background image

10

English

CAUTION

If drain stagnates in the drain piping, the piping may be 
clogged.

• Make sure to use the attached drain hose (1) and metal 

clamp (2). Also, insert the drain hose (1) into the root of 
the drain socket, and tighten the metal clamp (2) at the 
root of the drain socket tightly. 
(Refer to Fig. 25 and Fig. 26)
(Install the metal clamp (2) so that the tightening part is in 
the range of about 45°as shown in the Fig. 26.)
(Do not bond the drain socket and drain hose. If so, main-
tenance and inspection for the heat exchanger and oth-
ers cannot be conducted.)

CAUTION

If an old drain hose or an elbow or a clamp is used, it may 
cause water leakage.

• Bend the tip of the metal clamp (2) so that the sealing 

material does not bulge. (Refer to Fig. 26)

• When performing insulation, wind the large sealing mate-

rial (Large) (8) attached starting from the base of the 
metal clamp (2) and drain hose (1) in the direction of the 
arrow. (Refer to Fig. 25 and Fig. 26)

• Be sure to insulate all drain piping running indoors.

• Do not deflect the drain hose (1) inside of the indoor unit. 

(Refer to Fig. 27)
(It may cause abnormal noise such as bubbling noise.)
(If the drain hose (1) is deflected, it may damage the suc-
tion grille.)

• Install supports at a distance of 1 to 1.5m so that the pip-

ing may not deflect. (Refer to Fig. 23)

CAUTION

To prevent dust from entering the indoor unit, cover the gap 
with the drain piping by putty or insulation (field supply) so 
that no clearance is made.
However, when putting piping and remote controller wiring 
through the same hole, cover the gap between the through 
cover and the piping after ‘‘8. ELECTRIC WIRING WORK’’ 
is completed.

CAUTION

To avoid the attached drain hose (1) getting excessive 
force, do not bend nor twist it. (It may cause water leakage.)
When conducting the centralized drain piping, follow the 
instructions in Fig. 28. For the diameter of the centralized 
drain piping, select the diameter matching the capacity of 
the indoor unit to be connected. (Refer to technical guide-
book.).

• Connecting drain piping.

Do not connect the drain piping directly to the sewage 
that gives off ammonia odor. The ammonia in the sewage 
may go through the drain piping and corrode the heat 
exchanger of the indoor unit.

• When installing the drain pump kit (optional accessory), 

also refer to the installation manual included to the drain 
pump kit.

(2) After piping is finished, check if the drain flows smoothly.

• Gradually put about 0.6 liter of water for drain confirma-

tion into the drain pan from the air outlet. 
(Refer to Fig. 29)

Sealing material (Large) (8)
(accessory)

Metal clamp (2)
 (accessory)

Drain hose (1)
 (accessory)

Fig. 25

Do not make a gap to avoid 
dew condensation.

Sealing 
material 
(Large) (8)
(accessory)

Sealing material 
(Large) (8)
(accessory)

Metal clamp (2)

(accessory)

Metal clamp (2)
(accessory)

Drain hose (1)

(accessory)

Drain hose (1)
(accessory)

(For left rear/
left side)

(For right 
back / right side)

Inserting direction 
for the screw driver

approx. 45°

approx. 45°

Sealing material 
(Large) (8)
Applying direction

Fig. 26

Tightening part

Metal clamp (2) (accessory)

Drain hose (1) (accessory)

approx. 45°

Bend the tip without 
tearing the sealing 
material (Large) (8)

Do not deflect

Fig. 27

Centralized drain piping
If water stagnates in the 
drain piping, the piping 
may be clogged.

100mm  or more

Install with downward inclination 
of 1/100 or more so that no air 
will be stagnated. 

Fig. 28

Plastic container for pouring water
(Tube length of 100mm is necessary)

100mm 
or more

Air outlet

Fig. 29

4PEN469440-1D.book  Page 10  Tuesday, June 27, 2017  10:55 AM

Summary of Contents for FHA70AVEB

Page 1: ...INSTALLATION MANUAL FHA35AVEB FHA50AVEB FHA60AVEB FHA70AVEB FHA100AVEB FHA125AVEB FHA140AVEB Split System air conditioners 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 2: ...A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Ce...

Page 3: ...n the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installation work Failure to use the specified par...

Page 4: ...to the piping refrigerant and drain and resin parts Make sure to check in advance that the refrigerant to be used for installation work is according to the Outdoor Unit specifi cation The air conditi...

Page 5: ...drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner...

Page 6: ...70 dBA 2 Use hanging bolts for installation Investigate if the installation place can withstand the mass of the indoor unit and if necessary hang the indoor unit with bolts after it is reinforced by...

Page 7: ...ion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FH...

Page 8: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 9: ...substance other than the specified refrigerant such as air into the refrigeration circuit If the refrigerant leaks during the work ventilate the room Remove the stay for packing and delivering reinfo...

Page 10: ...connection Piping insulating material field supply For prevention of sweating do not expose the piping Clamp 4 accessory Tighten the piping insulating material Liquid side piping insulating method Jo...

Page 11: ...does not heat Refer to the outdoor unit installation manual or technical document for refrigerant piping CAUTION Do not use antioxidant when brazing piping It may result in malfunction of components...

Page 12: ...tached drain hose 1 getting excessive force do not bend nor twist it It may cause water leakage When conducting the centralized drain piping follow the instructions in Fig 28 For the diameter of the c...

Page 13: ...during the wiring work Otherwise it may cause damage If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 8...

Page 14: ...tension to the connecting section of the wirings 4 Connect the remote controller wiring led from the routing hole to the terminals P1 and P2 of the terminal block X1M 6P There is no polarity After th...

Page 15: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 16: ...using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wi...

Page 17: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WH...

Page 18: ...te controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate p...

Page 19: ...The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Te...

Page 20: ...THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L...

Page 21: ...4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 22: ...4P469440 1D 2017 06 Copyright 2017 Daikin 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Reviews: