![Daikin FDYB-KA Series Engineering Data Download Page 58](http://html1.mh-extra.com/html/daikin/fdyb-ka-series/fdyb-ka-series_engineering-data_2460404058.webp)
ED41-016B
Installation
FDYB-KA Series
57
15.1.4 Indoor Unit Installation
15.1.5 Refrigerant Piping Work
Nut (field supply)
Washer
(attached)
Tighten
(double nuts)
Fig. 5
Water level
Vinyl tube
Fig. 6
8
C : 3PN00281-18T-4
•
While installing unit, take care that dust etc. should not drop into the drainpan.
Install the indoor unit temporarily.
•
Attach the hanger bracket to the suspension bolt. Be sure to fix it securely by using a nut and
washer from the upper and lower sides of the hanger bracket.
Make sure the unit is level.
•
Level the unit with a level when installing. If the unit is not level, it could become the source of
water leaks.
•
Check if the unit is leveled at all four corners with a water level or a water-filled vinyl tube as
shown in the drawing.
Tighten the upper nut.
Be sure to completely insulate the duct to be connected (field supplied) and the connecting joint
on the main unit body
1
2
3
4
8
Torque wrench
Spanner
Piping union
Flare nut
Fig. 7
Coat here with
refrigerating machine oil.
Fig. 8
Fig. 9
Clamp
(×4)
Sealing pad
(Wrap the piping union with the sealing pad.)
Insulation for fitting (for gas pipe)
Piping fixing plate
Insulation for fitting (for liquid pipe)
Liquid piping (with insulation)
Gas piping (with insulation)
5
4
2
3
C : 3PN00281-18T-5
〈
For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.
〉
〈
Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Otherwise, a water leakage can result sometimes.
〉
WARNING Do not allow air or other substances other than the designated refrigerant to get mixed into the freezing cycle.
Ventilate the room if refrigerant gas leaks.
•
Use copper alloy seamless pipes. (lSO 1337)
•
The outdoor unit is charged with refrigerent.
•
Be sure to use both a spanner and torque wrench together, as shown in the drawing, when connecting or disconnecting pipes to/from the unit. (Fig. 7)
•
Refer to Table 1 for the dimensions of flare nut spaces.
•
When connecting the flare nut, coat the flare both inside and outside with refrigerating machine oil and initially tighten by hand 3 or 4 turns before
tightening firmly. (Fig. 8)
•
Refer to Table 1 to determine the proper tightening torque.
(Overtightening may damage the flare and cause leaks.)
•
Avoid the mixture into a refrigerating cycle of any air and whatnot except the designated refrigerant.
•
Make absolutely sure to execute heat insulation works on the pipe-connecting section after checking gas leakage by thoroughly studying the following
figure and using the attached heat insulating materials for couplings and . (Fasten both ends with the clamps .)
•
Wrap only the gas line side of the insulation for fitting (union) with the sealing pad . (Fig. 9)
•
Carry out sufficient ventilation if the refrigerant gas leaks during installation work.
•
Insulate connecting piping completely. While heating the highest temperature of gas piping became 120
°
C.
Use the insulator that the highest temperature can be resisted.
Table 1
Table
Pipe gauge
φ
6.4
φ
9.5
φ
12.7
φ
15.9
Pipe size
φ
6.4 (1/4")
φ
9.5 (3/8")
φ
12.7 (1/2")
φ
15.9 (5/8")
Further tightening angle
60 to 90 degrees
60 to 90 degrees
30 to 60 degrees
30 to 60 degrees
Recommended arm length of tool
Approx. 150mm
Approx. 200mm
Approx. 250mm
Approx. 300mm
Tightening torque
1420 – 1720 N
·
cm
(144 – 176 kgf
·
cm)
3270 – 3990 N
·
cm
(333 – 407 kgf
·
cm)
4950 – 6030 N
·
cm
(504 – 616 kgf
·
cm)
6180 – 7540 N
·
cm
(630 – 770 kgf
·
cm)
Flare dimensions A (mm)
8.3 – 8.7
12.0 – 12.4
15.4 – 15.8
18.6 – 19.0
Flare shape
If a torque wrench is not available, use the following method as a rule of thumb.
After the work is finished, make sure to check that there is no gas leak.
When you keep on tightening the flare nut with a spanner, there is a point where the tightening torque suddenly increases. From that position, further tighten
the flare nut the angle shown below:
2
3
5
4
For reference
R0.4 ~ 0.8
A
9
0
°
±
0
.5
°
45
°
±2
°
Summary of Contents for FDYB-KA Series
Page 11: ...Dimensions ED41 016B 10 FDYB KA Series FDYB50KA Unit mm C 3D024201B...
Page 12: ...ED41 016B Dimensions FDYB KA Series 11 FDYB60KA Unit mm C 3D024202B...
Page 13: ...Dimensions ED41 016B 12 FDYB KA Series FDYB71KA Unit mm C 3D024203B...
Page 14: ...ED41 016B Dimensions FDYB KA Series 13 5 2 Outdoor Units RY35F RY50GA Unit mm 3D004853B...
Page 17: ...Dimensions ED41 016B 16 FDYB KA Series RY250KU Unit mm C 3D029264...
Page 18: ...ED41 016B Dimensions FDYB KA Series 17 5 3 Installation Service Space For RY71 3D001951A 1...
Page 19: ...Dimensions ED41 016B 18 FDYB KA Series 3D001951A 2...
Page 20: ...ED41 016B Dimensions FDYB KA Series 19 For RY200 250 3D006578A...
Page 24: ...ED41 016B Piping Diagrams FDYB KA Series 23 RY250KUY1 Double Twin C 3D029828...
Page 29: ...Wiring Diagrams ED41 016B 28 FDYB KA Series 7 2 Outdoor Units 7 2 1 50Hz RY35FV1A RY50GAV1A...
Page 30: ...ED41 016B Wiring Diagrams FDYB KA Series 29 RY60GAV1A RY71KUV1 3D014495B...
Page 31: ...Wiring Diagrams ED41 016B 30 FDYB KA Series RY71KUY1 3D014603C...
Page 32: ...ED41 016B Wiring Diagrams FDYB KA Series 31 7 2 2 60Hz RY50GVAL RY60GVAL...
Page 33: ...Wiring Diagrams ED41 016B 32 FDYB KA Series RY71FUVAL RY200KUTAL 3D005370B 3D028902A...
Page 34: ...ED41 016B Wiring Diagrams FDYB KA Series 33 RY250KUTAL 3D028903A...
Page 49: ...Fan Performance ED41 016B 48 FDYB KA Series 11 Fan Performance 11 1 Fan Performance FDYB35KAVE...
Page 50: ...ED41 016B Fan Performance FDYB KA Series 49 FDYB50KAVE...
Page 51: ...Fan Performance ED41 016B 50 FDYB KA Series FDYB60KAVE FDYB71KAVE...
Page 54: ...ED41 016B Optional Accessories FDYB KA Series 53 Wireless Remote Controller BRC4C62 3D007898...