7 Commissioning

Installation manual

11

FBA35~140A2VEB
Split system air conditioners
4P456962-1C – 2017.04

Change  the  second  code  number  according  to  the  external  static
pressure of the duct to be connected as in table below.

M

C1

C2

External static pressure

FBA

35

50

60

71

13(23)

6

01

30

30

30

30

02

03

30

30

30

30

04

40

40

40

40

05

50

50

50

50

06

60

60

60

60

07

70

70

70

70

08

80

80

80

80

09

90

90

90

90

10

100

100

100

100

11

110

110

110

110

12

120

120

120

120

13

130

130

130

130

14

140

140

140

140

15

150

150

150

150

M

C1

C2

External static pressure

FBA

100

125

140

13(23)

6

01

40

50

50

02

03

04

40

05

50

50

50

06

60

60

60

07

70

70

70

08

80

80

80

09

90

90

90

10

100

100

100

11

110

110

110

12

120

120

120

13

130

130

130

14

140

140

140

15

150

150

150

Time to clean air filter

This setting must correspond with the air contamination in the room.
It determines the interval at which the 

TIME TO CLEAN AIR FILTER

notification is displayed on the user interface. When using a wireless
user  interface,  you  must  also  set  the  address  (see  the  installation
manual of the user interface).

If you want an interval of…

(air contamination)

Then

2

M

C1

C2

±2500 h (light)

10(20)

0

01

±1250 h (heavy)

02

No notification

3

02

2 user interfaces:

 When using 2 user interfaces one must be set

to "MAIN" and the other to "SUB".

7

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

7.1

Checklist before commissioning

Do NOT operate the system before the following checks are OK:

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

In case a wireless user interface is used: The 

indoor unit

decoration panel

 with infrared receiver is installed.

The 

outdoor unit

 is properly mounted.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed  according  to  this  document,  and  have  not  been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

The 

insulation resistance

 of the compressor is OK.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

7.2

To perform a test run

This  task  is  only  applicable  when  using  the  BRC1E52  or  BRC1E53
user  interface.  When  using  any  other  user  interface,  see  the
installation manual or service manual of the user interface.

NOTICE

Do not interrupt the test run.

INFORMATION

Backlight.

  To  perform  an  ON/OFF  action  on  the  user

interface,  the  backlight  does  not  need  to  be  lit.  For  any
other  action,  it  needs  to  be  lit  first.  The  backlight  is  lit  for
±30 seconds when you press a button.

(2)

Field settings are defined as follows:

M

: Mode number – 

First number

: for group of units – 

Number between brackets

: for individual unit

C1

: First code number

C2

: Second code number

: Default

Summary of Contents for FBA35A2VEB

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FBA35A2VEB FBA50A2VEB FBA60A2VEB FBA71A2VEB FBA100A2VEB FBA125A2VEB FBA140A2VEB...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...get audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay perso...

Page 4: ...mmable gas may leak out If the gas leaks out and stays around the air conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is l...

Page 5: ...f the flange to protect the air filter from damage during maintenance of the filter a b c 5 mm a Air inlet duct b Inside of the flange c Fixing screw Ceiling strength Check whether the ceiling is stro...

Page 6: ...crews a b b a e e d d c a Connection screw accessory b Flange field supply c Main unit d Insulation field supply e Aluminium tape field supply Filter Be sure to attach an air filter inside the air pas...

Page 7: ...pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with cable ties 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c...

Page 8: ...The R32 refrigerant if applicable in this unit is mildly flammable a a Refer to the outdoor unit specifications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as p...

Page 9: ...ctrical interference the distance between both wiring should always be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power su...

Page 10: ...1 1 22 RZQSG71L RZASG100M 2 1 65 2 RZQSG100L RZASG125M 4 3 33 3 2 32 2 2 05 RZQSG125L RZASG140M 4 3 33 3 2 32 2 2 05 RZQSG140L Combination FBA100A FBA125A FBA140A RZAG71M RZQG71L RZAG100M 1 0 73 RZQG1...

Page 11: ...tem before the following checks are OK You read the complete installation instructions as described in the installer reference guide The indoor units are properly mounted In case a wireless user inter...

Page 12: ...unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Nothing displayed the currently set temperature is not displayed The wiring...

Page 13: ...ADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECT...

Page 14: ......

Page 15: ......

Page 16: ...4P456962 1C 2017 04 Copyright 2017 Daikin...

Reviews: