5 Installation

Installation manual

7

FBA35~140A2VEB
Split system air conditioners
4P456962-1C – 2017.04

Rising  piping

.  If  necessary  to  make  the  slope  possible,  you  can

install rising piping.

▪ Drain  hose  inclination:  0~75  mm  to  avoid  stress  on  the  piping

and to avoid air bubbles.

▪ Rising  piping:  ≤300  mm  from  the  unit,  ≤625  mm  perpendicular

to the unit.

≤625

≤300

0~75

1000~1500

(mm)

b

a

b

c

a

d

d

a

Metal clamp (accessory)

b

Drain hose (accessory)

c

Rising drain piping (vinyl pipe of 25 mm nominal diameter
and 32 mm outer diameter) (field supply)

d

Hanging bars (field supply)

Combining  drain  pipes.

  You  can  combine  drain  pipes.  Make

sure to use drain pipes and T-joints with the correct gauge for the
operating capacity of the units.

≥100

≤625

(mm)

a

a

T-joint

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Push  the  drain  hose  as  far  as  possible  over  the  drain  pipe
connection.

2

Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.

3

Check for water leaks (see To check for water leaks).

4

Install the insulation piece (drain pipe).

5

Wind  the  large  sealing  pad  (=  insulation)  around  the  metal
clamp and drain hose, and fix it with cable ties.

6

Connect the drain piping to the drain hose.

4 mm

A

A'

A-A'

A

A'

f

6

5

2

c

e

4

b

a

d

b

a

d

c

3

1

2~6

1

a

Drain pipe connection (attached to the unit)

b

Drain hose (accessory)

c

Metal clamp (accessory)

d

Large sealing pad (accessory)

e

Insulation piece (drain pipe) (accessory)

f

Drain piping (field supply)

NOTICE

▪ Do NOT remove the drain pipe plug. Water might leak

out.

▪ Use  the  drain  outlet  only  to  discharge  the  water  if  the

drain pump is not used or before maintenance.

▪ Insert  and  remove  the  drain  plug  gently.  Excessive

force may deform the drain socket of the drain pan.

Pull out the plug.

▪ Do NOT wiggle the plug up and down.

a

Push in the plug.

▪ Set the plug and push it in using a Phillips screwdriver.

a

b

a

Drain plug

b

Phillips screwdriver

To check for water leaks

The  procedure  differs  depending  on  whether  electrical  wiring  is
already finished. When electrical wiring is not finished yet, you need
to  temporarily  connect  the  user  interface  and  power  supply  to  the
unit.

When electrical wiring is not finished yet

1

Temporarily connect electrical wiring.

2

Remove the switch box cover (a).

3

Connect  the  single-phase  power  supply  (50  Hz,  230  V)  to
connections  No.  1  and  No.  2  on  the  terminal  block  for  power
supply (d) and earth (c).

4

Reattach the switch box cover (a).

Summary of Contents for FBA35A2VEB

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FBA35A2VEB FBA50A2VEB FBA60A2VEB FBA71A2VEB FBA100A2VEB FBA125A2VEB FBA140A2VEB...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...get audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay perso...

Page 4: ...mmable gas may leak out If the gas leaks out and stays around the air conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is l...

Page 5: ...f the flange to protect the air filter from damage during maintenance of the filter a b c 5 mm a Air inlet duct b Inside of the flange c Fixing screw Ceiling strength Check whether the ceiling is stro...

Page 6: ...crews a b b a e e d d c a Connection screw accessory b Flange field supply c Main unit d Insulation field supply e Aluminium tape field supply Filter Be sure to attach an air filter inside the air pas...

Page 7: ...pipe 5 Wind the large sealing pad insulation around the metal clamp and drain hose and fix it with cable ties 6 Connect the drain piping to the drain hose 4 mm A A A A A A f 6 5 2 c e 4 b a d b a d c...

Page 8: ...The R32 refrigerant if applicable in this unit is mildly flammable a a Refer to the outdoor unit specifications for the type of refrigerant to be used Pipe length Keep refrigerant piping as short as p...

Page 9: ...ctrical interference the distance between both wiring should always be at least 50 mm NOTICE Be sure to keep the power line and transmission line apart from each other Transmission wiring and power su...

Page 10: ...1 1 22 RZQSG71L RZASG100M 2 1 65 2 RZQSG100L RZASG125M 4 3 33 3 2 32 2 2 05 RZQSG125L RZASG140M 4 3 33 3 2 32 2 2 05 RZQSG140L Combination FBA100A FBA125A FBA140A RZAG71M RZQG71L RZAG100M 1 0 73 RZQG1...

Page 11: ...tem before the following checks are OK You read the complete installation instructions as described in the installer reference guide The indoor units are properly mounted In case a wireless user inter...

Page 12: ...unit has NOT been done correctly the following error codes may be displayed on the user interface Error code Possible cause Nothing displayed the currently set temperature is not displayed The wiring...

Page 13: ...ADPROTECTOR D V D DIODE Q M THERMOSWITCH DB DIODEBRIDGE R RESISTOR DS DIPSWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECT...

Page 14: ......

Page 15: ......

Page 16: ...4P456962 1C 2017 04 Copyright 2017 Daikin...

Reviews: