4 About the system

Installation and operation manual

9

FDA125A5VEB
Split system air conditioners
4P494410-1D – 2022.10

4

About the system

WARNING

▪ Do  NOT  modify,  disassemble,  remove,  reinstall  or

repair  the  unit  yourself  as  incorrect  dismantling  or
installation  may  cause  an  electrical  shock  or  fire.
Contact your dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe  and  non-toxic.  R410A  is  a  non-combustible
refrigerant,  and  R32  is  a  mildly  flammable  refrigerant,
but  they  will  generate  a  toxic  gas  when  they
accidentally  leak  into  a  room  where  combustible  air
from  fan  heaters,  gas  cookers,  etc.  is  present.  Always
have  qualified  service  personnel  confirm  that  the  point
of  leakage  has  been  repaired  or  corrected  before
resuming operation.

NOTICE

Do  NOT  use  the  system  for  other  purposes.  In  order  to
avoid  any  quality  deterioration,  do  NOT  use  the  unit  for
cooling  precision  instruments,  food,  plants,  animals,  or
works of art.

NOTICE

For future modifications or expansions of your system:

A  full  overview  of  allowable  combinations  (for  future
system  extensions)  is  available  in  technical  engineering
data  and  should  be  consulted.  Contact  your  installer  to
receive more information and professional advice.

4.1

System layout

INFORMATION

The  following  figures  are  just  examples  and  may  NOT
completely match your system layout.

b

f

a

h

c

d

e

g

a

Indoor unit

b

Outdoor unit

c

User interface

d

Suction air

e

Discharge air

f

Refrigerant interconnection cable

g

Drain pipe

h

Earth wiring

5

User interface

CAUTION

▪ NEVER touch the internal parts of the controller.

▪ Do NOT remove the front panel. Some parts inside are

dangerous  to  touch  and  appliance  problems  may
happen.  For  checking  and  adjusting  the  internal  parts,
contact your dealer.

NOTICE

Do  NOT  wipe  the  controller  operation  panel  with  benzine,
thinner,  chemical  dust  cloth,  etc.  The  panel  may  get
discoloured  or  the  coating  peeled  off.  If  it  is  heavily  dirty,
soak  a  cloth  in  water-diluted  neutral  detergent,  squeeze  it
well  and  wipe  the  panel  clean.  Wipe  it  with  another  dry
cloth.

NOTICE

NEVER press the button of the user interface with a hard,
pointed object. The user interface may be damaged.

NOTICE

NEVER pull or twist the electric wire of the user interface. It
may cause the unit to malfunction.

This operation manual offers a non-exhaustive overview of the main
functions of the system.

For  more  information  about  the  user  interface,  see  the  operation
manual of the installed user interface.

6

Operation

6.1

Operation range

For combination with R410A outdoor unit

Outdoor units Temperature

Cooling

Heating

RZQ250

Outdoor

–5~46°C DB

–15~15°C WB

Indoor

14~28°C WB

10~27°C DB

RZQG125

Outdoor

–15~50°C DB

–20~15.5°C WB

Indoor

12~28°C WB

10~27°C DB

RZQSG125

Outdoor

–15~46°C DB

–15~15.5°C WB

Indoor

14~28°C WB

10~27°C DB

RR125

Outdoor

–15~46°C DB

Indoor

12~28°C WB

RQ125

Outdoor

–5~46°C DB

–10~15°C WB

Indoor

12~28°C WB

10~27°C DB

Indoor humidity

≤80%

(a)

(a)

To avoid condensation and water dripping out of the unit. If the
temperature or the humidity is beyond these conditions, safety
devices may be put in action and the air conditioner may not
operate.

For combination with R32 outdoor unit

Outdoor units Temperature

Cooling

Heating

RZAG125

Outdoor

–20~52°C DB

–20~24°C DB

–20~18°C WB

Indoor

17~38°C DB

12~28°C WB

10~27°C DB

Summary of Contents for FDA125A5VEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FDA125A5VEB...

Page 2: ...j atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robky pou vaj v...

Page 3: ...s amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following th...

Page 4: ...ical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied ma...

Page 5: ...xternal static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas duct so vibrations are NOT transmitted to the duct or ceiling...

Page 6: ...and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children SHALL NOT play with the appliance Cleaning...

Page 7: ...t is unhealthy to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 8: ...in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used WARNING The appliance using R32 refrigerant shall be stored so as to prevent mechanical...

Page 9: ...ce CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the inte...

Page 10: ...eration During defrost operation the indoor unit fan will stop operation and the following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minute...

Page 11: ...efrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used WARNING The appliance using R32 refrigerant shall be stored so...

Page 12: ...igerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used 11 1 1 To remove the accessories from the indoor unit 16 8 1 1 3...

Page 13: ...nside of the unit 4 Reinstall the interchangeable plate When installing an air inlet duct select fixing screws that stick out 5 mm on the inside of the flange to protect the air filter from damage dur...

Page 14: ...ation insulation rubber to the hanging bolts When welding make sure NOT to spatter onto the drain pan or the air filter If the metal duct passes through a metal lath wire lath or metal plate of the wo...

Page 15: ...eld supply d Hanging bars field supply Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with the correct gauge for the operating capacity of the units 100 62...

Page 16: ...ompliant with the latest version of ISO14903 can be used NOTICE The piping and other pressure containing parts shall be suitable for refrigerant Use phosphoric acid deoxidised seamless copper for refr...

Page 17: ...at is regularly turned ON and OFF by the utility 14 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are used slightly twist the stran...

Page 18: ...at the interface point between the user s supply and the public system EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment conne...

Page 19: ...est run is only completed if there is no malfunction code displayed on the user interface See the service manual for the complete list of error codes and a detailed troubleshooting guideline for each...

Page 20: ...represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Connection Protective earth screw Connector A Rectifier Symbol Meaning Symbol Meani...

Page 21: ...stor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch...

Page 22: ......

Page 23: ......

Page 24: ...4P494410 1D 2022 10 Copyright 2017 Daikin Verantwortung f r Energie und Umwelt...

Reviews: