![background image](http://html1.mh-extra.com/html/daikin/fxhq-m/fxhq-m_engineeiring-data_2459727024.webp)
EDUS39-600-F5
Installation
FXHQ-M
23
6-1 GENERAL INSTRUCTIONS
• For refrigerant pipe of outdoor units, see the installa-
tion manual attached to the outdoor unit.
• Execute thermal insulation work completely on both
sides of the gas pipe and the li
q
uid pipe or a water leak
may occur.
.
(The temperature of the gas pipe can reach up to
approximately 250°F, so use insulation pipe cover
that is sufficiently resistant.)
• In cases where the temperature and humidity of the
refrigerant pipe sections might exceed 86°F or RH
80%, reinforce the thermal insulation (3/4 in. or thicker)
or condensate may form on the surface of the insula-
tion pipe cover.
Before refrigerant pipe work, check which type of
refrigerant is used. Proper operation is not possible if
the types of refrigerant are not the same.
6-2 CONNECTING THE REFRIGERANT PIPE
• Ensure outdoor unit is charged
w
ith refrigerant.
• Use copper alloy seamless pipes.
• Be sure to use both a spanner and tor
q
ue
w
rench together,
as sho
w
n in the dra
w
ing,
w
hen connecting or disconnect-
ing pipes to/from the unit.
(Refer to Fig. 13)
• Refer to Table 2 to determine the proper tightening tor
q
ue.
• Refer to Table 2 for the dimensions of flare shape.
• When connecting the flare nut, coat the flare section (both
inside and outside)
w
ith ester oil or ether oil, rotate three or
• four times first, then scre
w
in.
(Refer to Fig. 14)
• Use the flare nut include
w
ith the main body of the unit.
CAUTION
• Oil must not adhere to any e
q
uipment other than a flare. If
oil adheres to resin or other parts, deterioration may occur..
Table 2
CAUTION
• Overtightening may damage the flare and cause a refriger-
ant leakage.
Not recommended but in case of emergency
You must use a tor
q
ue
w
rench but if one is not available,
you can use the follo
w
ing installation method:
When you keep tightening the flare nut
w
ith a spanner, there is
a point
w
here the tightening tor
q
ue suddenly increases. From
that position, further tighten the flare nut the angle sho
w
n
belo
w
:
Table 3
After the work is finished, make sure to check that
there is no gas leak.
6-3 BRAZING REFRIGERANT PIPING
• Do not use flux
w
hen brazing refrigerant pipe. Use phos-
phor copper brazing filler metal (BCuP)
w
hich does not
re
q
uire flux.
• Flux has an extremely negative effect on refrigerant piping
systems. For instance, if chlorine based flux is used, it
w
ill
cause pipe corrosion. If the flux contains fluorine, it
w
ill
damage the refrigerant oil.
• Before brazing local refrigerant pipe, nitrogen gas shall be
blo
w
n through the pipe to expel air from the pipe.
If brazing is done
w
ithout nitrogen gas blo
w
ing, a large
amount of oxide film develops inside the pipe
w
hich can
cause system malfunction.
• When brazing the refrigerant pipe, only begin brazing after
having carried out nitrogen substitution or
w
hile inserting
nitrogen into the refrigerant pipe. Once this is done, con-
nect the indoor unit
w
ith a flared or a flanged connection.
•
N
itrogen should be set to 2.9 psi
w
ith a pressure-reducing
valve if brazing
w
hile inserting nitrogen into the pipe.
(Refer to Fig. 15)
Tor
q
ue
w
rench
Flare nut
Pipe union
Spanner
Fig. 13
Fig. 14
Ester oil or ether oil.
Pipe size
(in.)
Tightening
tor
q
ue (ft.lbf)
Flare dimen-
sions A
(in.)
Flare shape (in.)
φ
1/4
10.4–12.7
0.342–0.358
φ
3/8
24.1–29.4
0.504–0.520
φ
1/2
36.5–44.5
0.638–0.654
φ
5/8
45.6–55.6
0.760–0.776
Pipe size (in.) Further tightening angle Recommended arm length of tool (in.)
φ
1/4
60 to 90 degrees
Approx. 5 7/8
φ
3/8
60 to 90 degrees
Approx. 7 7/8
φ
1/2
30 to 60 degrees
Approx. 9 13/16
φ
5/8
30 to 60 degrees
Approx. 11 13/16
R0.016-0.031
A
90˚± 2˚
45˚±2˚
Refrigerant pipe
Part to be
brazed
Taping
Pressure-reducing
valve
hands valve
N
itrogen
N
itrogen
Fig. 15
Summary of Contents for FXHQ-M
Page 1: ...AMERICAS EDUS 39 600 F5 FXHQ M Ceiling Suspended Type...
Page 5: ...Dimensions EDUS39 600 F5 4 FXHQ M 3 Dimensions FXHQ12MVJU 3D049330...
Page 6: ...EDUS39 600 F5 Dimensions FXHQ M 5 FXHQ24MVJU 3D049331...
Page 7: ...Dimensions EDUS39 600 F5 6 FXHQ M FXHQ36MVJU 3D049332...
Page 10: ...EDUS39 600 F5 Electric Characteristics FXHQ M 9 6 Electric Characteristics C 4D049333...