14 Electrical installation

Installation and operation manual

17

FDA125A5VEB
Split system air conditioners
4P494410-1D – 2022.10

WARNING: MILDLY FLAMMABLE MATERIAL

The  R32  refrigerant  (if  applicable)  in  this  unit  is  mildly
flammable.  Refer  to  the  outdoor  unit  specifications  for  the
type of refrigerant to be used.

Pipe length

. Keep refrigerant piping as short as possible.

Flare  connections

.  Connect  refrigerant  piping  to  the  unit  using

flare connections.

Insulation

.  Insulate  the  refrigerant  piping  on  the  indoor  unit  as

follows:

B

A

a

d

c

e f

b

b

a

d

c

e f

b

b

2

4

3

g

1

2

3

4

g

1

A B

A

Liquid piping

B

Gas piping

a

Insulation material (field supply)

b

Tie wrap (field supply)

c

Insulation pieces: Large (gas pipe), small (liquid pipe)
(accessories)

d

Flare nut (attached to the unit)

e

Refrigerant pipe connection (attached to the unit)

f

Unit

g

Sealing pads: Medium 1 (gas pipe), medium 2 (liquid
pipe) (accessories)

1

Turn up the seams of the insulation pieces.

2

Attach to the base of the unit.

3

Tighten the tie wrap on the insulation pieces.

4

Wrap the sealing pad from the base of the unit to the top
of the flare nut.

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

14

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provides  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Prevent hazards due to inadvertent resetting of the thermal
cut-out:  power  to  this  appliance  MUST  NOT  be  supplied
through  an  external  switching  device,  such  as  a  timer,  or
connected to a circuit that is regularly turned ON and OFF
by the utility.

14.1

Specifications of standard wiring
components

NOTICE

We recommend using solid (single-core) wires. If stranded
wires are used, slightly twist the strands to consolidate the
end  of  the  conductor  for  either  direct  use  in  the  terminal
clamp  or  insertion  in  a  round  crimp-style  terminal.  Details
are described in "Guidelines when connecting the electrical
wiring" in the installer reference guide.

Component

FDA125A

Power supply
cable

MCA

(a)

2.1 A

Voltage

220~240 V

Current

2.1 A

Phase

1~

Frequency

50/60 Hz

Wire sizes

MUST comply with national wiring

regulation.

3-core cable

Wire size based on the current,

but not less than 2.5 mm

2

Interconnection
cable
(indoor↔outdoor)

Voltage

220~240 V

Wire size

Only use harmonised wire

providing double insulation and

suitable for applicable voltage.

4-core cable

Minimum 1.5 mm

2

User interface
cable

Wire size

Only use harmonised wire

providing double insulation and

suitable for applicable voltage

2-core wire

Wire length

Maximum 500 m

Recommended field fuse

16 A

Earth leakage circuit breaker /
residual current device

MUST comply with national wiring

regulation

(a)

MCA=Minimum circuit ampacity. Stated values are maximum
values (see electrical data of indoor unit for exact values).

14.2

To connect the electrical wiring to
the indoor unit

NOTICE

▪ Follow  the  wiring  diagram  (delivered  with  the  unit,

located on the switch box cover).

▪ Make  sure  the  electrical  wiring  does  NOT  obstruct

proper reattachment of the service cover.

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover.

2

User  interface  cable

:  Route  the  cable  through  the  frame,

connect the cable to the terminal block, and fix the cable with a
cable tie.

Summary of Contents for FDA125A5VEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FDA125A5VEB...

Page 2: ...j atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robky pou vaj v...

Page 3: ...s amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following th...

Page 4: ...ical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied ma...

Page 5: ...xternal static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas duct so vibrations are NOT transmitted to the duct or ceiling...

Page 6: ...and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children SHALL NOT play with the appliance Cleaning...

Page 7: ...t is unhealthy to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 8: ...in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used WARNING The appliance using R32 refrigerant shall be stored so as to prevent mechanical...

Page 9: ...ce CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the inte...

Page 10: ...eration During defrost operation the indoor unit fan will stop operation and the following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minute...

Page 11: ...efrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used WARNING The appliance using R32 refrigerant shall be stored so...

Page 12: ...igerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used 11 1 1 To remove the accessories from the indoor unit 16 8 1 1 3...

Page 13: ...nside of the unit 4 Reinstall the interchangeable plate When installing an air inlet duct select fixing screws that stick out 5 mm on the inside of the flange to protect the air filter from damage dur...

Page 14: ...ation insulation rubber to the hanging bolts When welding make sure NOT to spatter onto the drain pan or the air filter If the metal duct passes through a metal lath wire lath or metal plate of the wo...

Page 15: ...eld supply d Hanging bars field supply Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with the correct gauge for the operating capacity of the units 100 62...

Page 16: ...ompliant with the latest version of ISO14903 can be used NOTICE The piping and other pressure containing parts shall be suitable for refrigerant Use phosphoric acid deoxidised seamless copper for refr...

Page 17: ...at is regularly turned ON and OFF by the utility 14 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are used slightly twist the stran...

Page 18: ...at the interface point between the user s supply and the public system EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment conne...

Page 19: ...est run is only completed if there is no malfunction code displayed on the user interface See the service manual for the complete list of error codes and a detailed troubleshooting guideline for each...