5 Configuration

Installation and operation manual

9

FXFQ20~125BVEB
VRV system air conditioner
4P540926-1B – 2019.01

5

Configuration

5.1

Field settings

Make  the  following  field  settings  so  that  they  correspond  with  the
actual installation setup and with the needs of the user:

▪ Ceiling height

▪ Design decoration panel (if applicable)

▪ Air flow direction

▪ Air volume when thermostat control is OFF

▪ Time to clean air filter

Setting: Ceiling height

This  setting  must  correspond  with  the  actual  distance  to  the  floor,
capacity class and air flow directions.

▪ For 3-way and 4-way air flows (which require an optional blocking

pad  kit),  see  the  installation  manual  of  the  optional  blocking  pad
kit.

▪ For all-round air flow, use the table below.

If the distance to the floor is (m)

Then

1

FXFQ20~100

FXFQ125

M

C1

C2

≤2.7

≤3.2

13 (23)

0

01

2.7<x≤3.0

3.2<x≤3.6

02

3.0<x≤3.5

3.6<x≤4.2

03

Setting: Decoration panel type

When  installing  or  changing  the  decoration  panel  type,  ALWAYS
check if the correct values are set.

If the … decoration panel is used

Then

1

M

C1

C2

Standard or self-cleaning

13

(23)

15

01

Design

02

Setting: Air flow direction

This setting must correspond with the actual used air flow directions.
See  the  installation  manual  of  the  optional  blocking  pad  kit  and  the
manual of the user interface.

Default: 01 (= all-round air flow)

Example: 

1

2

3

4

1

2

3

4

1

2

3

a

b

c

a

All-round air flow

b

4-way air flow (all air outlets open, 2 corners closed)
(optional blocking pad kit required)

c

3-way air flow (1 air outlet closed, all corners open)
(optional blocking pad kit required)

Setting: Air volume when thermostat control is OFF

This  setting  must  correspond  with  the  needs  of  the  user.  It
determines  the  fan  speed  of  the  indoor  unit  during  thermostat  OFF
condition.

1

If you have set the fan to operate, set the air volume speed:

If you want

Then

1

Outdoor unit

M

C1

C2

During cooling
operation

LL

2

12

(22)

6

01

Setup volume

2

02

During heating
operation

LL

2

12

(22)

3

01

Setup volume

2

02

Setting: Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which the 

TIME TO CLEAN AIR FILTER

notification is displayed on the user interface. When using a wireless
user  interface,  you  must  also  set  the  address  (see  the  installation
manual of the user interface).

If you want an interval of…

(air contamination)

Then

1

M

C1

C2

±2500 h (light)

10 (20)

0

01

±1250 h (heavy)

02

No notification

3

02

Individual setting in a simultaneous operation system

We  recommend  using  the  optional  user  interface  to  set  the  slave
unit.

Perform the following steps:

2

Change  the  second  code  number  to  02  to  perform  individual
setting on the slave unit.

If you want to set the slave unit as…

Then

1

M

C1

C2

Unified setting

21(11)

01

01

Individual setting

02

3

Perform field setting for the master unit.

4

Turn off the main power supply switch.

5

Disconnect  the  remote  controller  from  the  master  unit  and
connect it to the slave unit.

6

Change to individual setting.

7

Perform field setting for the slave unit.

8

Turn off the main power supply or, in case of more slave units,
repeat the previous steps for all slave units.

9

Disconnect the user interface from the slave unit and reconnect
it to the master unit.

It  is  not  necessary  to  rewire  the  remote  controller  from  the  master
unit  if  the  optional  user  interface  is  used.  (However,  remove  the
wires  attached  to  the  user  interface  terminal  board  of  the  master
unit)

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

C1

: First code number

C2

: Second code number

: Default

(2)

Fan speed:

LL

: Low fan speed

Setup volume

: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button

on the user interface.

Summary of Contents for FXFQ20BVEB

Page 1: ...d operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXFQ20BVEB FXFQ25BVEB FXFQ32BVEB FXFQ40BVEB FXFQ50BVEB FXFQ63BVEB FXFQ80BVEB FXFQ100B...

Page 2: ...pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nur...

Page 3: ...n airflow 14 12 4 1 To start the active circulation airflow 14 13 Maintenance and service 14 13 1 Precautions for maintenance and service 14 13 2 Cleaning the air filter suction grille air outlet and...

Page 4: ...allation with standard decoration panel 256 mm In case of installation with design decoration panel 294 mm In case of installation with self cleaning decoration panel 263 mm In case of installation wi...

Page 5: ...a1 Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine t...

Page 6: ...cessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against condensat...

Page 7: ...exposed to any substance which may corrode components containing refrigerant unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected aga...

Page 8: ...Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface ca...

Page 9: ...t the air volume speed If you want Then1 Outdoor unit M C1 C2 During cooling operation LL2 12 22 6 01 Setup volume2 02 During heating operation LL2 12 22 3 01 Setup volume2 02 Setting Time to clean ai...

Page 10: ...m a test run This task is only applicable when using the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTIC...

Page 11: ...here is a voltage imbalance There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three elect...

Page 12: ...ermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrestor SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Va...

Page 13: ...eezing of the outdoor unit s air cooled coil increases over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operati...

Page 14: ...mation Configuration 3 Select Circulation airflow Return Setting Main Menu 1 2 Circulation Airflow Individual Air Direction Energy Saving Options Schedule Maintenance Information Configuration 4 Choos...

Page 15: ...quipment How to clean the air filter NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation 1 Open the suction grille Standard panel 1 Design panel 1 1 2 2 2 Remo...

Page 16: ...he atmosphere Refrigerant type R410A Global warming potential GWP value 2087 5 NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicat...

Page 17: ...4P540926 1B 2019 01 15 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation U...

Page 18: ......

Page 19: ......

Page 20: ...4P540926 1B 2019 01 Copyright 2018 Daikin...

Reviews: