6 Configuration
Installation manual
10
FBA35~140A2VEB
Split system air conditioners
4P456962-1C – 2017.04
▪
Master unit:
Be sure to connect the wiring when combining with a
simultaneously operating multi-type in group control.
▪ Use separate power only in case of following combination:
1× RXS35L or RXM35M
2× RR100/125B or RQ100/125B
2× RR100/125B or RQ100/125B
4× RZQ200C
3× RZQ200C
3× RZQ200C
2×F RZQ200C
4× RZQ200C
2×F RZQ200C
▪
EN/IEC 61000‑3‑12
provided that the short-circuit power S
sc
is
greater than or equal to the minimum S
sc
value at the interface
point between the user's supply and the public system.
▪ EN/IEC
61000‑3‑12
=
European/International
Technical
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16 A and ≤75 A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply
with a short-circuit power S
sc
greater than or equal to the
minimum S
sc
value.
▪ Ensure that equipment is connected only to a supply with a short-
circuit power S
sc
greater than or equal to S
sc
in table below.
Combination
FBA35A
FBA50A
FBA60A
FBA71A
RZAG71M
2 (—)
—
—
1 (—)
RZQG71L
RZAG100M
3 (2.31)
2 (1.30)
—
—
RZQG100L
RZAG125M
4 (3.33)
3 (2.32)
2 (2.05)
—
RZQG125L
RZAG140M
4 (3.33)
3 (2.32)
—
2 (2.05)
RZQG140L
RZASG71M
2 (1.10)
—
—
1 (1.22)
RZQSG71L
RZASG100M
2 (1.65)
2 (—)
—
—
RZQSG100L
RZASG125M
4 (3.33)
3 (2.32)
2 (2.05)
—
RZQSG125L
RZASG140M
4 (3.33)
3 (2.32)
—
2 (2.05)
RZQSG140L
Combination
FBA100A
FBA125A
FBA140A
RZAG71M
—
—
—
RZQG71L
RZAG100M
1 (0.73)
—
—
RZQG100L
RZAG125M
—
1 (0.74)
—
RZQG125L
RZAG140M
—
—
1 (0.74)
RZQG140L
RZASG71M
—
—
—
RZQSG71L
RZASG100M
1 (—)
—
—
RZQSG100L
RZASG125M
—
1 (0.74)
—
RZQSG125L
RZASG140M
—
—
1 (0.74)
RZQSG140L
INFORMATION
In case of group control it is not necessary to address the
indoor unit. The address is automatically set when the
power is activated.
6
Configuration
6.1
Field settings
Make the following field settings so that they correspond with the
actual installation setup and with the needs of the user:
▪ External static pressure setting using:
▪ Airflow automatic adjustment setting
▪ User interface
▪ Time to clean air filter
To set airflow automatic adjustment
▪ When the air conditioning unit is running in fan operation mode:
1
Stop the air conditioning unit.
2
Set second code number to 03.
Setting content:
Then
2
M
C1
C2
Airflow adjustment is OFF
11(21)
7
01
Press ON/OFF to return to normal operating
mode.
Possible consequence:
The operation lamp
will light up and the unit will start the fan
operation for airflow automatic adjustment.
03
Operation stops after 1 to 8 minutes.
Possible consequence:
Setting is finished
and the operation lamp will be off.
02
If there is no change after airflow adjustment, perform the setting
again.
User interface
Check the indoor unit setting: the second code number of mode
11(21) must be set to 01.
(2)
Field settings are defined as follows:
▪
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
▪
C1
: First code number
▪
C2
: Second code number
▪
: Default