background image

English

9

• After piping is finished, cut the removed penetration 

cover along the shape of piping, and install it.
Also, for top panel penetration cover, as it was before 
removed, put the horizontal blade motor and thermistor 
lead through the clamp of the top panel penetration cover 
and fix. (Refer to Fig. 16 and Fig. 19)
When doing this, block any gaps between the piping pen-
etration cover and the piping using putty field supply to 
prevent dust from entering the indoor unit.

* Before brazing refrigerant piping, have nitrogen flow through 

the refrigerant piping and substitute air with nitrogen. Then, 
carry out brazing (NOTE 2). (Refer to Fig. 20) After all the 
brazing works are finished, carry out flare connection with the 
indoor unit.

NOTE

NOTE

NOTE

NOTE

1. The proper pressure for having nitrogen flow through the 

piping is approximately 0.02MPa, a pressure that makes 
one feel like breeze and can be obtained through a pres-
sure reducing valve.

2. Do not use flux when brazing refrigerant piping. Use phos-

phor copper brazing filler metal (BCuP-2: JIS Z 3264/B-
Cu93P-710/795: ISO 3677) that does not require flux. (If 
chlorinated flux is used, the piping will be corroded and, in 
addition if fluorine is contained, the refrigerant oil will be 
deteriorated and the refrigerant circuit will be affected 
badly.)

3. When carrying out leakage test of refrigerant piping and the 

indoor unit after the installation of indoor unit is finished, 
confirm the connecting outdoor unit installation manual for 
test pressure. Refer to also the outdoor unit installation 
manual or technical document for refrigerant piping.

4. In case of refrigerant shortage due to forgetting additional 

refrigerant charge etc., it will result in malfunction such as 
does not cool or does not heat. Refer to the outdoor unit 
installation manual or technical document for refrigerant 
piping.

CAUTION

Do not use antioxidant when brazing piping.
It may result in malfunction of components and clogging of 
piping due to residue.

7.

DRAIN PIPING WORK

(1) Carry out drain piping.

• Carry out drain piping so that drainage is ensured.
• Drain piping can be connected from the following direc-

tions: For right rear/right side, refer to Fig. 18 of ‘‘6. 
REFRIGERANT PIPING WORK’’, and for left rear/left 
side, refer to Fig. 21.

• When conducting left rear/left side drain piping, remove 

the protection net. Then, remove the drain socket cap 
and insulation material applied to left side drain socket 
and apply them to the right side drain socket. When doing 
this, insert the drain socket cap all the way in to prevent a 
water leakage.
After the drain hose (1) (accessory) installing, attach the 
protection net by reversing the steps taken to remove it. 
(Refer to Fig. 22)

• Select the piping diameter equal to or larger than that of 

the drain hose (1) (accessory) (polyvinyl chloride piping, 
nominal diameter 20mm, outside diameter 26mm).

• Install the drain piping as short as possible with down-

ward inclination of 1/100 or more by avoiding air stagna-
tion. (Refer to Fig. 23 and Fig. 24)
(It may cause abnormal sound such as bubbling noise.)

Thermistor lead

Horizontal blade motor lead

Top panel penetration 
cover clamp part

Fig. 19

View from air inlet side

Pressure reducing valve

Brazing place

Taping

Stop valve

Nitrogen

Nitrogen

Refrigerant piping

Fig. 20

Back side (sheet metal)
Detach parts

Putty or insulation

(field supply)

Left side
Drain piping

Left side
Detach parts

Left rear side
Drain piping

Fig. 21

Protection net

Fixing 
screw for
protection net

Fig. 22

Good

Wrong

Supports

1-1.5m

Downward inclination of 1/100 or more

Do not lift

Make sure there is no slack

Make sure it is not in the water

Fig. 23

Fig. 24

4PEN469440-1D.book  Page 9  Tuesday, June 27, 2017  10:55 AM

Summary of Contents for FHA70AVEB

Page 1: ...INSTALLATION MANUAL FHA35AVEB FHA50AVEB FHA60AVEB FHA70AVEB FHA100AVEB FHA125AVEB FHA140AVEB Split System air conditioners 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 2: ...A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Ce...

Page 3: ...n the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installation work Failure to use the specified par...

Page 4: ...to the piping refrigerant and drain and resin parts Make sure to check in advance that the refrigerant to be used for installation work is according to the Outdoor Unit specifi cation The air conditi...

Page 5: ...drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner...

Page 6: ...70 dBA 2 Use hanging bolts for installation Investigate if the installation place can withstand the mass of the indoor unit and if necessary hang the indoor unit with bolts after it is reinforced by...

Page 7: ...ion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FH...

Page 8: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 9: ...substance other than the specified refrigerant such as air into the refrigeration circuit If the refrigerant leaks during the work ventilate the room Remove the stay for packing and delivering reinfo...

Page 10: ...connection Piping insulating material field supply For prevention of sweating do not expose the piping Clamp 4 accessory Tighten the piping insulating material Liquid side piping insulating method Jo...

Page 11: ...does not heat Refer to the outdoor unit installation manual or technical document for refrigerant piping CAUTION Do not use antioxidant when brazing piping It may result in malfunction of components...

Page 12: ...tached drain hose 1 getting excessive force do not bend nor twist it It may cause water leakage When conducting the centralized drain piping follow the instructions in Fig 28 For the diameter of the c...

Page 13: ...during the wiring work Otherwise it may cause damage If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 8...

Page 14: ...tension to the connecting section of the wirings 4 Connect the remote controller wiring led from the routing hole to the terminals P1 and P2 of the terminal block X1M 6P There is no polarity After th...

Page 15: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 16: ...using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wi...

Page 17: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WH...

Page 18: ...te controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate p...

Page 19: ...The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Te...

Page 20: ...THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L...

Page 21: ...4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 22: ...4P469440 1D 2017 06 Copyright 2017 Daikin 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Reviews: