EDUS39-600-F5
Installation
FXHQ-M
21
(3-2)
Remove the decoration panels (left and right) and the
protection net.
• After removing the securing scre
w
s for the decoration
panels (one each), pull them for
w
ard in the direction of
the arro
w
and remove them.
(Refer to Fig. 3)
• Remove the securing scre
w
s for the protection net.
(Refer to Fig. 3)
• Raise one side of the protection net up
w
ardin the direc-
tion of the arro
w
(i) and remove back to
w
ard the arro
w
(ii).
(Refer to Fig. 4, 5)
Take out the accessories.
(3-3)
Remove the rear metal plate for transmission
w
ire,
remote controller
w
ire and refrigerant pipe.
• It is necessary to drill the knock out hole in the remov-
able part. Knock do
w
n several times
w
ith a punch and
hammer and remove the removable part
w
ith pliers.
• When setting the refrigerant pipe to the rear side,
remove the securing scre
w
s and the metal plate.
(Refer
to Fig. 6)
(3-4)
Remove the hanger brackets.
• Loosen the 2 bolts (M8) used to attach the hanger
brackets
w
hich are on each side (4 places left and right)
to
w
ithin 3/8 in..
(Refer to Fig. 7, 8)
• After removing the securing scre
w
s (M5) for the hanger
brackets on the rear side, pull the hanger brackets back
in the direction of the arro
w
, and remove them.
(Refer
to Fig. 8)
•
(4) Attach the suspension bolts. Use suspension bolts
which are W3/8 or M8-M10 in size.
• Adjust the distance of the suspension bolts from the ceiling
in advance.
(Refer to Fig. 9)
NOTE
• Use a hole-in anchor for existing ceilings, and a sunken
insert, sunken anchor or other field supplied parts for ne
w
ceilings to reinforce the ceiling to bear the
w
eight of the
unit. Adjust clearance from the ceiling before proceeding
further.
Decoration panel
securing scre
w
(M4)
Decoration panel
Fig. 3
Protection net
securing scre
w
s (M4)
Decoration
panel
Decoration panel
securing scre
w
s (M4)
Decoration panel
Decoration
panel
Accessories
Fig. 4
Fig. 5
Protection net
(ii)
(i)
(ii)
(i)
Hook
Protection net
If it raises too much,
a hook stops catching
and falling out.
Removable part
(metal plate)
If setting the refrigerant pipe to
the rear side, remove this metal plate.
After removing, attach the resin bush
(Refer to Fig. 26)
Metal plate
securing
scre
w
(M4)
Fig. 6
If setting the drain pipe to the
right side, block up the hole for
drain pipe
w
ith pate etc.
Indoor unit
Hanger bracket
3/8 or less
Length of loosening
should be less than 3/8
(Length : in.)
Fig. 7
Hanger bracket
fixing scre
w
(M5)
Hanger bracket
Hanger bracket
setting bolt (M8)
Fig. 8
Ceiling slab
Anchor
Suspension bolt
False ceiling
1–2 3/16
(Length : in.)
All the above parts are field supplied.
Fig. 9
Summary of Contents for FXHQ-M
Page 1: ...AMERICAS EDUS 39 600 F5 FXHQ M Ceiling Suspended Type...
Page 5: ...Dimensions EDUS39 600 F5 4 FXHQ M 3 Dimensions FXHQ12MVJU 3D049330...
Page 6: ...EDUS39 600 F5 Dimensions FXHQ M 5 FXHQ24MVJU 3D049331...
Page 7: ...Dimensions EDUS39 600 F5 6 FXHQ M FXHQ36MVJU 3D049332...
Page 10: ...EDUS39 600 F5 Electric Characteristics FXHQ M 9 6 Electric Characteristics C 4D049333...