![Daikin FHA70AVEB Installation Manual Download Page 16](http://html1.mh-extra.com/html/daikin/fha70aveb/fha70aveb_installation-manual_4700400016.webp)
14
English
NOTE
NOTE
NOTE
NOTE
1. Terminal numbers of outdoor and indoor units must be
matched.
2-1. Connect the remote controller only to the master unit.
2-2. The remote controller needs to be wired only to the mas-
ter unit; it does not need to be connected to the slave
units through transition wiring. (Do not connect transition
wiring to the slave units.)
2-3. The indoor temperature sensor is effective only for indoor
units to which the remote controller is connected.
2-4. The length of wiring between the indoor unit and the out-
door unit varies depending on the connected model, the
number of connected units, and the maximum piping
length.
For details, refer to the technical documents.
NOTE
NOTE
NOTE
NOTE
• Terminal numbers of outdoor and indoor units must be
matched.
When implementing group control
• When using as a pair unit or as a master unit for simultane-
ous operation system, you may carry out simultaneous start/
stop (group) control up to 16 units with the remote controller.
(Refer to Fig. 34)
• In this case, all the indoor units in the group will operate in
accordance with the group control remote controller.
• Select a remote controller which matches as many of the
functions (airflow direction, etc.) in the group as possible.
Wiring Method
(1) Remove the control box cover. (Refer to ‘‘9. HOW TO CON-
NECT WIRINGS AND WIRING EXAMPLE’’.)
(2) Connect crossover wiring between the terminals (P1, P2)
inside the control box for the remote controller. (There is no
polarity.) (Refer to Fig. 34 and Table 3)
Two remote controllers control (Controlling 1 indoor unit
by 2 remote controllers)
• When using 2 remote controllers, one must be set to “MAIN”
and the other to “SUB”.
MAIN/SUB CHANGEOVER
• Refer to the manual attached to the remote controller.
Wiring Method
(1) Remove the control box cover.
(2) Add wiring between the remote controller 2 (Sub) and the
terminal (P1, P2) of the terminal block (X1M) for the remote
controller in the control box. (There is no polarity.)
NOTE
NOTE
NOTE
NOTE
• Terminal numbers of outdoor and indoor units must be
matched.
P1 P2
1 2 3
1 2 3
1 2 3
P1 P2
P1 P2
P1 P2
1 2 3
1 2 3
1 2 3
Outdoor unit
Indoor unit
(Master)
Outdoor unit
Indoor unit
Indoor unit
Outdoor unit
Group control remote controller
(Optional accessory)
Earth leakage
breaker
Earth leakage
breaker
Earth leakage
breaker
NOTE)
NOTE)
NOTE)
Power supply
220 - 240V
~
50Hz
Power supply
220 - 240V
~
50Hz
Power supply
220 - 240V
~
50Hz
Group control
Fig. 33
Fig. 34
Outdoor
unit 1
Outdoor
unit 2
Outdoor
unit 16
Indoor
unit 1
Group control remote controller
Indoor
unit 2
(Slave)
Indoor
unit 2
(Master)
Indoor
unit 16
Fig. 35
Terminal for remote
controller wiring (P1, P2)
Crossover wiring
Terminal block
(X1M)
to next unit
Terminal block
(X1M)
Indoor unit 1
Indoor unit 2
(Master)
F2
P2 F1
P1
P1 P2
P1 P2
P1 P2
1 2 3
1 2 3
Outdoor unit
NOTE)
Indoor unit
Remote
controller
(Optional
accessory)
Remote
controller
(Optional
accessory)
Control with 2 remote controllers control
Earth
leakage
breaker
Outdoor unit
Indoor unit
(Slave)
Indoor unit
(Master)
Remote
controller 2
(Optional
accessory)
Remote
controller 1
(Optional
accessory)
Power supply
220 - 240V
~
50Hz
Fig. 36
Fig. 37
Remote
controller 1
(Main)
Remote
controller 2
(Sub)
Terminal block
(X1M)
(Master*)
Additional
remote controller
* For simultaneous operation system, be sure to
connect the remote controller to the master unit.
4PEN469440-1D.book Page 14 Tuesday, June 27, 2017 10:55 AM