background image

English

7

A. When the drain piping is tilted to the right, or to the right 

and back.
Place it level, or tilt it slightly to the right or the back. 
(Within 1°)

B. When the drain piping is tilted to the left, or to the left 

and back.
Place it level, or tilt it slightly to the left or the back. 
(Within 1°)

WARNING

The indoor unit must be securely installed on a place that 
can withstand the mass.
If the strength is insufficient, the indoor unit may fall down 
and cause injuries.

6.

REFRIGERANT PIPING WORK

• For the outdoor unit refrigerant piping, refer to the installation 

manual attached to the outdoor unit.

• Carry out insulation of both gas and liquid refrigerant piping 

securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 120°C. For use under high 
humidity, strengthen the insulation material for refrigerant 
piping. If not strengthened, the surface of insulation material 
may sweat.

• Make sure to check in advance that the refrigerant to be used 

for installation work is according to the Outdoor Unit specifi-
cation. (Unless the refrigerant is correct type, the normal 
operation cannot be expected.)

CAUTION

This air conditioner is a dedicated model for refrigerant 
R410A or R32. Make sure to meet the requirements shown 
right and carry out installation work.

• Use dedicated piping cutters and flaring tools according to 

the used refrigerant type.

• When making a flare connection, coat the flared inner sur-

face only with ether oil or ester oil.

• Use only the flare nuts attached to the air conditioner. If 

other flare nuts are used, it may cause refrigerant leak-
age.

• To prevent contamination or moisture from getting into the 

piping, take measures such as pinching or taping the pip-
ings.

Do not mix substance other than the specified refrigerant 
such as air into the refrigeration circuit.
If the refrigerant leaks during the work, ventilate the room.

• Remove the stay for packing and delivering (reinforcing 

plate) before refrigerant piping work. 
(Refer to Fig. 18)

• The refrigerant is pre-charged in the outdoor unit.
• When connecting the pipings to the air conditioner, make 

sure to use a spanner and a torque wrench as shown in 
Fig.13.
For the dimension of flared part, refer to the Table 1.

• When making a flare connection, coat the flared inner sur-

face only with ether oil or ester oil. (Refer to Fig. 14) Then, 
turn the flare nut 3 to 4 times with your hand and screw in the 
nut.

• For the tightening torque, refer to the Table 1.

Table 1 

CAUTION

• Do not have oil adhere to the screw fixing part of resin parts.

If oil adheres, it may weaken the strength of screwed part.

• Do not tighten flare nuts too tight.

If a flare nut cracks, the refrigerant may leak.

CAUTION

Insulation of field piping must be carried out up to the con-
nection inside the casing. If the piping is exposed to the 
atmosphere, it may cause sweating or burn due to touching 
the piping, electric shocks or a fire due to the wiring touch-
ing the piping. 

• After leak test, referring to Fig. 15, insulate both the gas and 

liquid piping connection with the attached joint insulating 
material (6) and (7) to prevent the piping from getting 
exposed. Then, tighten the both ends of insulating material 
with the clamp (4).

• Wrap the sealing material (Small) (9) around the joint insulat-

ing material (6) (flare nut section), only the gas piping side.

A

A.B

B

≤ 1°

≤ 1°

≤ 1°

Fig. 12

Piping size 

(mm)

Tightening 

torque (N·m)

Dimension 

for processing 

flare A (mm)

Flare shape

ø 6.4

15.7 ± 1.5

8.9 ± 0.2

ø 9.5

36.3 ± 3.6

13.0 ± 0.2

ø 12.7

54.9 ± 5.4

16.4 ± 0.2

ø15.9

68.6 ± 6.8

19.5 ± 0.2

Torque wrench

Spanner

Flare nut

Union joint

Fig. 13

Coat the flared inner surface 
only with ether oil or ester oil.

Fig. 14

R0.4-0.8

90°±2°

A

45°±2°

4PEN469440-1D.book  Page 7  Tuesday, June 27, 2017  10:55 AM

Summary of Contents for FHA70AVEB

Page 1: ...INSTALLATION MANUAL FHA35AVEB FHA50AVEB FHA60AVEB FHA70AVEB FHA100AVEB FHA125AVEB FHA140AVEB Split System air conditioners 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 2: ...A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Ce...

Page 3: ...n the event of a leakage Otherwise this may lead to an accident due to oxygen defi ciency Be sure to use only the specified parts and accessories for installation work Failure to use the specified par...

Page 4: ...to the piping refrigerant and drain and resin parts Make sure to check in advance that the refrigerant to be used for installation work is according to the Outdoor Unit specifi cation The air conditi...

Page 5: ...drain piping completely carried out Water leakage Does the drain flow out smoothly Water leakage Is the power supply voltage identical to that stated in the manufacturer s label on the air conditioner...

Page 6: ...70 dBA 2 Use hanging bolts for installation Investigate if the installation place can withstand the mass of the indoor unit and if necessary hang the indoor unit with bolts after it is reinforced by...

Page 7: ...ion to remove Refer to Fig 6 Take out accessories Refer to Fig 6 Open the knock hole at the wiring inlet side at the rear surface or top surface and install the attached resin bushing 10 Model name FH...

Page 8: ...for hanger 3 accessory and fix by double nuts firmly 2 Lift up the indoor unit slide from the front and put the hanger installing bolt M8 into the securely for temporary hanging Refer to Fig 11 3 Tigh...

Page 9: ...substance other than the specified refrigerant such as air into the refrigeration circuit If the refrigerant leaks during the work ventilate the room Remove the stay for packing and delivering reinfo...

Page 10: ...connection Piping insulating material field supply For prevention of sweating do not expose the piping Clamp 4 accessory Tighten the piping insulating material Liquid side piping insulating method Jo...

Page 11: ...does not heat Refer to the outdoor unit installation manual or technical document for refrigerant piping CAUTION Do not use antioxidant when brazing piping It may result in malfunction of components...

Page 12: ...tached drain hose 1 getting excessive force do not bend nor twist it It may cause water leakage When conducting the centralized drain piping follow the instructions in Fig 28 For the diameter of the c...

Page 13: ...during the wiring work Otherwise it may cause damage If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 8...

Page 14: ...tension to the connecting section of the wirings 4 Connect the remote controller wiring led from the routing hole to the terminals P1 and P2 of the terminal block X1M 6P There is no polarity After th...

Page 15: ...attached to the outdoor units Confirm the system type Pair type 1 remote controller controls 1 indoor unit standard system Refer to Fig 31 Simultaneous operation system 1 remote controller controls 2...

Page 16: ...using 2 remote controllers one must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover 2 Add wi...

Page 17: ...hose shown in the table 11 1 SETTING WHEN AN OPTIONAL ACCESSORY IS ATTACHED For setting when attaching an optional accessory refer to the installation manual attached to the optional accessory 11 2 WH...

Page 18: ...te controller terminal block of the master unit After the slave unit setting remove the remote controller wir ing and rewire the remote controller to the master unit The indoor unit does not operate p...

Page 19: ...The home menu is displayed Cool Set to 28 C Return Setting Service Settings 1 3 Test Operation Maintenance Contact Field Settings Demand Min Setpoints Differential Group Address Cool Return Setting Te...

Page 20: ...THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L...

Page 21: ...4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Page 22: ...4P469440 1D 2017 06 Copyright 2017 Daikin 4PEN469440 1D book Page 1 Tuesday June 27 2017 10 55 AM...

Reviews: