8 Disposal

Installation manual

12

FBA35~140A2VEB

Split system air conditioners

4P456962-1C – 2017.04

1

Perform introductory steps.

#

Action

1

Open the liquid stop valve (A) and gas stop valve (B)
by removing the stem cap and turning
counterclockwise with a hex wrench until it stops.

A

B

2

Close the service cover to prevent electric shocks.

3

Turn ON power for at least 6 hours before starting
operation to protect the compressor.

4

On the user interface, set the unit to cooling operation
mode.

2

Start the test run

#

Action

Result

1

Go to the home menu.

Cool

Set to

28

°C

2

Press at least 4 seconds.

The Service Settings menu
is displayed.

3

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

4

Press.

Test Operation is
displayed on the home
menu.

Cool

Return

Setting

Test Operation

5

Press within 10 seconds.

Test run starts.

3

Check operation for 3 minutes.

4

Stop the test run.

#

Action

Result

1

Press at least 4 seconds.

The Service Settings menu
is displayed.

2

Select Test Operation.

Return

Setting

Service Settings                   1/3

Test Operation

Maintenance Contact

Field Settings

Demand

Min Setpoints Differential

Group Address

3

Press.

The unit returns to normal
operation, and the home
menu is displayed.

7.3

Error codes when performing a
test run

If  the  installation  of  the  outdoor  unit  has  NOT  been  done  correctly,
the following error codes may be displayed on the user interface:

Error code

Possible cause

Nothing displayed

(the currently set
temperature is not
displayed)

▪ The  wiring  is  disconnected  or  there  is  a

wiring  error  (between  power  supply  and
outdoor  unit,  between  outdoor  unit  and
indoor  units,  between  indoor  unit  and
user interface).

▪ The  fuse  on  the  outdoor  or  indoor  unit

PCB has blown.

E3, E4 or L8

▪ The stop valves are closed.

▪ The air inlet or air outlet is blocked.

E7

There is a missing phase in case of three-
phase power supply units.

Note: 

Operation will be impossible. Turn

OFF the power, recheck the wiring, and
switch two of the three electrical wires.

L4

The air inlet or air outlet is blocked.

U0

The stop valves are closed.

U2

▪ There is a voltage imbalance.

▪ There  is  a  missing  phase  in  case  of

three-phase  power  supply  units. 

Note:

Operation  will  be  impossible.  Turn  OFF
the power, recheck the wiring, and switch
two of the three electrical wires.

U4 or UF

The inter-unit branch wiring is not correct.

UA

The outdoor and indoor unit are
incompatible.

8

Disposal

NOTICE

Do not try to dismantle the system yourself: the dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  must  comply  with  applicable  legislation.  Units  must
be  treated  at  a  specialised  treatment  facility  for  reuse,
recycling and recovery.

9

Technical data

▪ A 

subset

  of  the  latest  technical  data  is  available  on  the  regional

Daikin website (publicly accessible).

▪ The 

full  set

  of  latest  technical  data  is  available  on  the  Daikin

extranet (authentication required).

Summary of Contents for FBA35A2VEB

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FBA35A2VEB FBA50A2VEB FBA60A2VEB FBA71A2VEB FBA100A2VEB FBA125A2VEB FBA140A2VEB...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...get audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay perso...

Page 4: ...mmable gas may leak out If the gas leaks out and stays around the air conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is l...

Page 5: ...f the flange to protect the air filter from damage during maintenance of the filter a b c 5 mm a Air inlet duct b Inside of the flange c Fixing screw Ceiling strength Check whether the ceiling is stro...

Page 6: ...crews a b b a e e d d c a Connection screw accessory b Flange field supply c Main unit d Insulation field supply e Aluminium tape field supply Filter Be sure to attach an air filter inside the air pas...

Page 7: ...pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with cable ties 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c...

Page 8: ...The R32 refrigerant if applicable in this unit is mildly flammable a a Refer to the outdoor unit specifications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as p...

Page 9: ...ctrical interference the distance between both wiring should always be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power su...

Page 10: ...1 1 22 RZQSG71L RZASG100M 2 1 65 2 RZQSG100L RZASG125M 4 3 33 3 2 32 2 2 05 RZQSG125L RZASG140M 4 3 33 3 2 32 2 2 05 RZQSG140L Combination FBA100A FBA125A FBA140A RZAG71M RZQG71L RZAG100M 1 0 73 RZQG1...

Page 11: ...tem before the following checks are OK You read the complete installation instructions as described in the installer reference guide The indoor units are properly mounted In case a wireless user inter...

Page 12: ...unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Nothing displayed the currently set temperature is not displayed The wiring...

Page 13: ...ADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECT...

Page 14: ......

Page 15: ......

Page 16: ...4P456962 1C 2017 04 Copyright 2017 Daikin...

Reviews: