FC66006893

15

3 DIMENSIONS

In figures from page  p. 53 shows the dimensions of FWZ / FWS / FWR and shows the position of water connections.

Rated technical data are shown in  p. 51.

INSTALLATION REQUIREMENTS

 

A

ARNING:

 unit installation and start-up must be entrusted to com-

petent personnel and performed in a workmanlike manner, in ac-

cordance with current regulations. 

 

A

WARNING:

 First installation ensure that: 

1.  The place of installation has sufficient space for 

containing the device and for performing in-

stallation and maintenance. See figure   p.  57. 

2.  The air inlet and delivery are not obstructed.

3.  The hydraulic connections are positioned and dimen-

sioned as requested by the device. See figure from   p.  53. 

4.  The electric power supply line has the features requested on the 

fan coil's data plate.

For each unit an (IL) switch should be mounted on the power supply, 

with opening contacts at a distance of at least 3 mm and a suitable 

protection fuse (F) .

 

A

WARNING:

 Install the unit, circuit breaker (IL) and/or any remote 

controls in a place out of reach of persons who may be taking a bath 

or shower.

 

A

WARNING:

 the EMC filters connected to frequency converters 

(inverters) can create leakage currents toward ground (in order to 

make the unit EMC compliant, by reducing conducted emissions on 

power supply line). Depending on installation site, this can force the 

cut out of the differential safety switch. It is recommended to install 

a separate differential safety switch, only for the BLDC unit, with an 

adjustable threshold for the cut out current.

 

B

WARNING:

 base unit must be protect by original packaging to 

avoid demage at the worksite, before cabinet installation. 

 

B

WARNING:

 keep the cabinet inside the original packaging until the 

finally installation

Warning for ducted units:

The unit must be installed on the basis of design and technical con-

siderations, carrying out an aeraulic assessment and considering the 

BACK PRESSURE offered by the PIPING applied to the outlet to avoid the 

problem of failure to change speed: this responsibility cannot fall on the 

product but on the installation;

Install the unit with the appropriate inspection hatches for routine and 

special maintenance of the fan coils: for mechanical, electrical and hy-

draulic replacement;

4.1 INSTALLATION

It is advisable to install any 

accessories

 on the standard unit prior to 

positioning the latter.

Install any remote 

control panel

 in an easily accessible position allowing 

the user to set the functions while ensuring an accurate reading of the 

ambient temperature, if provided.

Avoid therefore:

 

Ū positions directly exposed to sunlight;

 

Ū positions exposed to direct currents of warm or cold air

 

Ū placing obstacles that impede an accurate temperature reading

For installation and use of accessories, please refer to the relative 

technical sheets.

Make the plumbing connections to the heat exchanger and, where the 

cooling function is to be used, to the condensate drainage outlet.

It is recommended to connect the installation intake to the upper part of 

the heat exchanger and the return to the bottom part of it.

Bleed air from the exchanger by means of the air vent valves (hexago-

nal wrench type 10) situated beside the plumbing connections of the 

exchanger.

In case of wall installation, to favour the drainage of condensate, the 

drain hose should be inclined downward, at least 3/5 mm; provide for 

the correct drainage of the condensate drain pipe according to need.

In case of ceiling installation, in particular when the EDPH accessory is 

present, install the unit with a slight slope (10 mm), in order to facilitate 

the condensate drainage. 11.7 p. 57

The condensate discharge could be on left side or right side, at the 

choice of the installer. Slope towards the chosen side, then close the un-

used side with the cap and place the pipette on the side of the chosen 

drain.  

Before switching the unit on, check that it is installed in such a way as 

to guarantee the required inclination for proper condensate drainage.

 

B

WARNING:

 Do not use thick pipes or pipes whose characteristics 

(i.e. corrugated conduits) may impede the condensate flow.

 

B

WARNING:

 tighten the hydraulic connections making sure to block 

the manifold with the appropriate wrench to prevent damage to the 

heat exchanger.

 

B

WARNING:

 The openable side doors must be fixed with screw, due 

to lack of controls onboard the fan coil.

 

B

WARNING:

 For fan coils equipped with auxiliary electric heating el-

ement, ensure that any combustible material is at least 30 cm away 

from the electric heating element.

 

B

WARNING:

In normal operation, particularly with the fan at minimum speed 

and ambient air with high relative humidity, condensation may form 

on the air outlet and on some external parts of the unit.

To avoid such issues while always remaining within the operating 

limits envisaged for the unit, it is necessary to limit the inlet tem-

perature of the water inside the heat exchanger. In particular, the 

difference between the air dew point  (T

A

,D

P

)  and the inlet water 

temperature (T

W

) must NOT exceed 14 °C, according to the follow-

ing relationship:  

T

W

>T

A

,D

P

-14 °C

Example

: in the case of ambient air at 25 ° C with 75% relative hu-

midity, the dew point temperature is about 20 ° C and therefore the 

inlet temperature of the water in the battery must be greater then:

 

Ū 20-14 = 6 °C in order to avoid condensation on a fancoil equipped 

with a valve.

 

Ū 20-12 = 8 °C If the valve kit accessory can not be installed.

Fan coil with valve

Air temperature dry bulb (°C)

Relative Humidity 

%

21

23

25

27

29

31

33

40

5

5

5

5

5

5

5

50

5

5

5

5

5

6

8

60

5

5

5

5

7

9

11

70

5

5

6

8

9

11

13

80

5

6

8

10

12

14

16

90

6

8

10

12

14

16

18

Fan coil without valve

Air temperature dry bulb (°C)

Relative Humidity 

%

21

23

25

27

29

31

33

40

6

6

6

6

6

6

6

50

6

6

6

6

6

8

10

60

6

6

6

7

9

11

13

70

6

6

8

10

11

13

15

80

6

8

10

12

12

16

18

90

8

10

12

14

14

18

20

In the event the indoor unit is stopped for a prolonged period, with 

the fan stopped and circulation of cold water in the heat exchanger, 

Summary of Contents for FWZ

Page 1: ...Motor Manuel d installation utilisation et entretien 1 8 kW Ventilo convecteurs ventilateur centrifuge et moteur EC Installation use and maintenance manual 1 8 kW Fan coil units with centrifugal fan...

Page 2: ......

Page 3: ...UNIT p 4 LUOGO DI INSTALLAZIONE p 4 2 1 AVVERTENZE PER LA QUALIT DELL ACQUA p 4 3 DATI DIMENSIONALI p 7 4 AVVERTENZE PER L INSTALLAZIONE p 7 4 1 INSTALLAZIONE p 7 4 2 MONTAGGIO UNIT BASE E MOBILE DI...

Page 4: ...Ventilconvettore per installazione orizzontale o verticale con mobile di co pertura oppure ad incasso Versioni disponibili FWZ installazione a parete con mobile uscita aria verticale FWR installazio n...

Page 5: ...enum box coibentato con connessioni circolari lato aspirazione FWS CDRP1A Kitpompadiscaricocondensa EDPV Bacinellaausiliariadiraccoltacondensaverticale EDPH Bacinellaausiliariadiraccoltacondensaorizzo...

Page 6: ...regolazione della temperatura dell ambiente interrompendo il flusso dell acqua at traverso lo scambiatore di calore Il kit include valvola attuatore elettrotermico kit idraulico per installazione del...

Page 7: ...l installazione e l uso di eventuali accessori si rimanda alle relative schede tecniche Realizzare i collegamenti idraulici alla batteria di scambio termico e nel caso di funzionamento in fase di raff...

Page 8: ...aston MVI Motore Ventilatore Inverter Integrato EMC FILTER Filtro antidisturbo EMI RFI BN L2 Marrone fase IN filtro BU N4 Blu neutro IN filtro BK U1 Nero fase OUT filtro BU U3 Blu neutro OUT filtro VC...

Page 9: ...apparecchio sia livellato secondo necessit e che lo scari co condensa non sia ostruito depositi di calcinacci ecc Verificare che l apparecchio sia installato in modo da garantire il corret to flusso d...

Page 10: ...le controllare lo stato degli scambiatore prima di ogni periodo di funzionamento verificando che le alette non siano ostruite dall impurit PULIZIA DEL MOBILE DI COPERTURA Utilizzate un panno morbido N...

Page 11: ...p 12 2 DESCRIPTION AND INTENDED USE OF UNIT p 12 INSTALLATION SITE p 12 2 1 WATER QUALITY WARNINGS p 12 3 DIMENSIONS p 15 4 INSTALLATION REQUIREMENTS p 15 4 1 INSTALLATION p 15 4 2 MOUNTING BASE UNIT...

Page 12: ...or with re cessed installation Available versions FWZ Suspended wall installation with cabinet with vertical air flow FWR Floor and ceiling mounted with cabinet FWS vertical and horizon tal recess mo...

Page 13: ...lated with circular connections supply side FWS EICC Plenum box insulated with circular connections intake side FWS CDRP1A Condensate drainage pump kit EDPV Auxiliary water drip tray vertical EDPH Aux...

Page 14: ...panel for fan coils control the room tempera ture by stopping the water flow through the heat exchanger The kit includes valve electrothermal actuator plumbing kits for installing the valve on the hea...

Page 15: ...oling function is to be used to the condensate drainage outlet It is recommended to connect the installation intake to the upper part of the heat exchanger and the return to the bottom part of it Blee...

Page 16: ...ase BU U3 Blue filter OUT neutral VC ON OFF cold hot water valve 2 pipes system accessory ON OFF cold water valve 4 pipes system accessory VH hot water valve 4 pipes system accessory BN Brown valves p...

Page 17: ...nry debris etc Check that the unit is installed in such a way as to guarantee the proper air flow Check the tightness of the plumbing connections to the exchanger and condensate drainage line Make sur...

Page 18: ...dition of the exchangers before the start of every period of use and to make sure that the fins are not obstructed by dirt CLEANING THE CABINET Use a soft cloth Never pour liquids onto the unit as thi...

Page 19: ...ONCTIONNELLE p 25 6 UTILISATION p 25 7 ENTRETIEN p 25 NETTOYAGE DU FILTRE AIR p 26 NETTOAYAGE DE LA BATTERIE D CHANGE THERMIQUE p 26 NETTOYAGE DE L HABILLAGE p 26 8 RECHERCHE DES CAUSES D ANOMALIE p 2...

Page 20: ...stallation horizontale or verticale avec habillage ou encatr e Versions disponibles FWZ installation murale en applique habillage soufflage d air vertical FWR Installation au sol et en plafonnier avec...

Page 21: ...res c t sou age FWS EICC Les pl nums isol avec raccords circulaires c t aspiration FWS CDRP1A Kitpompepurgedescondensats EDPV Bacauxiliairedecollectedescondensats vertical EDPH Bacauxiliairedecollecte...

Page 22: ...biante en interrompant le flux d eau travers l changeur de chaleur Le kit comprend vanne actionneur lectrothermique kit hydraulique pour l installation de la valve sur l echangeur de chaleur Pour plus...

Page 23: ...les raccordements hydrauliques l changeur thermique pour la modalit chauffage et l coulement des condensats pour la modalit rafra chissement Il est recommand de pr voir le refoulement de l installati...

Page 24: ...se DIP1 DIP2 DIP3 DIP4 1 1550rpm OFF OFF OFF 2 1450rpm ON OFF OFF 3 1350rpm OFF ON OFF 4 1250rpm ON ON OFF 5 1150rpm OFF OFF ON 6 1050rpm ON OFF ON 7 950rpm OFF ON ON 8 850rpm ON ON ON Note maximum vi...

Page 25: ...nitial se r f rer aux sch mas lectriques partir de p 60 15 remonter le panneau avant de l unit base 4 vis ou le bac principal de r cup ration des condensats pour les versions avec installation au plaf...

Page 26: ...tte occasion un filtre d origine Le mod le d unit terminale est indiqu sur la plaque d identification pr sente sur la flasque interne NETTOAYAGE DE LA BATTERIE D CHANGE THERMIQUE Contr ler l tat des c...

Page 27: ...REIBUNG UND ERWARTETE VERWENDUNG EINHEIT S 28 INSTALLATIONSORT S 28 2 1 WASSERQUALIT T WARNUNG S 28 3 ABMESSUNGEN S 31 4 HINWEISE F R DIE INSTALLATION S 31 4 1 EINSTELLUNG S 31 4 2 MONTAGE VON EINHEIT...

Page 28: ...NG UND ERWARTETE VERWENDUNG EINHEIT Hhorizontale oder vertikal Ger teinstallation mit Verkleidung oder Unterputzinstallation Verf gbareVersionen FWZ Wandinstallation Verkleidung mit vertikaler Luftaus...

Page 29: ...Anschlusskasten isoliert mit runden Anschl s sen Saugseite FWS CDRP1A Kondenswasserablass Kit EDPV Zus tzlichesKondenswassersammelbeckenVertikale EDPH Zus tzlichesKondenswassersammelbecken horizontal...

Page 30: ...rlaubt die Temperaturregelung durch Unterbrechung desWasserflusses durch denW rmetauscher Il kit include Ventile Elektrothermischer Antrieb Hydrauliksatz f r die Ventilinstallation an der Batterie F r...

Page 31: ...Gebrauch des eventuellen Zubeh rs wird auf die entsprechenden technischen Datenbl tter verwiesen Die Wasseranschl sse zum W rmetauscher und im Falle des K hlbetriebs zum Kondenswasserablass herstellen...

Page 32: ...ter OUT Filter VC Kalt Warmwasser ON OFF Ventil 2 Leiter System Zubeh r Kalt wasser ON OFF Ventil 4 Leiter System Zubeh r VH Warmwasser ON OFF Ventil 4 Leiter System Zubeh r BN Braun Ventil Versorgung...

Page 33: ...Stromversorgung kontrollieren Kontrollieren dass derW rmeaustauscher entl ftet ist DieVerkleidung wieder anbringen und den Filter wieder einbauen DieSpannungzumGebl sekonvektoreinschaltenunddieFunkti...

Page 34: ...igen kann Keine scharfen chemischen L sungsmittel verwenden Die Luftausblasklappe nicht mit sehr hei emWasser reinigen 8 ST RUNGSSUCHE Funktioniert das Ger t nicht richtig f hren Sie die in der nachst...

Page 35: ...p 41 6 USO p 41 7 MANTENIMIENTO p 41 LIMPIEZA DEL FILTRO DE AIRE p 42 LIMPIEZA DE LA BATER A DE INTERCAMBIO T RMICO p 42 LIMPIEZA DEL MUEBLE CARCASA p 42 8 LOCALIZACI N DE AVER AS p 42 9 DATOST CNICOS...

Page 36: ...ector para montaje horizontal u vertical con mueble u de empotrar Versiones disponibles FWZ instalaci n en pared con mueble con salida de aire vertical FWR montaje en el suelo y en el techo con mueble...

Page 37: ...do ccon conexiones redondas lado aspiraci n FWS CDRP1A Kitparalabombadevaciadodell quidode condensaci n EDPV Bandejaauxiliarpararecogerell quidode condensaci nvertical EDPH Bandejaauxiliarpararecogere...

Page 38: ...laci n de la tempera tura ambiente interrumpiendo el flujo de agua mediante el intercambiador de calor El kit est compuesto por v lvula accionador electrot rmic kit hidraulico para instalar la valvula...

Page 39: ...aire caliente o fr o interponer obst culos que impidan medir correctamente la temperatura Para la instalaci n y el uso de cualquier accesorio consulte las fichas t cni cas correspondientes Efect e la...

Page 40: ...6 1050rpm ON OFF ON 7 950rpm OFF ON ON 8 850rpm ON ON ON Nota Normalmente no se utiliza la velocidad m xima 1550 rpm Leyenda general de la conexi n el ctrica IL Interruptor de l nea no suministrado F...

Page 41: ...onsulte los esquemas el ctricos de p 60 15 volver a montar el panel delantero de la unidad base 4 tornillos o la cu beta principal colectora de condensaci n para las versiones con instalaci n en techo...

Page 42: ...uesto origina les el modelo del terminal se identifica f cilmente en la placa de identificaci n ubicada en el costado interno LIMPIEZA DE LA BATER A DE INTERCAMBIO T RMICO Se recomienda controlar el e...

Page 43: ...VONATKOZ FIGYELMEZTET SEK o 47 4 1 BE P T S o 47 4 2 ALAPEGYS G S FED SZEKR NY FELSZEREL SE o 48 5 VERIFICA FUNZIONALE o 49 6 HASZN LAT o 49 7 KARBANTART S o 49 LEVEG SZ R TISZT T SA o 50 A H CSER L S...

Page 44: ...be p t sre fed szek r nnyel vagy be p tve Rendelkez sre ll v ltozatok FWZ falra szerelhet burkolatos f gg leges leveg kimenet FWR Parapet mennyezet alatti burkolatos FWS r gz t s f gg leges v zszintes...

Page 45: ...at lakoz sokkal kis l si oldal FWS EICC Csatlakoz doboz szigetelt k r alak csat lakoz sokkal sz v oldal FWS CDRP1A Kondenzelvezet szivatty k szlet EDPV Kieg sz t f gg legeskondenzv zgy jt t lca EDPH K...

Page 46: ...t szab lyoz s t az ltal hogy megszak tja a v z raml s t a h cser l n kereszt l A k szlet az al bbi r szekb l ll szelep elektrotermikus aktu tor hidraulikus k szlet a szelep tekercsre val felszerel s h...

Page 47: ...A h cser l leveg kivezet s t mag nak a telepnek a v zbek t si oldalain l elhe lyezett kif v szelep 10 es kulcs m k dtet s vel lehet elv gezni Falra szerel s eset n a kondenzv z jobb elvezet s rt hajl...

Page 48: ...Melegv z BE KI szelep 4 cs ves rendszerhez tartoz k BN Barna szelep t pell t s f zisa BU K k a szelep t pell t sa nulla SAI El re telep tett bels leveg h m rs klet szonda SAE T voli leveg h m rs klet...

Page 49: ...em haszn lt ny l sokat v z ll anyaggal 5 VERIFICA FUNZIONALE Ellen rizze hogy a k sz l k szintben legyen sz ks g szerint s a kondenz v z levezet ne legyen eldugulva meszes lerak d sok stb Ellen rizze...

Page 50: ...asoljuk hogy minden vben a haszn lat el tt ellen rizze a h cser l k lla pot t s n zze meg hogy a lamell k nincsenek e elt m dve szennyez d ssel BURKOLATOS K SZ L K TISZT T SA Haszn ljon puha ruh t Soh...

Page 51: ...1 50 V ph Hz 4 pipes FWZ FWS FWR 02 03 06 08 Speed min med max min med max min med max min med max Control voltage DF 1R E V 5 10 6 60 8 10 3 70 5 50 7 20 5 00 6 70 8 90 3 60 6 20 8 60 Total cooling...

Page 52: ...et air grill Grille sortie d air Luftauslass Gitter Rejilla salida aire Leveg kivezet r cs 8 Motore elettrico Electric motor Moteur lectrique Elektromotor Motor el ctrico Villanymotor 9 Filtro aria Ai...

Page 53: ...oz sai 4DF DF Attacchi idraulici batteria addizionale ad 1 rango DF DF 1 row additional heat exchanger water connections Raccords hydrauliques batterie additionnelle 1 rang DF Wasseranschl sse zus tzl...

Page 54: ...standard Water connections standard heat exchanger Raccords hydrauliques changeur standard Wasseranschl sse Standardbatterie Conexiones hidr ulicas bater a STD Alap h cser l v zoldali csatlakoz sai 4D...

Page 55: ...t r 4 Attacchi idraulici batteria standard Water connections standard heat exchanger Raccords hydrauliques changeur standard Wasseranschl sse Standardbatterie Conexiones hidr ulicas bater a STD Alap h...

Page 56: ...opertura Cabinet Habillage Verkleidung Mueble carcasa Burkolatos k sz l k 11 5 Rotazione batteria Heat exchanger rotation Rotation du changeur Umdrehung des w rmetauschers Rotaci n del cambiador A h c...

Page 57: ...installation Espaces n cessaires l installation FWS FWR installation plafonnier Installationsbereich FWS FWR Deckeninstallation Espacios de instalaci n FWS FWR en el techo Telep t shez sz ks ges hely...

Page 58: ...s Positionen zum Einh ngen der Gitter mit aufgesetzten Filtern Posiciones para enganchar las rejillas con filtros adjuntos R csok r gz t s re szolg l poz ci k r gz tett sz r kkel 2 Pieghe previste pe...

Page 59: ...FWS 02 03 06 E2MV2B07A6 E2MV2B07A6 E2M2V207A6 E2M2V207A6 E2MPV207A6 E2MPV207A6 213112 213112 22CX230NC2 22CX24NC2 2 EMUJC 010 08 E2MV2B10A6 E2MV2B07A6 E2M2V210A6 E2M2V207A6 E2MPV210A6 E2MPV207A6 21313...

Page 60: ...FWZ FWR FWS 60 12 FWZ FWR FWS ELECTRICAL WIRINGS 12 1 FWR S Z 02 08 base wiring diagram 12 2 FWEC10 2 pipes systems...

Page 61: ...FC66006893 61 12 3 FWEC10 3 pipes systems...

Page 62: ...FWZ FWR FWS 62 12 4 FWEC3 FWZ R S 02 08...

Page 63: ...FC66006893 63 12 5 FWEC3 FWZ R S 02 08 heating element...

Page 64: ...FWZ FWR FWS 64 12 6 FWECSAPA FWZ R S 02 08 ON OFF valve...

Page 65: ...FC66006893 65 12 7 FWECSAPA FWZ R S 02 08 ON OFF valve heating element...

Page 66: ...FWZ FWR FWS 66 12 8 FWECSAPA FWZ R S 02 08 modulating valve...

Page 67: ...FC66006893 67 12 9 FWECSAPA FWZ R S 02 08 modulating valve heating element...

Page 68: ...Zandvoordestraat 300 B 8400 Oostende Belgium...