9 Relocation

Installation and operation manual

12

FDA125A5VEB

Split system air conditioners

4P494410-1D – 2022.10

Malfunction

Measure

If the user interface displays 

.

Notify your installer and
report the error code. To
display an error code see
the reference guide of the
user interface.

INFORMATION

Refer  to  the  reference  guide  located  on 

https://

www.daikin.eu

  for  more  troubleshooting  tips.  Use  the

search function   to find your model.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

9

Relocation

Contact  your  dealer  to  remove  and  reinstall  the  entire  unit.  Moving
units requires technical expertise.

10

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

For the installer

11

About the box

11.1

Indoor unit

INFORMATION

The  following  figures  are  just  examples  and  may  NOT
completely match your system layout.

WARNING: MILDLY FLAMMABLE MATERIAL

The  R32  refrigerant  (if  applicable)  in  this  unit  is  mildly
flammable.  Refer  to  the  outdoor  unit  specifications  for  the
type of refrigerant to be used.

11.1.1

To remove the accessories from the
indoor unit

16×

d

c

b

a

e

f

g

h

i

j

a

Installation and operation manual

b

General safety precautions

c

Washers for hanger bracket

d

Screws for duct flanges

e

Metal clamp

f

Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe)

g

Drain hose

h

Insulation piece: Small (liquid pipe)

i

Insulation piece: Large (gas pipe)

j

Wire for common power supply

12

Unit installation

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

12.1

Preparing the installation site

WARNING

The  appliance  using  R32  refrigerant  shall  be  stored  so  as
to  prevent  mechanical  damage  and  in  a  well-ventilated
room  without  continuously  operating  ignition  sources  (e.g.
open  flames,  an  operating  gas  appliance,  or  an  operating
electric heater). The room size shall be as specified in the
General safety precaution.

12.1.1

Installation site requirements of the
indoor unit

INFORMATION

The sound pressure level is less than 70 dBA.

▪ Use

 suspension bolts

 for installation.

Spacing

. Mind the following requirements:

≥300

a

e

b

f

g

d

c

a

Service space

b

Drain pipe

c

Power supply wiring port

d

Transmission wiring port

e

Maintenance drain outlet

f

Gas pipe

g

Liquid pipe

Installation options:

Summary of Contents for FDA125A5VEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FDA125A5VEB...

Page 2: ...j atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v robky pou vaj v...

Page 3: ...s amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 following th...

Page 4: ...ical data 20 17 1 Wiring diagram 20 17 1 1 Unified wiring diagram legend 20 1 About the documentation 1 1 About this document WARNING Make sure installation servicing maintenance repair and applied ma...

Page 5: ...xternal static pressure for the unit Refer to the technical datasheet of your model for the setting range Make sure to install the canvas duct so vibrations are NOT transmitted to the duct or ceiling...

Page 6: ...and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved Children SHALL NOT play with the appliance Cleaning...

Page 7: ...t is unhealthy to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 8: ...in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used WARNING The appliance using R32 refrigerant shall be stored so as to prevent mechanical...

Page 9: ...ce CAUTION NEVER touch the internal parts of the controller Do NOT remove the front panel Some parts inside are dangerous to touch and appliance problems may happen For checking and adjusting the inte...

Page 10: ...eration During defrost operation the indoor unit fan will stop operation and the following icon will appear on the home screen The system will resume normal operation after approximately 6 to 8 minute...

Page 11: ...efrigerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used WARNING The appliance using R32 refrigerant shall be stored so...

Page 12: ...igerant if applicable in this unit is mildly flammable Refer to the outdoor unit specifications for the type of refrigerant to be used 11 1 1 To remove the accessories from the indoor unit 16 8 1 1 3...

Page 13: ...nside of the unit 4 Reinstall the interchangeable plate When installing an air inlet duct select fixing screws that stick out 5 mm on the inside of the flange to protect the air filter from damage dur...

Page 14: ...ation insulation rubber to the hanging bolts When welding make sure NOT to spatter onto the drain pan or the air filter If the metal duct passes through a metal lath wire lath or metal plate of the wo...

Page 15: ...eld supply d Hanging bars field supply Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with the correct gauge for the operating capacity of the units 100 62...

Page 16: ...ompliant with the latest version of ISO14903 can be used NOTICE The piping and other pressure containing parts shall be suitable for refrigerant Use phosphoric acid deoxidised seamless copper for refr...

Page 17: ...at is regularly turned ON and OFF by the utility 14 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are used slightly twist the stran...

Page 18: ...at the interface point between the user s supply and the public system EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment conne...

Page 19: ...est run is only completed if there is no malfunction code displayed on the user interface See the service manual for the complete list of error codes and a detailed troubleshooting guideline for each...

Page 20: ...represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective earth Connection Protective earth screw Connector A Rectifier Symbol Meaning Symbol Meani...

Page 21: ...stor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant leak detector S NPH Pressure sensor high S NPL Pressure sensor low S PH HPS Pressure switch high S PL Pressure switch...

Page 22: ......

Page 23: ......

Page 24: ...4P494410 1D 2022 10 Copyright 2017 Daikin Verantwortung f r Energie und Umwelt...

Reviews: