6.1

Field settings

Make  the  following  field  settings  so  that  they  correspond  with  the
actual installation setup and with the needs of the user:

▪ Ceiling height

▪ Air flow direction

▪ Air volume when thermostat control is OFF

▪ Time to clean air filter

Setting: Ceiling height

This  setting  must  correspond  with  the  actual  distance  to  the  floor,
capacity class and air flow directions.

▪ For 3-way and 4-way air flows (which require an optional blocking

pad  kit),  see  the  installation  manual  of  the  optional  blocking  pad
kit.

▪ For all-round air flow, use the table below.

If the distance to the floor is (m)

Then

1

FCAHG71

FCAHG100~140

M

C1

C2

≤2.7

≤3.2

13 (23)

0

01

2.7<x≤3.0

3.2<x≤3.6

02

3.0<x≤3.5

3.6<x≤4.2

03

Setting: Air flow direction

This setting must correspond with the actual used air flow directions.
See the installation manual of the optional blocking pad kit, and the
manual of the user interface.

Default: 01 (= all-round air flow)

Example: 

1

2

3

4

1

2

3

4

1

2

3

a

b

c

a

All-round air flow

b

4-way air flow (all air outlets open, 2 corners closed)
(optional blocking pad kit required)

c

3-way air flow (1 air outlet closed, all corners open)
(optional blocking pad kit required)

Setting: Air volume when thermostat control is OFF

This  setting  must  correspond  with  the  needs  of  the  user.  It
determines  the  fan  speed  of  the  indoor  unit  during  thermostat  OFF
condition.

1

Set  how  the  fan  has  to  operate  during  thermostat  OFF
condition:

If the fan has to…

Then

1

M

C1

C2

Operate as normal

(= according to settings in step 2)

11 (21)

2

01

Stop operation

(

Possible consequence: 

Warm air will go

up, and cold air will go down. During
heating operation, this might prevent the
room thermistor from going to thermostat
ON, and the user might experience cold
feet.)

02

2

If you have set that the fan has to operate as normal, also set
the air volume speed:

If you want

Then

1

M

C1

C2

During cooling
operation

LL

2

12 (22)

6

01

Setup volume

2

02

During heating
operation

LL

2

12 (22)

3

01

Setup volume

2

02

Setting: Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which the 

TIME TO CLEAN AIR FILTER

notification is displayed on the user interface. When using a wireless
user  interface,  you  must  also  set  the  address  (see  the  installation
manual of the user interface).

If you want an interval of…

(air contamination)

Then

1

M

C1

C2

±2500 h (light)

10 (20)

0

01

±1250 h (heavy)

02

No notification

3

02

(1)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

C1

: First code number

C2

: Second code number

: Default

(2)

Fan speed:

LL

: Low fan speed

Setup volume

: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button

on the user interface.

Summary of Contents for FCAHG71FVEB

Page 1: ...Installation and operation manual Split system air conditioners English Installation and operation manual Split system air conditioners FCAHG71FVEB FCAHG100FVEB FCAHG125FVEB FCAHG140FVEB...

Page 2: ...a ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmi...

Page 3: ...o clean the air outlet and outside panels 15 12 2 About the refrigerant 16 12 3 After sales service and warranty 16 12 3 1 Warranty period 16 12 3 2 Recommended maintenance and inspection 16 13 Troubl...

Page 4: ...truction sheet for the connection of the optional sensor kit and decoration panels o Wire harness for the self cleaning decoration panel 3 About the units and options 3 1 About the indoor unit Use the...

Page 5: ...with a fresh air intake kit Install the fresh air intake kit always before installing the unit Decoration panel Install the decoration panel always after installing the unit Ceiling strength Check wh...

Page 6: ...on and cause water to drip 5 1 2 Guidelines when installing the drain piping Make sure condensation water can be evacuated properly This involves General guidelines Connecting the drain piping to the...

Page 7: ...temporarily connect the user interface and power supply to the unit When electrical wiring is not finished yet 1 Temporarily connect electrical wiring Remove the switch box cover a Connect the user i...

Page 8: ...3 3 To connect the electrical wiring on the indoor unit NOTICE Follow the wiring diagram delivered with the unit located at the inside of the service cover For instructions on how to connect the decor...

Page 9: ...losed all corners open optional blocking pad kit required Setting Air volume when thermostat control is OFF This setting must correspond with the needs of the user It determines the fan speed of the i...

Page 10: ...ng the BRC1E52 or BRC1E53 user interface When using any other user interface see the installation manual or service manual of the user interface NOTICE Do not interrupt the test run INFORMATION Backli...

Page 11: ...d the currently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit a...

Page 12: ...s used see the its wiring diagram Symbols X1M Main terminal Earth wiring 15 Wire number 15 Field wire Field cable 12 2 Connection continues on page 12 column 2 1 Several wiring possibilities Option No...

Page 13: ...grille and air filter 10 User interface CAUTION Never touch the internal parts of the controller Do not remove the front panel Some parts inside are dangerous to touch and appliance problems may happe...

Page 14: ...tem starts operating To stop 3 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the system stops operating NOTICE Do not turn off power immediately after...

Page 15: ...ce Discoloration and deformation 1 Open the suction grille 1 2 Remove the air filter 1 2 3 3 Clean the air filter Use a vacuum cleaner or wash with water If the air filter is very dirty use a soft bru...

Page 16: ...eep your air conditioner in operation as long as possible Contact your dealer for more information When asking your dealer for an intervention always state The complete model name of the air condition...

Page 17: ...rection does not correspond with the user interface display The fan direction does not swing This is because the unit is being controlled by the micro computer 13 1 4 Symptom White mist comes out of a...

Page 18: ...normal condition This continues for one minute 13 1 14 Symptom The compressor in the outdoor unit does not stop after a short heating operation This is to prevent refrigerant from remaining in the com...

Page 19: ......

Page 20: ...4P429472 1 2015 12 Copyright 2015 Daikin...

Reviews: