4 Installation

Installation and operation manual

5

FXFQ20~125BVEB
VRV system air conditioner
4P540926-1B – 2019.01

4

Installation

4.1

Mounting the indoor unit

4.1.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

In  case  of  installation  with  a  fresh  air  intake  kit

.  Install  the

fresh air intake kit always 

before

 installing the unit.

Decoration  panel

.  Install  the  decoration  panel  always 

after

installing the unit.

Ceiling  strength

.  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

▪ For existing ceilings, use anchors.

▪ For  new  ceilings,  use  sunken  inserts,  sunken  anchors  or  other

field supplied parts.

A

c

b

d
e

a

A

50~100 mm

: In case of installation with standard panel

100~150 mm

: In case of installation with fresh air intake kit

or design panel

130~180 mm

: In case of installation with self-cleaning

decoration panel

a

Ceiling slab

b

Anchor

c

Long nut or turnbuckle

d

Suspension bolt

e

Suspended ceiling

Suspension bolts.

 Use M8~M10 suspension bolts for installation.

Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
using  a  nut  and  washer  from  the  upper  and  lower  sides  of  the
hanger bracket.

(mm)

780

710

a1

b

b

a2

c

a1

Nut (field supply)

a2

Double nut (field supply)

b

Washer (accessories)

c

Hanger bracket (attached to the unit)

Paper  pattern  for  installation 

(upper  part  of  the  packing).  Use

the paper pattern to determine the correct horizontal positioning. It
contains  the  necessary  dimensions  and  centers.  You  can  attach
the paper pattern to the unit.

a

c

b

d

a

Centre of the unit

b

Centre of the ceiling opening

c

Paper pattern for installation (upper part of the packing)

d

Screws (accessories)

Ceiling opening and unit

:

▪ Make sure the ceiling opening is within the following limits:

Minimum

: 860 mm to be able to fit the unit.

Maximum

:  910  mm  to  ensure  enough  overlap  between  the

decoration  panel  and  the  suspended  ceiling.  If  the  ceiling
opening is larger, add extra ceiling material.

▪ Make  sure  the  unit  and  its  hanger  brackets  (suspension)  are

centered within the ceiling opening.

(mm)

710
840
860~910

950

c
d

e
f

780

840

860~910

950

c

d e

f

a

b

a

Drain piping

b

Refrigerant piping

c

Hanger bracket pitch (suspension)

d

Unit

e

Ceiling opening

f

Decoration panel

If A

Then

B

C

A

C

B

≥860 mm

10 mm

45 mm

≤910 mm

35 mm

20 mm

A

Ceiling opening

B

Distance between the unit and the ceiling opening

C

Overlap between the decoration panel and the suspended
ceiling

Installation  guide

.  Use  the  installation  guide  to  determine  the

correct vertical position.

2

1

2

1

2
1

2
1

A

B

1

1

2

C

a b c

2

1

2

D

A

In case of installation with standard decoration panel

B

In case of installation with fresh air intake kit

C

In case of installation with self-cleaning decoration panel

D

In case of installation with design decoration panel

a

Suspended ceiling

b

Installation guide (accessory)

c

Unit

Summary of Contents for FXFQ20BVEB

Page 1: ...d operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXFQ20BVEB FXFQ25BVEB FXFQ32BVEB FXFQ40BVEB FXFQ50BVEB FXFQ63BVEB FXFQ80BVEB FXFQ100B...

Page 2: ...pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nur...

Page 3: ...n airflow 14 12 4 1 To start the active circulation airflow 14 13 Maintenance and service 14 13 1 Precautions for maintenance and service 14 13 2 Cleaning the air filter suction grille air outlet and...

Page 4: ...allation with standard decoration panel 256 mm In case of installation with design decoration panel 294 mm In case of installation with self cleaning decoration panel 263 mm In case of installation wi...

Page 5: ...a1 Nut field supply a2 Double nut field supply b Washer accessories c Hanger bracket attached to the unit Paper pattern for installation upper part of the packing Use the paper pattern to determine t...

Page 6: ...cessory b Drain hose accessory c Rising drain piping vinyl pipe of 25 mm nominal diameter and 32 mm outer diameter field supply d Hanging bars field supply Condensation Take measures against condensat...

Page 7: ...exposed to any substance which may corrode components containing refrigerant unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected aga...

Page 8: ...Be sure to keep the power line and transmission line apart from each other Transmission wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface ca...

Page 9: ...t the air volume speed If you want Then1 Outdoor unit M C1 C2 During cooling operation LL2 12 22 6 01 Setup volume2 02 During heating operation LL2 12 22 3 01 Setup volume2 02 Setting Time to clean ai...

Page 10: ...m a test run This task is only applicable when using the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTIC...

Page 11: ...here is a voltage imbalance There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck the wiring and switch two of the three elect...

Page 12: ...ermostat S RH Humidity sensor S W SW Operation switch SA F1S Surge arrestor SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Va...

Page 13: ...eezing of the outdoor unit s air cooled coil increases over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operati...

Page 14: ...mation Configuration 3 Select Circulation airflow Return Setting Main Menu 1 2 Circulation Airflow Individual Air Direction Energy Saving Options Schedule Maintenance Information Configuration 4 Choos...

Page 15: ...quipment How to clean the air filter NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation 1 Open the suction grille Standard panel 1 Design panel 1 1 2 2 2 Remo...

Page 16: ...he atmosphere Refrigerant type R410A Global warming potential GWP value 2087 5 NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicat...

Page 17: ...4P540926 1B 2019 01 15 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation U...

Page 18: ......

Page 19: ......

Page 20: ...4P540926 1B 2019 01 Copyright 2018 Daikin...

Reviews: