Installation
ED41-016B
62
FDYB-KA Series
15.1.9 Field Setting
15.1.10 Test Operation
Upper part of remote controller
Lower part of remote controller
Insert the screwdriver here and gently
work off the upper part of remote controller.
S
M
S
S
M
Remote controller
PC board
(Factory setting)
(Only one remote controller needs to be changed)
C : 3PN00281-18T-10
〈
Field setting must be made from the remote controller in accordance with the installation condition.
〉
•
Setting can be made by changing the "Mode number", "FIRST CODE No.", and "SECOND CODE No.".
•
For setting and operation, refer to the "FIELD SETTING" in the installation manual of the remote controller.
Setting external static pressure
•
Change the SECOND CODE No. according to Table 3 depending on the resistance of the connecting duct.
SECOND CODE No. is factory set to "01"
Table 3
Setting air filter sign
•
Change to the SECOND CODE No. 02 according to Table 4.
∗
SECOND CODE No. is factory set to "01" for [ON]
•
Filter maintenance should be carried out which is appropriate to the type of filter in use.
Table 4
Control by 2 Remote Controllers (Controlling 1 indoor unit by 2 remote controllers)
•
When using 2 remote controllers, one must be set to "MAIN" and the other to "SUB".
•
The other remote controller is required. (Optional remote controller model: BRC1B62)
〈
MAIN/SUB CHANGEOVER
〉
(1) Insert a – screwdriver into the recess between the upper and lower part of remote
controller and, working from the 2 positions, pry off the upper part.
(The remote controller PC board is attached to the upper part of remote controller.)
(2) Turn the main/sub changeover switch on one of the two remote controller PC boards to "S". (Leave the switch of the other remote controller set to "M".)
External static pressure (50/60Hz)
Standard static pressure:
20Pa (2 mmH
2
O)
High static pressure:
69Pa (7 mmH
2
O)
Setting
Filter sign indication
[ON]
Filter sign indication
[OFF]
Mode No.
10 (20)
FIRST CODE No.
3
Mode No.
13 (23)
FIRST CODE No.
6
SECOND CODE No.
01
02
SECOND CODE No.
01
02
C : 3PN00281-18T-11
〈〈
Refer to the section of "FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND
CHECK AFTER INSTALLATION IS FINISHED" (p. 2).
〉〉
(1) Open the gas side stop valve.
(2) Open the liquid side stop valve.
(3) Electrify crank case heater for 6 or 12 hours. (Outdoor model K, KU type
→
6 hours, FU type
→
12 hours)
(4) Set to cooling operation with the remote controller and start operation by pushing ON/OFF button. ( )
(5) Press Inspection/Test Operation button 4 times ( ) and operate at Test Operation mode for 3 minutes.
(6) Press Inspection/Test Operation button ( ) and operate normally.
(7) Confirm function of unit according to the operation manual.
〈
PRECAUTIONS
〉
1. In case something is wrong with the unit and it does not operate,
refer to the malfunction diagnosis label attached to the unit.
TEST
TEST
Summary of Contents for FDYB-KA Series
Page 11: ...Dimensions ED41 016B 10 FDYB KA Series FDYB50KA Unit mm C 3D024201B...
Page 12: ...ED41 016B Dimensions FDYB KA Series 11 FDYB60KA Unit mm C 3D024202B...
Page 13: ...Dimensions ED41 016B 12 FDYB KA Series FDYB71KA Unit mm C 3D024203B...
Page 14: ...ED41 016B Dimensions FDYB KA Series 13 5 2 Outdoor Units RY35F RY50GA Unit mm 3D004853B...
Page 17: ...Dimensions ED41 016B 16 FDYB KA Series RY250KU Unit mm C 3D029264...
Page 18: ...ED41 016B Dimensions FDYB KA Series 17 5 3 Installation Service Space For RY71 3D001951A 1...
Page 19: ...Dimensions ED41 016B 18 FDYB KA Series 3D001951A 2...
Page 20: ...ED41 016B Dimensions FDYB KA Series 19 For RY200 250 3D006578A...
Page 24: ...ED41 016B Piping Diagrams FDYB KA Series 23 RY250KUY1 Double Twin C 3D029828...
Page 29: ...Wiring Diagrams ED41 016B 28 FDYB KA Series 7 2 Outdoor Units 7 2 1 50Hz RY35FV1A RY50GAV1A...
Page 30: ...ED41 016B Wiring Diagrams FDYB KA Series 29 RY60GAV1A RY71KUV1 3D014495B...
Page 31: ...Wiring Diagrams ED41 016B 30 FDYB KA Series RY71KUY1 3D014603C...
Page 32: ...ED41 016B Wiring Diagrams FDYB KA Series 31 7 2 2 60Hz RY50GVAL RY60GVAL...
Page 33: ...Wiring Diagrams ED41 016B 32 FDYB KA Series RY71FUVAL RY200KUTAL 3D005370B 3D028902A...
Page 34: ...ED41 016B Wiring Diagrams FDYB KA Series 33 RY250KUTAL 3D028903A...
Page 49: ...Fan Performance ED41 016B 48 FDYB KA Series 11 Fan Performance 11 1 Fan Performance FDYB35KAVE...
Page 50: ...ED41 016B Fan Performance FDYB KA Series 49 FDYB50KAVE...
Page 51: ...Fan Performance ED41 016B 50 FDYB KA Series FDYB60KAVE FDYB71KAVE...
Page 54: ...ED41 016B Optional Accessories FDYB KA Series 53 Wireless Remote Controller BRC4C62 3D007898...