background image

English

3

(Refer to the installation manual attached to the remote con-
troller for how to install.)

CARRY OUT THE WORK GIVING CAUTION TO THE FOL-
LOWING ITEMS AND AFTER THE WORK IS COMPLETED 
CHECK THESE AGAIN.

1. Items to be checked after the installation work is completed

*Make sure to recheck the items of “SAFETY PRECAUTIONS” 

2. Items to be checked at delivery 

3. Points of the operation explanation

3.

SELECTION OF INSTALLATION LOCATION

When unpacking and moving the indoor unit after 
unpacked, do not apply force to the piping (refrigerant and 
drain) and resin parts.

(1) Select the installation location that meets the following con-

ditions and get approval of the customer.
• Where the cool and warm air spreads evenly in the room.
• Where there is no obstacles in the air passage.
• Where drainage can be ensured.
• Where the ceiling lower surface is not inclined.
• Where there is sufficient strength to withstand the mass 

of the indoor unit (if the strength is insufficient, the indoor 
unit may vibrate and get in contact with the ceiling and 
generate unpleasant chattering noise).

• Where a space sufficient for installation and service can 

be ensured. (Refer to Fig. 1 and Fig. 2)

• Where the piping length between the indoor and the out-

door units is ensured within the allowable length. (Refer 
to the installation manual attached to the outdoor unit.)

• Where there is no risk of flammable gas leak.

Items to be checked

In case of defec-
tive

Check 

column

Are the indoor and outdoor 
units rigidly fixed?

Drop · vibration · 
noise

Are the installation work of the 
outdoor and indoor units com-
plete?

Does not operate 
· burnout

Have you carried out a 
leakage test with the test 
pressure specified in the 
outdoor unit installation 
manual?

Does not cool / 
Does not heat

Is the insulation of refriger-
ant piping and drain piping 
completely carried out? 

Water leakage

Does the drain flow out 
smoothly?

Water leakage

Is the power supply voltage 
identical to that stated in 
the manufacturer’s label on 
the air conditioner?

Does not operate 
· burnout

Are you sure that there is 
no wrong wiring or piping or 
no loose wiring? 

Does not operate 
· burnout

Is earthing completed?

Danger in case of 
leakage

Are the sizes of electric wir-
ing according to the specifi-
cation?

Does not operate 
· burnout

Is any of air outlets or inlets 
of the indoor and outdoor 
units blocked with obsta-
cles?

Does not cool / 
Does not heat
(It may lead to 
capacity drop due 
to fan speed drop 
or malfunction of 
equipment.)

Have you recorded the 
refrigerant piping length 
and the refrigerant charge 
added?

Refrigerant 
charge amount is 
not clear

Items to be checked

Check 

column

Have you carried out field setting? (if necessary)
Are the control box cover, the air filter and the suction 
grille attached?
Does the cool air discharge during the cooling opera-
tion and the warm air discharge during heating opera-
tion comes out of the unit?

Have you explained how to operate the air condi-
tioner showing the operation manual to the cus-
tomer? 
Have you explained the description of cooling, 
heating, program dry and automatic (cooling/
heating) given in the operation manual to the 
customer?
If you set the fan speed at thermostat OFF, did 
you explain the set fan speed to the customer?
Have you handed the operation manual and the 
installation manual to the customer?

In addition to the general usage, since the items in the 
operation manual with the 

WARNING and 

CAU-

TION marks are likely to result in human bodily injuries 
and property damages, it is necessary not only to 
explain these items to the customer but also to have the 
customer read them.
It is also necessary to explain the items of “NOT MAL-
FUNCTION OF THE AIR CONDITIONER” to the customer 
and have the customer read them carefully.

4PEN469440-1D.book  Page 3  Tuesday, June 27, 2017  10:55 AM

Summary of Contents for FHA70AVEB

Page 1: ...INSTALLATION MANUAL FHA35AVEB FHA50AVEB FHA60AVEB FHA70AVEB FHA100AVEB FHA125AVEB FHA140AVEB Split System air conditioners 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 2: ...A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Ce...

Page 3: ...n the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installation work Failure to use the specified par...

Page 4: ...to the piping refrigerant and drain and resin parts Make sure to check in advance that the refrigerant to be used for installation work is according to the Outdoor Unit specifi cation The air conditi...

Page 5: ...drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner...

Page 6: ...70 dBA 2 Use hanging bolts for installation Investigate if the installation place can withstand the mass of the indoor unit and if necessary hang the indoor unit with bolts after it is reinforced by...

Page 7: ...ion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FH...

Page 8: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 9: ...substance other than the specified refrigerant such as air into the refrigeration circuit If the refrigerant leaks during the work ventilate the room Remove the stay for packing and delivering reinfo...

Page 10: ...connection Piping insulating material field supply For prevention of sweating do not expose the piping Clamp 4 accessory Tighten the piping insulating material Liquid side piping insulating method Jo...

Page 11: ...does not heat Refer to the outdoor unit installation manual or technical document for refrigerant piping CAUTION Do not use antioxidant when brazing piping It may result in malfunction of components...

Page 12: ...tached drain hose 1 getting excessive force do not bend nor twist it It may cause water leakage When conducting the centralized drain piping follow the instructions in Fig 28 For the diameter of the c...

Page 13: ...during the wiring work Otherwise it may cause damage If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 8...

Page 14: ...tension to the connecting section of the wirings 4 Connect the remote controller wiring led from the routing hole to the terminals P1 and P2 of the terminal block X1M 6P There is no polarity After th...

Page 15: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 16: ...using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wi...

Page 17: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WH...

Page 18: ...te controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate p...

Page 19: ...The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Te...

Page 20: ...THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L...

Page 21: ...4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 22: ...4P469440 1D 2017 06 Copyright 2017 Daikin 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Reviews: