25 4 24 5 35 0 32 0 26 7 26 6 26 6 26 6 26 0 24 5...

Page 13: ...Distributions EDUS39 600 F5 12 FXHQ M 8 Air Velocity and Temperature Distributions FXHQ12M Cooling mode FXHQ12M Heating mode 3D052938 AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIBUTIONS AIRFLOW DISTRIBUTI...

Page 14: ...600 F5 Air Velocity and Temperature Distributions FXHQ M 13 FXHQ24M Cooling mode FXHQ24M Heating mode 3D052939 AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIBUTIONS AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIB...

Page 15: ...ocity and Temperature Distributions EDUS39 600 F5 14 FXHQ M FXHQ36M Cooling mode FXHQ36M Heating mode 3D052940 AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIBUTIONS AIRFLOW DISTRIBUTIONS TEMPERATURE DISTRIB...

Page 16: ...Octave Band Level 208V 230V Ceiling Suspended Type Notes Operation noise differs with operation and ambient conditions dBA Model 208 230V 60Hz H L FXHQ12MVJU 38 33 FXHQ24MVJU 44 36 FXHQ36MVJU 46 41 F...

Page 17: ...erious injury or death Do not install unit in an area where flammable mate rials are present due to risk of explosions that can cause serious injury or death Refrigerant gas may produce toxic gas if i...

Page 18: ...lectrical parts turn off the unit Be sure to establish a ground Do not ground the unit to a utility pipe arrester or tele phone ground Incomplete ground may cause electrical shock or fire A high surge...

Page 19: ...r opening hold the unit by the hanger brackets 4 Do not apply force to the refrigerant piping drain piping or plastic parts For the installation of an outdoor unit refer to the installa tion manual at...

Page 20: ...aterials are present due to risk of explosion resulting in serious injury or death WARNING If the supporting structural members are not strong enough to take the unit s weight the unit could fall out...

Page 21: ...N 1 Relative position of holes for indoor unit suspension bolt position piping and wiringg 2 Drill holes for suspension bolts refrigerant drain pipe and wire Refer to the paper pattern for installatio...

Page 22: ...the arrow and remove them Refer to Fig 8 4 Attach the suspension bolts Use suspension bolts which are W3 8 or M8 M10 in size Adjust the distance of the suspension bolts from the ceiling in advance Re...

Page 23: ...ng is set either level or slightly tilted to ensure proper drainage Refer to Fig 12 A When the drain piping is tilted to the right or to the right and back do the following Place it level or tilt it s...

Page 24: ...you can use the following installation method When you keep tightening the flare nut with a spanner there is a point where the tightening torque suddenly increases From that position further tighten...

Page 25: ...sissors to cut the removed penetration lid into the shape of the pipe and attach As when removing the top penetration lid secure the lead lines for the swing motor and thermistor by passing them thro...

Page 26: ...pipe completely into the drain socket and securely attach the metal clamp bracket inside the gray tape area on the inserted tip of the drain pipe Refer to Fig 22 Screw the screws on the metal clamp br...

Page 27: ...s A 8 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRES Allowable length of transmission wire between indoor out door units and between the indoor unit and the remote con troller wire are as follows...

Page 28: ...e remote controller wire and transmission wire pass to a maximum of 2 wires WARNING Never connect power supply wiring to the terminal block for remote controller wiring as this could damage the entire...

Page 29: ...wire refer to the INSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 9 2 WIRING EXAMPLE Fit the power supply wire of each unit with a switch and fuse as shown in the drawing C...

Page 30: ...e remote controller in accordance with the installation manual Setting can be made by changing the Mode No FIRST CODE NO and SECOND CODE NO For setting and operation refer to the FIELD SETTING section...

Page 31: ...arting and stopping of equipment Individual indoor units can be field prgrammed at the remote controller to change the T1 T2 sequence of operation of the equipment based upon the application How to se...

Page 32: ...on code shows the check oper ation has not been performed yet 12 1 HOW TO DIAGNOSE FOR MALFUNCTION With the power on it is possible to monitor the type of malfunction by looking at the malfunction cod...

Page 33: ...ON CODE For places where the malfunction code is left blank the indication is not displayed The shaded areas indicate when the unit does not display a malfunction code and con tinues running even thou...

Page 34: ...or nothing pro grammed in the data hold IC U0 Low pressure drop due to insufficient refrigerant or electronic expanison valve error U2 Power source voltage failure U3 Failure to carry out check operat...

Page 35: ...er bracket 4 Clamp Quantity 1 pc 1 pc 8 pcs 9 pcs Shape Name 5 Paper pattern for installation Insulation pipe cover Sealing pad Quantity 1 pc 1 each 1 each Shape 6 For gas pipe 7 For liquid pipe 8 Lar...

Page 36: ...1645 Wallace Drive Suite 110 Carrollton TX75006 info daikinac com www daikinac com EDUS39 600 F5 Printed in U S A 05 2007 AMERICAS May 2007...

Reviews: