7 Disposal

Installation and operation manual

11

FXFQ20~125BVEB
VRV system air conditioner
4P540926-1B – 2019.01

#

Action

Result

4

Press.

The home menu is
displayed.

5

Stop the test run.

#

Action

Result

1

Press at least 4 seconds.

The Service Settings menu
is displayed.

2

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

3

Press.

The unit returns to normal
operation, and the home
menu is displayed.

6.3

Error codes when performing a
test run

If  the  installation  of  the  outdoor  unit  has  NOT  been  done  correctly,
the following error codes may be displayed on the user interface:

Error code

Possible cause

Nothing displayed

(the currently set
temperature is not
displayed)

▪ The  wiring  is  disconnected  or  there  is  a

wiring  error  (between  power  supply  and
outdoor  unit,  between  outdoor  unit  and
indoor  units,  between  indoor  unit  and
user interface).

▪ The  fuse  on  the  outdoor  or  indoor  unit

PCB has blown.

E3, E4 or L8

▪ The stop valves are closed.

▪ The air inlet or air outlet is blocked.

E7

There is a missing phase in case of three-
phase power supply units.

Note: 

Operation will be impossible. Turn

OFF the power, recheck the wiring, and
switch two of the three electrical wires.

Error code

Possible cause

L4

The air inlet or air outlet is blocked.

U0

The stop valves are closed.

U2

▪ There is a voltage imbalance.

▪ There  is  a  missing  phase  in  case  of

three-phase  power  supply  units. 

Note:

Operation  will  be  impossible.  Turn  OFF
the power, recheck the wiring, and switch
two of the three electrical wires.

U4 or UF

The inter-unit branch wiring is not correct.

UA

The outdoor and indoor unit are
incompatible.

7

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

8

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

extranet (authentication required).

8.1

Piping diagram: Indoor unit

b

a

c

a

Liquid pipe connection

b

Gas pipe connection

c

Heat exchanger

8.2

Wiring diagram

8.2.1

Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the
unit.  Part  numbering  is  by  Arabic  numbers  in  ascending  order  for
each part and is represented in the overview below symbol "*" in the
part code.

Symbols

:

Circuit breaker

Protective earth

Connection

Protective earth (screw)

,

Connector

A

Rectifier

Earth

Relay connector

Field wiring

Short-circuit connector

Fuse

Terminal

INDOOR

Indoor unit

Terminal strip

OUTDOOR

Outdoor unit

Wire clamp

Colors:

BLK

Black

ORG

Orange

BLU

Blue

PNK

Pink

BRN

Brown

PRP, PPL

Purple

GRN

Green

RED

Red

GRY

Grey

WHT

White

YLW

Yellow

Legends:

A*P

Printed circuit board

Summary of Contents for FXFQ20BVEB

Page 1: ...d operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXFQ20BVEB FXFQ25BVEB FXFQ32BVEB FXFQ40BVEB FXFQ50BVEB FXFQ63BVEB FXFQ80BVEB FXFQ100B...

Page 2: ...pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nur...

Page 3: ...n airflow 14 12 4 1 To start the active circulation airflow 14 13 Maintenance and service 14 13 1 Precautions for maintenance and service 14 13 2 Cleaning the air filter suction grille air outlet and...

Page 4: ...allation with standard decoration panel 256 mm In case of installation with design decoration panel 294 mm In case of installation with self cleaning decoration panel 263 mm In case of installation wi...

Page 5: ...a1 Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine t...

Page 6: ...cessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against condensat...

Page 7: ...exposed to any substance which may corrode components containing refrigerant unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected aga...

Page 8: ...Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface ca...

Page 9: ...t the air volume speed If you want Then1 Outdoor unit M C1 C2 During cooling operation LL2 12 22 6 01 Setup volume2 02 During heating operation LL2 12 22 3 01 Setup volume2 02 Setting Time to clean ai...

Page 10: ...m a test run This task is only applicable when using the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTIC...

Page 11: ...here is a voltage imbalance There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three elect...

Page 12: ...ermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrestor SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Va...

Page 13: ...eezing of the outdoor unit s air cooled coil increases over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operati...

Page 14: ...mation Configuration 3 Select Circulation airflow Return Setting Main Menu 1 2 Circulation Airflow Individual Air Direction Energy Saving Options Schedule Maintenance Information Configuration 4 Choos...

Page 15: ...quipment How to clean the air filter NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation 1 Open the suction grille Standard panel 1 Design panel 1 1 2 2 2 Remo...

Page 16: ...he atmosphere Refrigerant type R410A Global warming potential GWP value 2087 5 NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicat...