background image

English

20

10. TEST OPERATION

(1) Make sure the service lids are closed on the indoor and outdoor units.
(2) Refer to the section of “FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUC-

TION AND CHECK AFTER INSTALLATION IS FINISHED” . 

After finishing the construction of refrigerant piping, drain piping, and electric wiring, conduct test operation 
accordingly to protect the unit.

10-1 HOW TO TEST OPERATION

1

Open the gas side stop valve.

2

Open the liquid side stop valve.

3

Electrify for more than 6 hours (Not required in case of a unit exclusively designed for cooling only).

4

Set to cooling operation with the remote controller and start operation by pushing ON/OFF button 
(

).

5

Press INSPECTION/TEST OPERATION button (

) 4 times (2 times for wireless remote controller) 

and operate at Test Operation mode for 3 minutes.

6

Press AIR FLOW DIRECTION ADJUST button (

) to make sure the unit is in operation.

7

Press INSPECTION/TEST OPERATION button (

) and operate normally.

8

Confirm function of unit according to the operation manual.

PRECAUTIONS

Refer to the diagnoses below if the unit does not operate properly.

After completing the test run, press the INSPECTION/TEST OPERATION button once to put the unit 
in inspection mode, and make sure the malfunction code is “00” (=normal).
If the code reads anything other than “00”, refer to the malfunction diagnoses below.

10-2 HOW TO DIAGNOSE FOR PROBLEMS

With the power on. Troubles can be monitored on the remote controller or the LED’s on the PC 
board of the indoor unit.

Trouble shooting with the display on the liquid crystal display remote controller.

1

With the wired remote controller. (NOTE 1) 
When the operation stops due to trouble, operation lamp flashed, and “ 

 ” and the error code are

indicated on the liquid crystal display . In such a case, diagnose the fault contents by referning to
the table on the Error code list it case of group control, the unit No. is displayed so that the indoor
unit no with the trouble can be recognized. (NOTE 2)

2

With the wireless remote controller.
(Refer also to the operation manual attached to the wireless remote controller)
When the operation stops due to trouble. the display on the indoor unit flashes. In such a case, diag-
nose the fault contents with the table on the Error code list looking for the error code which can be
found by following procedures. (NOTE 2)

(1)

Press the INSPECTION /TEST OPERATION button, “ 

 ” is displayed and  “ 0 ” flashes.

(2)

Press the PROGRAMMING TIME button and find the unit No. which stopped due to trouble.
Number of beeps 3 short beeps ......... Perform all the following operations 

1 short beep ........... Perform (3) and (6)
1 long beep ............ No trouble

(3)

Press the OPERATION MODE SELECTOR button and upper figure of the error code flashes.

(4)

Continue pressing the PROGRAMMING TIME button unit it makes 2 short beeps and find the upper 
code.

(5)

Press the OPERATION MODE SELECTOR button and lower figure of the error code flashes.

(6)

Continue pressing the PROGRAMMING TIME button unit it makes a long beep and find the lower 
code.

A long beep indicate the error code.

Trouble shooting with the LEDs on the PC board (Refer to Table 9 )
The following checking can be made with the service monitor LEDs (green). (Normal when flashing) 

: LED on         

: LED off       

: LED flashing

: Not used for trouble shooting

TEST

TEST

01_EN_3P083811-3T.fm  Page 20  Friday, September 3, 2004  10:17 AM

Summary of Contents for FAY71LVE

Page 1: ...RUCTIONS AVANT L INSTALLATION CONSERVER CE MANUEL A PORTEE DE MAIN POUR REFERENCE ULTERIEURE LEA CUIDADOSAMENTE ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN...

Page 2: ...ller andra normgivande dokument under f ruts ttning att anv ndning sker i verensst mmelse med v ra instruktioner respektive utstyr er i overensstemmelse med f lgende standard er eller andre normgivend...

Page 3: ...s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i...

Page 4: ...ion work Do not try to install the machine yourself Improper installation may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Impr...

Page 5: ...ater leakage b where corrosive gas such as sulfurous acid gas is produced Corroding copper pipes or soldered parts may result in refrigerant leakage c near machinery emitting electromagnetic waves Ele...

Page 6: ...he Installation manual included with the remote controllers Table 1 NOTE If the customer wishes to use a remote controller that is not listed above select a suitable remote controller after consulting...

Page 7: ...likely to occur Check Are the indoor and outdoor unit fixed firmly The units may drop vibrate or make noise Is the gas leak test finished It may result in insufficient cooling Is the unit fully insul...

Page 8: ...the paper pattern for installation 3 so refer to it when con sidering the necessity for reinforcing the location 3 The indoor unit may not be directly installed on the wall Use the attached installati...

Page 9: ...r a total of 2 bolts on either side If dealing with concrete use commercially available foundation bolts M8 M10 3 If using the left bottom left right or bottom right positions for the piping cut out t...

Page 10: ...ot to catch the horizontal flaps remove the front grill by pulling in the direction of the arrow Remove the drain plug the insulation tubing and the drain hose from the drain pan and replace Refer to...

Page 11: ...e wiring the units ground wirings Then fix them securely on the refrigerant pipe Seal the piping through hole with putty corking material 9 Push on both bottom edges of the indoor unit using both hand...

Page 12: ...lare suitable for the type of refrigerant Apply ester oil or ether oil around the flare section before connecting To prevent dust moisuture or other foreign matter from infiltrating the tube either pi...

Page 13: ...out nitrogen substitution NOTE 1 or while inserting nitrogen into the refrigerant piping NOTE 2 Once this is done connect the indoor unit with a flared or a flanged connection NOTES 1 Refer to the Man...

Page 14: ...section of the drain hose which is indoors Refer to Fig 17 Make sure the diameter of the piping is the same as the piping hard vinyl chloride nominal diameter 13mm or bigger Insulating tubing tape In...

Page 15: ...r also to WIRING DIAGRAM attached to the unit body For remote controller wiring details refer to the installation manual attached to the remote controller All wiring must be performed by an authorized...

Page 16: ...in case of no protection 2 For European and Asian market Vinyl cord with sheath or cable Insulated thickness 1 mm or more For Australian regular Shield wire Insulated thickness 1 mm or more Wire Size...

Page 17: ...en firmly secure using the included clamp small 5 according to the figure Refer to Fig 20 1 2 3 REMOTE CNTRL TRANSMISSION WIRING F1 F2 P1 P2 Fig 20 In case of using the power supply terminal together...

Page 18: ...round crimp style terminals for connecting wires to the power supply terminal block Refer to Fig 21 If unavailable observe the following points when wiring Do not connect wires of different gauge to t...

Page 19: ...ntroller that suits the indoor unit which has the most functions as attached swing flap 4 For simultaneous operation system connect the remote controller cord to the master unit 1 2 3 P1 P2 1 2 3 P1 P...

Page 20: ...ress setting is necessary Refer to the installation manual attached to the wireless remote controller for setting instructions 9 3 SETTING INDOOR UNIT NUMBER OF SIMULTANEOUS OPERATION SYSTEM When usin...

Page 21: ...to 9 1 to 9 2 for the slave unit 7 Turn off the main power supply switch after 6 8 If there is more than one slave unit repeat steps 4 to 7 9 Detach the remote controller from the slave unit after th...

Page 22: ...l block for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and the...

Page 23: ...l display remote controller 1 With the wired remote controller NOTE 1 When the operation stops due to trouble operation lamp flashed and and the error code are indicated on the liquid crystal display...

Page 24: ...ype of indoor or outdoor unit the malfunction code may or may not be displayed Microcomputer normal monitor Transmission normal monitor Details HAP H1P HBP H2P FAY L FAYP L FAQ BUV1B Indoor unit is no...

Page 25: ...ntion outdoor unit Compressor possibly locked LC Transmission malfunction between the outdoor control units inverters outdoor unit P1 Open phase outdoor unit P3 PC board temperature sensor malfunction...

Page 26: ...NIT 2 NOTE 4 3 WIRED REMOTE CONTROLLER 4 CONTROL BOX INDOOR 5 RECEIVER DISPLAY UNIT ATTACHED TO WIRELESS REMOTE CONTROLLER 6 IN CASE OF SIMULTANEOUS OPERATION SYSTEM 7 INDOOR UNIT MASTER 8 INDOOR UNIT...

Page 27: ...T EMITTING DIODE DEFROST ORANGE SELECTOR SWITCH MAIN SUB SELECTOR SWITCH WIRELESS ADDRES SET X15A X35A CONNECTOR FLOAT SWITCH CONNECTOR GROUP CONTROL ADAPTOR SS1 R1T SELECTOR SWITCH MAIN SUB THERMISTO...

Page 28: ...IODE DEFROST ORANGE SELECTOR SWITCH MAIN SUB SELECTOR SWITCH WIRELESS ADDRES SET X15A X35A CONNECTOR FLOAT SWITCH CONNECTOR GROUP CONTROL ADAPTOR SS1 R1T SELECTOR SWITCH MAIN SUB THERMISTOR AIR WIRING...

Page 29: ...AIN SUB SELECTOR SWITCH WIRELESS ADDRES SET X15A X35A CONNECTOR FLOAT SWITCH CONNECTOR GROUP CONTROL ADAPTOR R1T SS1 THERMISTOR AIR SELECTOR SWITCH MAIN SUB WIRING DIAGRAM 2 IN CASE USING CENTRAL REMO...

Page 30: ...0412 HT 3P083811 3U EM02A063D 00_CV_3P083811 3U fm Page 2 Tuesday November 30 2004 4 30 PM...

Reviews: