Installation
ED41-016B
64
FDYB-KA Series
Outdoor unit
Gauge manifold
Low
side
High
side
Stop valve for liquid
Stop valve for gas
Service port
Vacuum
pump
1
2
3
L N
1 2 3
L N
V1, VAL, TYPE Power supply
•
The outdoor unit has the Fuse (5A)
for the interconnection cable.
Select the interconnection cable size
with the Fuse (5A).
Indoor unit
Outdoor unit
C : 3PN00281-18T-13
〈
REFRIGERANT PIPING
〉
Model
Max. allowable length
Max allowable height
Additional refrigerant
required for refrigerant
pipe exceeding 10m
in length. (NOTE 1)
Gas pipe
Liquid pipe
RY35
20 m
20g/m
φ
12.7
×
t 0.8
RY60
60g/m
Heat pump
RY50
15 m
30g/m
φ
6.4
×
t 0.8
30 m
φ
15.9
×
t 1.0
NOTE: 1) If RY60 type is connected, extra refrigerant
is needed if 5m is exceeded.
2) For pipe connection refer to
"REFRIGERANT PIPING WORK".
〈
AIR PURGE
〉
•
Leak test
1. Evaluate the pipes and check vacuum. (No pressure increase for 1 minute)
2. Charge Nitrogen (N
2
)
3. Check for leaks by applying soap water to pipe connections.
4. Discharge Nitrogen.
5. Conduct air purge again and check vacuum.
6. Open valves and charge refrigerant into the connection pipe and into the indoor unit.
7. Leak test must follow the standard pr. EN378-7.
〈
ELECTRIC WIRING WORK
〉
•
All field supplied parts and materials and electric works must conform to local codes.
•
All wiring must be performed by an authorized electrician.
•
Use copper wires only.
•
For electric wiring work, refer also to the "WIRING DIAGRAM" attached to the outdoor unit.
•
A circuit breaker capable of shutting down power supply to the entire system must be installed.
Model
Series
RY35
RY50
RY60
Type
V1
V1
VAL
V1
VAL
Field fuse
15
20
20
20
25
Cable type (
∗
)
H05VV–U3G
H05VV–U3G
H05VV–U3G
Power supply
Interconnection cable
type (
∗
)
H05VV–U4G
H05VV–U4G
H05VV–U4G
Size
Wiring size must comply
with the applicable local
and national code.
∗
Only in protected pipes, for outdoor installation use type H07RN · F.
Summary of Contents for FDYB-KA Series
Page 11: ...Dimensions ED41 016B 10 FDYB KA Series FDYB50KA Unit mm C 3D024201B...
Page 12: ...ED41 016B Dimensions FDYB KA Series 11 FDYB60KA Unit mm C 3D024202B...
Page 13: ...Dimensions ED41 016B 12 FDYB KA Series FDYB71KA Unit mm C 3D024203B...
Page 14: ...ED41 016B Dimensions FDYB KA Series 13 5 2 Outdoor Units RY35F RY50GA Unit mm 3D004853B...
Page 17: ...Dimensions ED41 016B 16 FDYB KA Series RY250KU Unit mm C 3D029264...
Page 18: ...ED41 016B Dimensions FDYB KA Series 17 5 3 Installation Service Space For RY71 3D001951A 1...
Page 19: ...Dimensions ED41 016B 18 FDYB KA Series 3D001951A 2...
Page 20: ...ED41 016B Dimensions FDYB KA Series 19 For RY200 250 3D006578A...
Page 24: ...ED41 016B Piping Diagrams FDYB KA Series 23 RY250KUY1 Double Twin C 3D029828...
Page 29: ...Wiring Diagrams ED41 016B 28 FDYB KA Series 7 2 Outdoor Units 7 2 1 50Hz RY35FV1A RY50GAV1A...
Page 30: ...ED41 016B Wiring Diagrams FDYB KA Series 29 RY60GAV1A RY71KUV1 3D014495B...
Page 31: ...Wiring Diagrams ED41 016B 30 FDYB KA Series RY71KUY1 3D014603C...
Page 32: ...ED41 016B Wiring Diagrams FDYB KA Series 31 7 2 2 60Hz RY50GVAL RY60GVAL...
Page 33: ...Wiring Diagrams ED41 016B 32 FDYB KA Series RY71FUVAL RY200KUTAL 3D005370B 3D028902A...
Page 34: ...ED41 016B Wiring Diagrams FDYB KA Series 33 RY250KUTAL 3D028903A...
Page 49: ...Fan Performance ED41 016B 48 FDYB KA Series 11 Fan Performance 11 1 Fan Performance FDYB35KAVE...
Page 50: ...ED41 016B Fan Performance FDYB KA Series 49 FDYB50KAVE...
Page 51: ...Fan Performance ED41 016B 50 FDYB KA Series FDYB60KAVE FDYB71KAVE...
Page 54: ...ED41 016B Optional Accessories FDYB KA Series 53 Wireless Remote Controller BRC4C62 3D007898...