15 Commissioning

Installation and operation manual

18

FDA125A5VEB

Split system air conditioners

4P494410-1D – 2022.10

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

4

Divide  the  small  sealing  (accessory)  and  wrap  it  around  the
cables to prevent water from entering the unit. Seal all gaps to
prevent small animals from entering the system.

5

Reattach the service cover.

When using 1 user interface with 1 indoor unit.

1 2 3

a

a

a

b

c

1 2 3

P

1

P

2

P

1

P

2

d

1 2

L N

3

b

c

b

c

1 2 3

P

1

P

2

P

1

P

2

d

L N

L N

L N

When using 2 user interfaces

(1)

1 2 3

b

c

1 2 3

P

1

P

2

P

1

P

2

P

1

P

2

d

d

a

L N

b

c

a

L N

When using group control

(1)

b

c

P

1

P

2

d

P

1

P

2

P

1

P

2

P

1

P

2

a

1 2 3 L N

1 2 3

1 2 3 L N

1 2 3

1 2 3 L N

1 2 3

b

c

a

b

c

a

b

c

a

b

c

a

b

c

a

L N

L N

L N

a

Power supply

b

Main switch

c

Fuse

d

User interface

Master unit:

 Be sure to connect the wiring when combining with a

simultaneously operating multi-type in group control.

INFORMATION

In  case  of  group  control,  it  is  not  necessary  to  assign  a
group  address  to  the  indoor  unit.  The  group  address  is
automatically set when the power is turned on.

EN/IEC  61000‑3‑12

  provided  that  the  short-circuit  power  S

sc

  is

greater  than  or  equal  to  the  minimum  S

sc

  value  at  the  interface

point between the user's supply and the public system.

▪ EN/IEC 

61000‑3‑12 

European/International 

Technical

Standard  setting  the  limits  for  harmonic  currents  produced  by
equipment  connected  to  public  low-voltage  systems  with  input
current >16 A and ≤75 A per phase.

▪ It is the responsibility of the installer or user of the equipment to

ensure, by consultation with the distribution network operator if
necessary,  that  the  equipment  is  connected  ONLY  to  a  supply
with  a  short-circuit  power  S

sc

  greater  than  or  equal  to  the

minimum S

sc

 value.

To  comply  with  EN/IEC  61000‑3‑12,  following  rules  must  be
considered:

▪ In  case  of  combination  of  units  2x  FDA125A  +  RZQ250,  use

separate power supplies.

N

L

2

1

3

▪ Otherwise,  refer  to  the  table  with  S

sc

  values  for  FDA125A  on  the

extranet.

▪ If  the  S

sc

  value  is  NOT  mentioned  in  the  table  for  the  used

combination, use the common power supply wire delivered with
the unit.

▪ If  the  S

sc

  value  is  mentioned  in  the  table,  both  the  common

power supply wire or a separate power supply can be used, but
a separate power supply is preferred.

L N

2

1

3

a

a

Wire for common power supply (accessory)

15

Commissioning

NOTICE

General 

commissioning 

checklist.

 

Next 

to 

the

commissioning  instructions  in  this  chapter,  a  general
commissioning  checklist  is  also  available  on  the  Daikin
Business Portal (authentication required).

The  general  commissioning  checklist  is  complementary  to
the  instructions  in  this  chapter  and  can  be  used  as  a
guideline and reporting template during commissioning and
hand-over to the user.

(1)

Dashed line represents separate power supply.

Summary of Contents for FDA125A5VEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FDA125A5VEB...

Page 2: ...j atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robky pou vaj v...

Page 3: ...s amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following th...

Page 4: ...ical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied ma...

Page 5: ...xternal static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas duct so vibrations are NOT transmitted to the duct or ceiling...

Page 6: ...and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children SHALL NOT play with the appliance Cleaning...

Page 7: ...t is unhealthy to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 8: ...in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used WARNING The appliance using R32 refrigerant shall be stored so as to prevent mechanical...

Page 9: ...ce CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the inte...

Page 10: ...eration During defrost operation the indoor unit fan will stop operation and the following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minute...

Page 11: ...efrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used WARNING The appliance using R32 refrigerant shall be stored so...

Page 12: ...igerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used 11 1 1 To remove the accessories from the indoor unit 16 8 1 1 3...

Page 13: ...nside of the unit 4 Reinstall the interchangeable plate When installing an air inlet duct select fixing screws that stick out 5 mm on the inside of the flange to protect the air filter from damage dur...

Page 14: ...ation insulation rubber to the hanging bolts When welding make sure NOT to spatter onto the drain pan or the air filter If the metal duct passes through a metal lath wire lath or metal plate of the wo...

Page 15: ...eld supply d Hanging bars field supply Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with the correct gauge for the operating capacity of the units 100 62...

Page 16: ...ompliant with the latest version of ISO14903 can be used NOTICE The piping and other pressure containing parts shall be suitable for refrigerant Use phosphoric acid deoxidised seamless copper for refr...

Page 17: ...at is regularly turned ON and OFF by the utility 14 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are used slightly twist the stran...

Page 18: ...at the interface point between the user s supply and the public system EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment conne...

Page 19: ...est run is only completed if there is no malfunction code displayed on the user interface See the service manual for the complete list of error codes and a detailed troubleshooting guideline for each...

Page 20: ...represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Connection Protective earth screw Connector A Rectifier Symbol Meaning Symbol Meani...

Page 21: ...stor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch...

Page 22: ......

Page 23: ......

Page 24: ...4P494410 1D 2022 10 Copyright 2017 Daikin Verantwortung f r Energie und Umwelt...

Reviews: