Installation
ED41-016B
58
FDYB-KA Series
Caution to be Taken When Brazing Refrigerant Piping
“Do not use flux when brazing copper-to-copper refrigerant piping. (Particularly for the HFC refrigerant
piping) Therefore, use the phosphor copper brazing filler metal (BCuP) which does not require flux.”
(Flux has extremely harmful influence on refrigerant piping systems. For instance, if the chlorine based flux
is used, it will cause pipe corrosion or, in particular, if the flux contains fluorine, it will damage the refrigerant
oil. The use of flux is strictly forbidden since the cleaning on site is impossible.)
15.1.6 Drain Piping Work
(Caution) Keep in mind that if the phosphor copper brazing filler metal is used and the brazing temperature
and the heating time exceed a certain point, the phosphor changes into the gaseous state (e.g.
BCuP -1 to 5 : between 700 and 800°C) which causes pin holes and results in refrigerant
leakage.
Rubber plug
Drain pipe (3/4 B)
Nominal diameter 26
Completely
insulate
Units: mm
Fig. 11
Completely insulate
Do not raise.
Do not bend.
Do not leave
in water.
Drain piping
Central drain piping
100mm
or more
Fig. 12
Watering can
Fig. 13
WRONG
CORRECT
Fig. 10
Rig drain piping
•
Keep piping as short as possible and slope it downwards so that
air may not remained trapped inside the pipe.
WARNING Rig the drain pipe as shown below and take
measures against condensation, improperly
rigged piping could lead to leaks and eventually
wet furniture and belongings.
Connect the drain pipe as described below
•
It is necessary to clean the drainpan.
•
The drain pipe outlet can be either on the right or left side.
•
After making the connection, wrap the drain pipes completely with insulation.
•
When connecting the drain pipe to the outlet on the left side, remote the rubber plug and attached it to the outlet
on the right side.
•
Insulate the drain hose inside the building.
•
In order to prevent foreign matter from building up inside the piping, you should avoid curves as much as
possible, and arrange so the trap can be cleaned.
NOTE)
•
If installing central drain piping, install according to the following right figure.
C : 3PN00281-18T-6
1
After piping work is finished, check drainage flows smoothly.
•
Add approximately 1000 cc of water gradually and check drainage flow. (Fig. 13)
•
Make sure that water does not leak from the drain piping, connecting parts and the drain plug.
2
WHEN ELECTRIC WIRING WORK IS FINISHED
•
Check drainage flow during COOL running, explained under the section entitled TEST OPERATION.
Summary of Contents for FDYB-KA Series
Page 11: ...Dimensions ED41 016B 10 FDYB KA Series FDYB50KA Unit mm C 3D024201B...
Page 12: ...ED41 016B Dimensions FDYB KA Series 11 FDYB60KA Unit mm C 3D024202B...
Page 13: ...Dimensions ED41 016B 12 FDYB KA Series FDYB71KA Unit mm C 3D024203B...
Page 14: ...ED41 016B Dimensions FDYB KA Series 13 5 2 Outdoor Units RY35F RY50GA Unit mm 3D004853B...
Page 17: ...Dimensions ED41 016B 16 FDYB KA Series RY250KU Unit mm C 3D029264...
Page 18: ...ED41 016B Dimensions FDYB KA Series 17 5 3 Installation Service Space For RY71 3D001951A 1...
Page 19: ...Dimensions ED41 016B 18 FDYB KA Series 3D001951A 2...
Page 20: ...ED41 016B Dimensions FDYB KA Series 19 For RY200 250 3D006578A...
Page 24: ...ED41 016B Piping Diagrams FDYB KA Series 23 RY250KUY1 Double Twin C 3D029828...
Page 29: ...Wiring Diagrams ED41 016B 28 FDYB KA Series 7 2 Outdoor Units 7 2 1 50Hz RY35FV1A RY50GAV1A...
Page 30: ...ED41 016B Wiring Diagrams FDYB KA Series 29 RY60GAV1A RY71KUV1 3D014495B...
Page 31: ...Wiring Diagrams ED41 016B 30 FDYB KA Series RY71KUY1 3D014603C...
Page 32: ...ED41 016B Wiring Diagrams FDYB KA Series 31 7 2 2 60Hz RY50GVAL RY60GVAL...
Page 33: ...Wiring Diagrams ED41 016B 32 FDYB KA Series RY71FUVAL RY200KUTAL 3D005370B 3D028902A...
Page 34: ...ED41 016B Wiring Diagrams FDYB KA Series 33 RY250KUTAL 3D028903A...
Page 49: ...Fan Performance ED41 016B 48 FDYB KA Series 11 Fan Performance 11 1 Fan Performance FDYB35KAVE...
Page 50: ...ED41 016B Fan Performance FDYB KA Series 49 FDYB50KAVE...
Page 51: ...Fan Performance ED41 016B 50 FDYB KA Series FDYB60KAVE FDYB71KAVE...
Page 54: ...ED41 016B Optional Accessories FDYB KA Series 53 Wireless Remote Controller BRC4C62 3D007898...