4 Installation

Installation and operation manual

8

FXFQ20~125BVEB

VRV system air conditioner

4P540926-1B – 2019.01

4.3.1

Specifications of standard wiring
components

Component

Class

20~40

50

63

80

100

125

Power
supply cable

MCA

(a)

0.5 A

0.6 A 0.7 A

1.2

A

1.3 A 1.4 A

Voltage

220~240 V

Phase

1~

Frequency

50/60 Hz

Wire sizes

Must comply with applicable legislation

Interconnection cable

4-core cable 1.5 mm

2

~2.5 mm

2

 and

applicable for 220~240 V

H05RN-F (60245 IEC 57)

User interface cable

Vinyl cords with 0.75 to 1.25 mm² sheath

or cables (2‑core wires)

Maximum 500 m

H03VV-F (60227 IEC 52)

Recommended field fuse

16 A

Earth leakage circuit
breaker

Must comply with applicable legislation

(a)

MCA=Minimum circuit ampacity. Stated values are
maximum values (see electrical data of combination with
indoor units for exact values).

4.3.2

To connect the electrical wiring on the
indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located at the inside of the service cover).

▪ For instructions on how to connect the decoration panel

and the sensor kit, see the installation manual delivered
with the panel or the kit.

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover.

2

User  interface  cable

:  Route  the  cable  through  the  frame,

connect the cable to the terminal block, and fix the cable with a
cable tie.

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

4

Divide  the  small  sealing  (accessory)  and  wrap  it  around  the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

5

Reattach the service cover.

NOTICE

When  closing  the  service  cover,  make  sure  that  the
tightening torque for screws is ≤1.5N•m.

Wiring example

For  complete  system  example  refer  to  the  installer  and  user
reference  guide  located  on: 

http://www.daikineurope.com/support-

and-manuals/product-information/

.

a

b

c

d

e

f

h

g

i

a

Power supply

b

Main switch

c

Power supply wiring

d

Unit interconnection wiring

e

Switch

f

Fuse

g

BS unit (only REYQ)

h

Indoor unit

i

User interface

a

(mm)

e

e

b

c

10~15

70~90

10~20

d

c

b

10~15

d

70~90

7

N

L

a

Service cover (with wiring diagram on the back)

b

Opening for cables

c

Connection of power supply (including earth)

d

Cable tie

e

Connection of user interface and interconnection cable

Summary of Contents for FXFQ20BVEB

Page 1: ...d operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXFQ20BVEB FXFQ25BVEB FXFQ32BVEB FXFQ40BVEB FXFQ50BVEB FXFQ63BVEB FXFQ80BVEB FXFQ100B...

Page 2: ...pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nur...

Page 3: ...n airflow 14 12 4 1 To start the active circulation airflow 14 13 Maintenance and service 14 13 1 Precautions for maintenance and service 14 13 2 Cleaning the air filter suction grille air outlet and...

Page 4: ...allation with standard decoration panel 256 mm In case of installation with design decoration panel 294 mm In case of installation with self cleaning decoration panel 263 mm In case of installation wi...

Page 5: ...a1 Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine t...

Page 6: ...cessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against condensat...

Page 7: ...exposed to any substance which may corrode components containing refrigerant unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected aga...

Page 8: ...Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface ca...

Page 9: ...t the air volume speed If you want Then1 Outdoor unit M C1 C2 During cooling operation LL2 12 22 6 01 Setup volume2 02 During heating operation LL2 12 22 3 01 Setup volume2 02 Setting Time to clean ai...

Page 10: ...m a test run This task is only applicable when using the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTIC...

Page 11: ...here is a voltage imbalance There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three elect...

Page 12: ...ermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrestor SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Va...

Page 13: ...eezing of the outdoor unit s air cooled coil increases over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operati...

Page 14: ...mation Configuration 3 Select Circulation airflow Return Setting Main Menu 1 2 Circulation Airflow Individual Air Direction Energy Saving Options Schedule Maintenance Information Configuration 4 Choos...

Page 15: ...quipment How to clean the air filter NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation 1 Open the suction grille Standard panel 1 Design panel 1 1 2 2 2 Remo...

Page 16: ...he atmosphere Refrigerant type R410A Global warming potential GWP value 2087 5 NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicat...

Page 17: ...4P540926 1B 2019 01 15 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation U...

Page 18: ......

Page 19: ......

Page 20: ...4P540926 1B 2019 01 Copyright 2018 Daikin...

Reviews: