background image

2

English

• If refrigerant gas leaks during installation work, ventilate the 

area immediately.
Toxic gas may be produced if refrigerant gas comes into con-
tact with a fire.

• After completing the installation work, check to make sure 

that there is no leakage of refrigerant gas.
Toxic gas may be produced if refrigerant gas leaks into the 
room and comes into contact with a source of a fire, such as 
a fan heater, stove or cooker.

• Never directly touch any accidental leaking refrigerant. This 

could result in severe wounds caused by frostbite.

CAUTION

• Install drain piping according to this installation manual to 

ensure good drainage, and insulate the piping to prevent 
condensation. 
Improper drain piping may cause water leakage, make the 
furniture get wet.

• Install the air conditioner, power supply wiring, remote con-

troller wiring and transmission wiring at least 1 meter away 
from televisions or radios to prevent image interference or 
noise.
(Depending on the radio waves, a distance of 1 meter may 
not be sufficient to eliminate the noise.)

• Install the indoor unit as far as possible from fluorescent 

lamps.
If a wireless remote controller kit is installed, the transmission 
distance may be shorter in a room where an electronic light-
ing type (inverter or rapid start type) fluorescent lamp is 
installed.

• Do not install the air conditioner in places such as the following:

1. Where there is mist of oil, oil spray or vapour for example 

a kitchen.
Resin parts may deteriorate, and cause them to fall out or 
water to leak. 

2. Where corrosive gas, such as sulfurous acid gas, is pro-

duced.
Corrosion of copper pipings or brazed parts may cause 
the refrigerant to leak.

3. Where there is machinery which emits electromagnetic 

waves.
Electromagnetic waves may disturb the control system, 
and cause malfunction of the equipment.

4. Where flammable gases may leak, where carbon fibre or 

ignitable dust is suspended in the air or where volatile 
flammables, such as thinner or gasoline, are handled.
If the gas should leak and remained around the air condi-
tioner, it may cause ignition.

• The air conditioner is not intended for use in a potentially 

explosive atmosphere.

2.

BEFORE INSTALLATION

When unpacking and moving the indoor unit after 
unpacked, do not apply force to the piping (refrigerant and 
drain) and resin parts.

• Make sure to check in advance that the refrigerant to be used 

for installation work is according to the Outdoor Unit specifi-
cation.
(The air conditioner will not properly operate if a wrong refrig-
erant is used.)

• For installation of the outdoor unit, refer to the installation 

manual attached to the outdoor unit.

• Do not throw away the accessories until the installation work 

is completed.

• After the indoor unit is carried into the room, to avoid the 

indoor unit from getting damaged, take measures to protect 
the indoor unit with packing materials.
(1) Determine the route to carry the unit into the room.
(2) Do not unpack the unit until it is carried to the installation 

location.
Where unpacking is unavoidable, use a sling of soft 
material or protective plates together with a rope when 
lifting, to avoid damage or scratches to the indoor units.

• Have the customer actually operate the air conditioner while 

looking at the manual.
Instruct the customer how to operate the air conditioner (par-
ticularly cleaning of the air filters, operation procedures, and 
temperature adjustment).

• For selection of installation location, use the installation pat-

tern paper (used in common with the packing case.) as refer-
ence.

• Do not use the air conditioner where in the salty atmosphere 

such as coastal areas, vehicles, vessels or the voltage fluc-
tuation is frequent such as factories.

• Take off static electricity from the body when carrying out wir-

ing and the control box cover is removed. 
The electric parts may be damaged.

2-1

ACCESSORIES

Check if the following accessories are attached to the 
indoor unit.

2-2

OPTIONAL ACCESSORIES

• For this indoor unit, the remote controller is separately 

required.

• There are 2 kinds of remote controller; wired type and wire-

less type.
Install the remote controller to the place where the customer 
has given consent.
Refer to the catalog for the applicable model.

Name

(1) Drain 

hose

(2) Metal 

clamp 

(3) Washer 

for hanger

(4) Clamp

Quantity

1 pc.

1 pc.

8 pcs.

7 pcs.

Shape

Name

(5) Installa-
tion pattern 

paper

Joint insulat-

ing material

Sealing mate-

rial

(10) Resin 

bushing

Quantity

1 sheet

1 each

1 each

1 pc.

Shape

(6) For gas 

piping

(7) For liq-

uid piping

(8) Large

(9) Small

Name

(11) Wiring 

fixture

(12) Screw 

for wiring 

fixture

(Miscellaneous)

• Operation manual
• Installation manual
• Declaration of confor-

mity

Quantity

2 pcs.

2 pcs.

Shape

M4 × 12

4PEN469440-1D.book  Page 2  Tuesday, June 27, 2017  10:55 AM

Summary of Contents for FHA70AVEB

Page 1: ...INSTALLATION MANUAL FHA35AVEB FHA50AVEB FHA60AVEB FHA70AVEB FHA100AVEB FHA125AVEB FHA140AVEB Split System air conditioners 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 2: ...A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Ce...

Page 3: ...n the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installation work Failure to use the specified par...

Page 4: ...to the piping refrigerant and drain and resin parts Make sure to check in advance that the refrigerant to be used for installation work is according to the Outdoor Unit specifi cation The air conditi...

Page 5: ...drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner...

Page 6: ...70 dBA 2 Use hanging bolts for installation Investigate if the installation place can withstand the mass of the indoor unit and if necessary hang the indoor unit with bolts after it is reinforced by...

Page 7: ...ion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FH...

Page 8: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 9: ...substance other than the specified refrigerant such as air into the refrigeration circuit If the refrigerant leaks during the work ventilate the room Remove the stay for packing and delivering reinfo...

Page 10: ...connection Piping insulating material field supply For prevention of sweating do not expose the piping Clamp 4 accessory Tighten the piping insulating material Liquid side piping insulating method Jo...

Page 11: ...does not heat Refer to the outdoor unit installation manual or technical document for refrigerant piping CAUTION Do not use antioxidant when brazing piping It may result in malfunction of components...

Page 12: ...tached drain hose 1 getting excessive force do not bend nor twist it It may cause water leakage When conducting the centralized drain piping follow the instructions in Fig 28 For the diameter of the c...

Page 13: ...during the wiring work Otherwise it may cause damage If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 8...

Page 14: ...tension to the connecting section of the wirings 4 Connect the remote controller wiring led from the routing hole to the terminals P1 and P2 of the terminal block X1M 6P There is no polarity After th...

Page 15: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 16: ...using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wi...

Page 17: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WH...

Page 18: ...te controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate p...

Page 19: ...The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Te...

Page 20: ...THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L...

Page 21: ...4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 22: ...4P469440 1D 2017 06 Copyright 2017 Daikin 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Reviews: