background image

4 Installation

Installation and operation manual

6

FXFQ20~125BVEB

VRV system air conditioner

4P540926-1B – 2019.01

Level

. Make sure the unit is level at all 4 corners using a level or a

water-filled vinyl tube.

c

b

b

a

a

Level

b

Vinyl tube

c

Water level

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

4.1.2

Guidelines when installing the drain
piping

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe size.

 Keep the pipe size equal to or greater than that of the

connecting  pipe  (vinyl  pipe  of  25  mm  nominal  diameter  and
32 mm outer diameter).

Slope.

 Make sure the drain piping slopes down (at least 1/100) to

prevent air from being trapped in the piping. Use hanging bars as
shown.

1~1.5 m

a

a

Hanging bar

O

Allowed

X

Not allowed

Rising  piping

.  If  necessary  to  make  the  slope  possible,  you  can

install rising piping.

▪ Drain  hose  inclination:  0~75  mm  to  avoid  stress  on  the  piping

and to avoid air bubbles.

▪ Rising  piping:  ≤300  mm  from  the  unit,  ≤675  mm  perpendicular

to the unit.

≤675

≤300

0~75

1000~1500

(mm)

b

a

b

c

a

d

d

a

Metal clamp (accessory)

b

Drain hose (accessory)

c

Rising drain piping (vinyl pipe of 25 mm nominal diameter
and 32 mm outer diameter) (field supply)

d

Hanging bars (field supply)

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

Combining  drain  pipes.

  You  can  combine  drain  pipes.  Make

sure  to  use  drain  pipes  and  T-joints  with  a  correct  gauge  for  the
operating capacity of the units.

≥100

675

(mm)

a

a

T-joint

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Push  the  drain  hose  as  far  as  possible  over  the  drain  pipe
connection.

2

Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.

3

Check  for  water  leaks  (see 

"To  check  for  water  leaks"  on

page 6

).

4

Install the insulation piece (drain pipe).

5

Wind  the  large  sealing  pad  (=  insulation)  around  the  metal
clamp and drain hose, and fix it with cable ties.

6

Connect the drain piping to the drain hose.

≤4 mm

A

A'

A-A'

A

A'

f

6

5

2

c

e

4

b

a

d

b

a

d

c

3

1

2~6

1

a

Drain pipe connection (attached to the unit)

b

Drain hose (accessory)

c

Metal clamp (accessory)

d

Large sealing pad (accessory)

e

Insulation piece (drain pipe) (accessory)

f

Drain piping (field supply)

To check for water leaks

The  procedure  differs  depending  on  whether  electrical  wiring  is
already finished. When electrical wiring is not finished yet, you need
to  temporarily  connect  the  user  interface  and  power  supply  to  the
unit.

When electrical wiring is not finished yet

1

Temporarily connect electrical wiring.

Summary of Contents for FXFQ20BVEB

Page 1: ...d operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXFQ20BVEB FXFQ25BVEB FXFQ32BVEB FXFQ40BVEB FXFQ50BVEB FXFQ63BVEB FXFQ80BVEB FXFQ100B...

Page 2: ...pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nur...

Page 3: ...n airflow 14 12 4 1 To start the active circulation airflow 14 13 Maintenance and service 14 13 1 Precautions for maintenance and service 14 13 2 Cleaning the air filter suction grille air outlet and...

Page 4: ...allation with standard decoration panel 256 mm In case of installation with design decoration panel 294 mm In case of installation with self cleaning decoration panel 263 mm In case of installation wi...

Page 5: ...a1 Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine t...

Page 6: ...cessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against condensat...

Page 7: ...exposed to any substance which may corrode components containing refrigerant unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected aga...

Page 8: ...Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface ca...

Page 9: ...t the air volume speed If you want Then1 Outdoor unit M C1 C2 During cooling operation LL2 12 22 6 01 Setup volume2 02 During heating operation LL2 12 22 3 01 Setup volume2 02 Setting Time to clean ai...

Page 10: ...m a test run This task is only applicable when using the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTIC...

Page 11: ...here is a voltage imbalance There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three elect...

Page 12: ...ermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrestor SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Va...

Page 13: ...eezing of the outdoor unit s air cooled coil increases over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operati...

Page 14: ...mation Configuration 3 Select Circulation airflow Return Setting Main Menu 1 2 Circulation Airflow Individual Air Direction Energy Saving Options Schedule Maintenance Information Configuration 4 Choos...

Page 15: ...quipment How to clean the air filter NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation 1 Open the suction grille Standard panel 1 Design panel 1 1 2 2 2 Remo...

Page 16: ...he atmosphere Refrigerant type R410A Global warming potential GWP value 2087 5 NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicat...

Page 17: ...4P540926 1B 2019 01 15 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation U...

Page 18: ......

Page 19: ......

Page 20: ...4P540926 1B 2019 01 Copyright 2018 Daikin...

Reviews: