12 Unit installation
Installation and operation manual
15
FDA125A5VEB
Split system air conditioners
4P494410-1D – 2022.10
▪ General guidelines
▪ Connecting the drain piping to the indoor unit
▪ Checking for water leaks
General guidelines
▪
Drain pump.
For this "high lift type", the drainage sounds will be
reduced when the drain pump is installed in a higher location.
Recommended height is 300 mm.
▪
Pipe length.
Keep drain piping as short as possible.
▪
Pipe size.
Keep the pipe size equal to or greater than that of the
connecting pipe (vinyl pipe of 20 mm nominal diameter and
26 mm outer diameter).
▪
Slope.
Make sure the drain piping slopes down (at least 1/100) to
prevent air from being trapped in the piping. Use hanging bars as
shown.
1~1.5 m
a
a
Hanging bar
Allowed
Not allowed
▪
Condensation.
Take measures against condensation. Insulate
the complete drain piping in the building.
▪
Rising piping
. If necessary to make the slope possible, you can
install rising piping.
▪ Drain hose inclination: 0~75 mm to avoid stress on the piping
and to avoid air bubbles.
▪ Rising piping: ≤300 mm from the unit, ≤625 mm perpendicular
to the unit.
≤625
≤300
0~75
1000~1500
(mm)
b
a
b
a
d
d
c
a
Metal clamp (accessory)
b
Drain hose (accessory)
c
Rising drain piping (vinyl pipe of 25 mm nominal diameter
and 32 mm outer diameter) (field supply)
d
Hanging bars (field supply)
▪
Combining drain pipes.
You can combine drain pipes. Make
sure to use drain pipes and T-joints with the correct gauge for the
operating capacity of the units.
≥100
≤625
(mm)
a
a
T-joint
To connect the drain piping to the indoor unit
NOTICE
Incorrect connection of the drain hose might cause leaks,
and damage the installation space and surroundings.
1
Push the drain hose as far as possible over the drain pipe
connection.
2
Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.
3
4
Install the insulation piece (drain pipe).
5
Wind the large sealing pad (= insulation) around the metal
clamp and drain hose, and fix it with cable ties.
6
Connect the drain piping to the drain hose.
≤4 mm
A
A'
A-A'
A
A'
f
6
5
2
c
e
4
b
a
d
b
a
d
c
3
1
2~6
1
a
Drain pipe connection (attached to the unit)
b
Drain hose (accessory)
c
Metal clamp (accessory)
d
Large sealing pad (accessory)
e
Insulation piece (drain pipe) (accessory)
f
Drain piping (field supply)
NOTICE
▪ Do NOT remove the drain pipe plug. Water might leak
out.
▪ Use the drain outlet only to discharge the water if the
drain pump is not used or before maintenance.
▪ Insert and remove the drain plug gently. Excessive
force may deform the drain socket of the drain pan.
Pull out the plug.
▪ Do NOT wiggle the plug up and down.
a
Push in the plug.
▪ Set the plug and push it in using a Phillips screwdriver.
a
b
a
Drain plug
b
Philips screwdriver