5 Installation

Installation and operation manual

5

FCAHG71~140FVEB
Split system air conditioners
4P429472-1 – 2015.12

(mm)

≥1500

≥2000

≥4000

≥1500

A

B

C

b

a

d

a

c

A

Minimum distance to the wall (see below)

B

Minimum and maximum distance to the floor (see below)

C

≥298 mm

: In case of installation with standard decoration

panel

≥348 mm

: In case of installation with fresh air intake kit

≥378 mm

: In case of installation with self-cleaning

decoration panel

a

Indoor unit

b

Lighting (the figure shows ceiling-mounted lighting, but
recessed lighting is also allowed)

c

Air fan

d

Static volume (example: table)

A:  Minimum  distance  to  the  wall

.  Depends  on  the  air  flow

directions towards the wall.

≥1500

≥500

≥200

a

A

A

A

b

c

a

Air outlet and corners open

b

Air outlet closed, corners open (optional blocking pad kit
required)

c

Air outlet and corners closed (optional blocking pad kit
required)

B: Minimum and maximum distance to the floor

:

▪ Minimum: 2.5 m to avoid accidental touching.

▪ Maximum: Depends on the air flow directions and the capacity

class.  Also  make  sure  the  "Ceiling  height"  field  setting
corresponds  with  the  actual  situation.  See 

"6.1  Field

settings" on page 9

.

If air flow direction…

Then B

FCAHG71

FCAHG100~140

All-round

≤3.5 m

≤4.2 m

4-way

(a)

≤4.0 m

≤4.5 m

3-way

(a)

≤3.5 m

≤4.2 m

(a)

Optional blocking kit required

5

Installation

5.1

Mounting the indoor unit

5.1.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

In  case  of  installation  with  a  fresh  air  intake  kit

.  Install  the

fresh air intake kit always 

before

 installing the unit.

Decoration  panel

.  Install  the  decoration  panel  always 

after

installing the unit.

Ceiling  strength

.  Check  whether  the  ceiling  is  strong  enough  to

support the weight of the unit. If there is a risk, reinforce the ceiling
before installing the unit.

▪ For existing ceilings, use anchors.

▪ For  new  ceilings,  use  sunken  inserts,  sunken  anchors  or  other

field supplied parts.

A

c

b

d
e

a

A

50~100 mm

: In case of installation with standard panel

100~150 mm

: In case of installation with fresh air intake kit

130~180 mm

: In case of installation with self-cleaning

decoration panel

a

Ceiling slab

b

Anchor

c

Long nut or turnbuckle

d

Suspension bolt

e

Suspended ceiling

Suspension bolts.

 Use M8~M10 suspension bolts for installation.

Attach  the  hanger  bracket  to  the  suspension  bolt.  Fix  it  securely
by using a nut and washer from the upper and lower sides of the
hanger bracket.

(mm)

780

710

a1

b

b

a2

c

a1

Nut (field supply)

a2

Double nut (field supply)

b

Washer (accessories)

c

Hanger bracket (attached to the unit)

Paper  pattern  for  installation 

(upper  part  of  the  packing).  Use

the paper pattern to determine the correct horizontal positioning. It
contains  the  necessary  dimensions  and  centres.  You  can  attach
the paper pattern to the unit.

a

c

b

d

a

Centre of the unit

b

Centre of the ceiling opening

c

Paper pattern for installation (upper part of the packing)

d

Screws (accessories)

Ceiling opening and unit

:

▪ Make sure the ceiling opening is within its limits:

Minimum

: 860 mm to be able to fit the unit.

Maximum

: 910 mm to ensure enough overlapping between the

decoration  panel  and  the  suspended  ceiling.  If  the  ceiling
opening is bigger, add extra ceiling material.

▪ Make  sure  the  unit  and  its  hanger  brackets  (suspension)  are

centred within the ceiling opening.

Summary of Contents for FCAHG71FVEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAHG71FVEB FCAHG100FVEB FCAHG125FVEB FCAHG140FVEB...

Page 2: ...a ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmi...

Page 3: ...o clean the air outlet and outside panels 15 12 2 About the refrigerant 16 12 3 After sales service and warranty 16 12 3 1 Warranty period 16 12 3 2 Recommended maintenance and inspection 16 13 Troubl...

Page 4: ...truction sheet for the connection of the optional sensor kit and decoration panels o Wire harness for the self cleaning decoration panel 3 About the units and options 3 1 About the indoor unit Use the...

Page 5: ...with a fresh air intake kit Install the fresh air intake kit always before installing the unit Decoration panel Install the decoration panel always after installing the unit Ceiling strength Check wh...

Page 6: ...on and cause water to drip 5 1 2 Guidelines when installing the drain piping Make sure condensation water can be evacuated properly This involves General guidelines Connecting the drain piping to the...

Page 7: ...temporarily connect the user interface and power supply to the unit When electrical wiring is not finished yet 1 Temporarily connect electrical wiring Remove the switch box cover a Connect the user i...

Page 8: ...3 3 To connect the electrical wiring on the indoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover For instructions on how to connect the decor...

Page 9: ...losed all corners open optional blocking pad kit required Setting Air volume when thermostat control is OFF This setting must correspond with the needs of the user It determines the fan speed of the i...

Page 10: ...ng the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION Backli...

Page 11: ...d the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit a...

Page 12: ...s used see the its wiring diagram Symbols X1M Main terminal Earth wiring 15 Wire number 15 Field wire Field cable 12 2 Connection continues on page 12 column 2 1 Several wiring possibilities Option No...

Page 13: ...grille and air filter 10 User interface CAUTION Never touch the internal parts of the controller Do not remove the front panel Some parts inside are dangerous to touch and appliance problems may happe...

Page 14: ...tem starts operating To stop 3 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the system stops operating NOTICE Do not turn off power immediately after...

Page 15: ...ce Discoloration and deformation 1 Open the suction grille 1 2 Remove the air filter 1 2 3 3 Clean the air filter Use a vacuum cleaner or wash with water If the air filter is very dirty use a soft bru...

Page 16: ...eep your air conditioner in operation as long as possible Contact your dealer for more information When asking your dealer for an intervention always state The complete model name of the air condition...

Page 17: ...rection does not correspond with the user interface display The fan direction does not swing This is because the unit is being controlled by the micro computer 13 1 4 Symptom White mist comes out of a...

Page 18: ...normal condition This continues for one minute 13 1 14 Symptom The compressor in the outdoor unit does not stop after a short heating operation This is to prevent refrigerant from remaining in the com...

Page 19: ......

Page 20: ...4P429472 1 2015 12 Copyright 2015 Daikin...

Reviews: