EDUS39-600-F5
Installation
FXHQ-M
29
3. When including BS unit
NOTE
1. It is not necessary to designate an indoor unit address
w
hen using group control. The address is automatically
set
w
hen po
w
er is activated.
2. All transmission
w
ires except for remote controller
w
ires
are polarized and must match the terminal symbol.
3. A single s
w
itch can be used to supply po
w
er to units on
the same system but branch s
w
itches and branch circuit
breakers must be selected carefully.
4. Do not ground the e
q
uipment on gas pipes,
w
ater pipes,
or lightning rods, or crossground
w
ith telephones.
Improper grounding can result in electric shock.
10. ATTACHING THE SUCTION GRILLE,
THE DECORATION PANELS AND THE
PROTECTION NET
Once
w
iring is complete, firmly attach the control box lid, the
suction grille, the decoration panels, and the protection net in
the order opposite to detachment.
• Attach the protection net from the
w
ay of the hook (i), fix 2
securing scre
w
s of the middle of the other side first (ii), then
fix the remaining securing scre
w
s (iii).
11. FIELD SETTING
Make sure the control box lids are closed on the indoor
and outdoor units, and turn on the power.
Field setting must be made from the remote controller in
accordance with the installation manual.
• Setting can be made by changing the
Mode No
.,
FIRST
CODE NO
., and
SECOND CODE NO.
• For setting and operation, refer to the
FIELD SETTING
section in the installation manual of the remote controller.
11-1 SETTING AIR FILTER SIGN
• Remote controllers are e
q
uipped
w
ith li
q
uid crystal display
air filter signs to display
w
hen to clean air filters.
• Change the
SECOND CODE NO
. according to Table 5
depending on the amount of dirt or dust in the room.
SECOND CODE NO
. is factory set to [01] for air filter con-
tamination-light.
Table 5
Wireless remote controllers:
• When using
w
ireless remote controllers, a
w
ireless remote-
controller address setting is necessary. Refer to the instal
I
N
/D OUT/D
F
1
F
2
F
1
F
2
I
N
/D
OUT/D
F
1
F
2
F
1
F
2
L
1
L
2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
BS unit
Outdoor unit
Po
w
er
supply
208-230V
60Hz
Indoor unit A
Most
do
w
nstream
indoor unit
Po
w
er
supply
208-230V
60Hz
Control box
Control box
I
N
/D
OUT/D
F
1
F
2
F
1
F
2
BS unit
Control box
L
1
L
2
P
1
P
2
P
1
P
2
F
1
F
2
T
1
T
2
Remote
controller
L
2
L
1
Fig. 33
L
2
L
1
Setting
Spacing time of dis-
play air filter sign
(long life type)
Mode
N
o.
FIRST
CODE
N
O.
SECO
N
D
CODE
N
O.
Air filter contamina-
tion-light
Approx. 2500 hrs
10 (20)
0
01
Air filter contamina-
tion-heavy
Approx. 1250 hrs
02
Decoration
panel
Protection net
(ii)
(ii)
(i)
(i)
Hook
Hook
(ii)
Fig. 34
Protection net
securing scre
w
s (M4)
(iii)
Summary of Contents for FXHQ-M
Page 1: ...AMERICAS EDUS 39 600 F5 FXHQ M Ceiling Suspended Type...
Page 5: ...Dimensions EDUS39 600 F5 4 FXHQ M 3 Dimensions FXHQ12MVJU 3D049330...
Page 6: ...EDUS39 600 F5 Dimensions FXHQ M 5 FXHQ24MVJU 3D049331...
Page 7: ...Dimensions EDUS39 600 F5 6 FXHQ M FXHQ36MVJU 3D049332...
Page 10: ...EDUS39 600 F5 Electric Characteristics FXHQ M 9 6 Electric Characteristics C 4D049333...