ED41-016B
Capacity Table
FDYB-KA Series
41
8.3
Change in Capacity (Reference)
8.3.1
RY35F, 50G(A), 60G(A), 71KU
Capacity correction factor by the length of refrigerant piping (Reference)
The cooling and the heating capacity of the unit has to be corrected in accordance with the length of
refrigerant piping. (The distance between the indoor unit and the outdoor unit)
Notes:
1.
line: Correction factor for heating capacity
line: Correction factor for cooling capacity
2. The correction factor remains the same whether the outdoor unit is to be installed above or below the
indoor unit.
3. You cannot extend the refrigerant piping exceeding the limit shown in the above table. However, if the
unit has a limited length of refrigerant piping less than 50m, refer to the correction factor within the
range of its limitation.
8.3.2
RY71FU, 200KU, 250KU
Length of refrigerant piping (Total length)
0
80
85
90
95
100
(%)
5
10
15
20
25
30
35
40
45
50 (m)
Cooling/Heating capacity correction factor
71
71
35 : 20m
50·60 : 30m
35 : 20m
50·60 : 30m
(P1003)
3D006500B
Summary of Contents for FDYB-KA Series
Page 11: ...Dimensions ED41 016B 10 FDYB KA Series FDYB50KA Unit mm C 3D024201B...
Page 12: ...ED41 016B Dimensions FDYB KA Series 11 FDYB60KA Unit mm C 3D024202B...
Page 13: ...Dimensions ED41 016B 12 FDYB KA Series FDYB71KA Unit mm C 3D024203B...
Page 14: ...ED41 016B Dimensions FDYB KA Series 13 5 2 Outdoor Units RY35F RY50GA Unit mm 3D004853B...
Page 17: ...Dimensions ED41 016B 16 FDYB KA Series RY250KU Unit mm C 3D029264...
Page 18: ...ED41 016B Dimensions FDYB KA Series 17 5 3 Installation Service Space For RY71 3D001951A 1...
Page 19: ...Dimensions ED41 016B 18 FDYB KA Series 3D001951A 2...
Page 20: ...ED41 016B Dimensions FDYB KA Series 19 For RY200 250 3D006578A...
Page 24: ...ED41 016B Piping Diagrams FDYB KA Series 23 RY250KUY1 Double Twin C 3D029828...
Page 29: ...Wiring Diagrams ED41 016B 28 FDYB KA Series 7 2 Outdoor Units 7 2 1 50Hz RY35FV1A RY50GAV1A...
Page 30: ...ED41 016B Wiring Diagrams FDYB KA Series 29 RY60GAV1A RY71KUV1 3D014495B...
Page 31: ...Wiring Diagrams ED41 016B 30 FDYB KA Series RY71KUY1 3D014603C...
Page 32: ...ED41 016B Wiring Diagrams FDYB KA Series 31 7 2 2 60Hz RY50GVAL RY60GVAL...
Page 33: ...Wiring Diagrams ED41 016B 32 FDYB KA Series RY71FUVAL RY200KUTAL 3D005370B 3D028902A...
Page 34: ...ED41 016B Wiring Diagrams FDYB KA Series 33 RY250KUTAL 3D028903A...
Page 49: ...Fan Performance ED41 016B 48 FDYB KA Series 11 Fan Performance 11 1 Fan Performance FDYB35KAVE...
Page 50: ...ED41 016B Fan Performance FDYB KA Series 49 FDYB50KAVE...
Page 51: ...Fan Performance ED41 016B 50 FDYB KA Series FDYB60KAVE FDYB71KAVE...
Page 54: ...ED41 016B Optional Accessories FDYB KA Series 53 Wireless Remote Controller BRC4C62 3D007898...